CPM2A Specifications
20
Item Specification
Basic
interrupts Interrupt
processing External interrupts: 4
(Shared by the external interrupt inputs (counter mode) and the quick-response inputs.)
Interval timer
interrupts 1 (Scheduled Interrupt Mode or Single Interrupt Mode)
High-
speed
High-speed
counter One high-speed counter: 20 kHz single-phase or 5 kHz two-phase (linear count method)
Counter interrupt: 1 (set value comparison or set-value range comparison)
coun
er Interrupt
Inputs
(counter
mode)
Four inputs (Shared with external interrupt inputs (counter mode) and quick-response inputs.)
Counter interrupts: 4 (Shared by the external interrupt inputs and quick-response inputs.)
Pulse output Two points with no acceleration/deceleration, 10 Hz to 10 kHz each, and no direction control.
One point with waveform acceleration/deceleration, 10 Hz to 10 kHz, and direction control.
Two points with variable duty-ratio outputs using PWM(––).
(Pulse outputs can be used with transistor outputs only, they cannot be used with relay outputs.)
Synchronized pulse
control One point:
A pulse output can be created by combining the high-speed counter with the pulse output and
multiplying the frequency of the input pulses from the high-speed counter by a fixed factor.
(This output is possible with transistor outputs only, it cannot be used with relay outputs.)
Quick-response inputs Four points (Min. input pulse width: 50 µs min.)
Analog controls 2 controls, setting range: 0 to 200
Input time constant Can be set for all input points.
(1 ms, 2 ms, 3 ms, 5 ms, 10 ms, 20 ms, 40 ms, or 80 ms; default setting: 10 ms)
Clock function Shows the year, month, day of the week, day, hour, minute, and second. (Battery backup)
Communications
functions Built-in peripheral port:
Supports host link, peripheral bus, no-protocol, or Programming Console connections.
Built-in RS-232C port:
Supports host link, no-protocol, 1:1 Slave Unit link, 1:1 Master Unit link, or 1:1 NT Link
connections.
Functions provided by
Expansion Units Analog I/O Unit: Provides 2 analog inputs and 1 analog output.
CompoBus/S I/O Link Unit: Provides 8 inputs and 8 outputs as a CompoBus/S Slave.
Temperature Sensor Units: Provide 2 or 4 thermocouple inputs, or 2 or 4 temperature-resistance
thermometer inputs.
Memory protection HR area, AR area, program contents, read/write DM area contents, and counter values
maintained during power interruptions.
Memory backup Flash memory:
Program, read-only DM area, and PC Setup
Battery backup:
The read/write DM area, HR area, AR area, and counter values are backed up by a battery.
(Battery life is approximately 5 years at an ambient temperature of 25°C.)
Self-diagnostic functions CPU Unit failure (watchdog timer), I/O bus error, and memory failure, battery error
Program checks No END instruction and programming errors are checked at the start of operation.