5/23
2CDC110004C0207
5
Analog signal converters
CC-U/STD, CC-U/RTD, CC-U/TC
Technical data
Type CC-U/STD CC-U/RTD 3) CC-U/TC
Input circuits - Analog inputs J-G-H Current Voltage Potentio-
meter Temperature sensors Thermocouples
(IEC 584-1 and 2)
Input signal 0-20 mA 0-100 mV 470 - PT10, PT100, PT1000 TC.K TC.J
4-20 mA 0-1 V 1 M 2) (IEL 751 and JICC 1604) TC.T TC.S
10-50 mA 0-5 V TC.E TC.N
0-1 mA 1-5 V TC.R TC.B
0-10 V
2-10 V
± 10 V
Limitation of input signals ± 55 mA ± 11 V - -
Rated input range
---
Max. temperature adjustable:
6-60 °C for PT1000
50-500 °C for PT100
500-850 °C for PT10
refer to temperature specs.
of individual thermocouples
Infl uence of line resistance - - - 0.015 °C/< 0.01 % / 100
Gain adjustment range
(universal devices)
0.9-
110 mA
45 mV -
22 V - see DIP switch settings
Offset adjustment range (universal devices) -137.5...+62.5 % ± 5 % ± 10 %
Input impedance for different ranges - -
without detection of input signal interruption
51 6 M3 G--
with detection of input signal interruption
51 3.5 M9.5 G--
Suppression at 50 Hz - - - - > 40 dB
Common-mode rejection - - - 120 dB 105 dB
Output circuits - Analog outputs D-F, A-C Current Voltage
Output signal 0-20 mA, 4-20 mA 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V
Output burden 600 4.7 K
Accuracy 1) ±0.1 % of full-scale ±0.2 % of full-scale ±0.1 % of full-scale
Residual ripple - < 0.15 % -
Response time 200 μs 10 ms 200 ms
Transmission frequency 1 kHz 80 Hz 2 Hz (to -3 dB)
Supply circuits K-M
Rated supply voltage 24-48 V DC 110-240 V AC
Supply voltage range 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC
Supply voltage tolerance DC: -15...+15 % AC: -15...+10 %
Rated frequency 0 Hz or 50/60 Hz
Power consumption 2 W at 24 V DC 4.5 VA at 230 V AC
Indication of operational states
Supply voltage U: green LED
General data
Ambient temperature range operation / storage -20...+60 °C / -40...+80 °C
Temperature coeffi cient ±150 ppm/°C ±250 ppm/°C ±200 ppm/°C at min. offset
±400 ppm/°C at max. offset
Mounting position any
Mounting DIN rail (IEC/EN 60715), snap-on mounting / screw mounting with adapter
Electrical connection
Wire size rigid plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
fi ne-strand with(out) wire end ferrule plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
Stripping length 7 mm (0.28 inch)
Tightening torque 0.4 Nm (3.5 ib.in)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD)
IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic fi eld
(HF radiation resistance)
IEC/EN 61000-4-3 10 V/m
fast transients (Burst)
IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge)
IEC/EN 61000-4-5 2 kV / 1 kV
HF line emission
IEC/EN 61000-4-6 10 V
Interference emission
EN 61000-6-4 Class B
Isolation data
Isolation test (between all isolated circuits) 1.5 kV
Test voltage (between all isolated circuits) 1.5 kV / 50 Hz
1) includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
2) Detection of an input signal break (fail safe) and resistance > 10 k results in a linearity of 0,2 %.
3) When connecting a 2-wire sensor, the terminals J and H have to be jumpered.