https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page1/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection, consisting of protective plug and base element, with integrated status indicator and knife
disconnection for a 2-wire floating signal circuit with high nominal current.
Your advantages
Space-saving and cost-saving with a narrow overall width of just 6mm
Continuous monitoring of protective devices, plus mechanical status indicator with optional remote signaling
Finding the right product for all possible requirements in MCR applications is easy, thanks to the complete range of products with customized
features
Easy testing and documentation with CHECKMASTER2 with pluggable protective modules
The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4055626134864
Weight per Piece (excluding packing) 40.000 g
Custom tariff number 85363010
Country of origin Germany
Technical data
Dimensions
Height 105.8 mm
Width 6.2 mm +0.1mm
Depth 100 mm (incl. DIN rail 7.5mm)
https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page2/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %
Altitude ≤ 4000 m (amsl (above mean sea level))
Degree of protection IP20
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
light grey RAL 7035
Mounting type DIN rail: TH 35 - 7.5 mm
Type DIN rail module, two-section, divisible
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN24 VDC
Maximum continuous voltage UC30 VDC
21 VAC
Rated current 6 A (55°C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line) 0.5 kA
Nominal discharge current In (8/20) µs (line-earth) 5 kA
Pulse discharge current Iimp (10/350)µs (line-earth) 0.5 kA
Total discharge current Itotal (8/20)µs 5 kA
Voltage protection level Up (line-line) ≤ 50 V (C1 - 1 kV/500 A)
≤ 45 V (C3 - 25 A)
≤ 50 V (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 1.35 kV (C1 - 1 kV/500 A)
≤ 1.45 kV (C2 - 10 kV / 5 kA)
≤ 850 V (C3 - 25 A)
≤ 1.1 kV (C3 - 100 A)
https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page3/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Technical data
Protective circuit
Response time tA (line-line) ≤ 1 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3dB), sym. in 150Ω system typ. 1 MHz
Capacity (line-earth) typ. 2.2 nF
Resistance per path ≤ 100 mΩ
Surge protection fault message optical
Max. required back-up fuse 6.3 A (FF)
Impulse durability (line-line) C1 - 1kV / 500A
C3 - 100A
Impulse durability (line-earth) C1 - 1kV / 500A
C2 - 10kV / 5kA
C3 - 100A
D1 - 500A
Pulse reset time (line-earth) ≤ 40ms
Connection data
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page4/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Pictogram
U
Diagram
I [A]
T [°C]
6
4
2
8
40 907050 60 80
Dimensional drawing
92,5
100
105,8 6,2⁺⁰¹
Circuit diagram
4
5
6
1
2
3
!
unprotected protected
Classifications
eCl@ss
eCl@ss 10.0.1 27130807
eCl@ss 11.0 27130807
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130800
eCl@ss 7.0 27130807
eCl@ss 9.0 27130807
ETIM
ETIM 2.0 EC000943
ETIM 3.0 EC000943
ETIM 4.0 EC000943
ETIM 6.0 EC000943
ETIM 7.0 EC000943
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page5/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Classifications
UNSPSC
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
UNSPSC 18.0 39121620
UNSPSC 19.0 39121620
UNSPSC 20.0 39121620
UNSPSC 21.0 39121620
Approvals
Approvals
Approvals
DNV GL / CSA / UL Listed / CSAus / cCSAus
Ex Approvals
Approval details
DNV GL https://approvalfinder.dnvgl.com/ TAE000027G
CSA http://www.csagroup.org/services-industries/product-listing/ 70136717
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168
CSAus http://www.csagroup.org/services-industries/product-listing/ 70136717
cCSAus
https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page6/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Accessories
Accessories
End block
End clamp-CLIPFIX 35-5-3022276
Quick mounting end clamp for NS 35/7,5 DIN rail or NS 35/15 DIN rail, with marking option, with parking option for
FBS...5, FBS...6, KSS 5, KSS 6, width: 5.15 mm, color: gray
Labeled terminal marker
Zack Marker strip, flat-ZBF 6 CUS-0825027
Zack Marker strip, flat, Strip, can be ordered: Strip, white, labeled according to customer specifications, mounting type:
snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm, Number of individual
labels: 10
Zack Marker strip, flat-ZBF 6,QR:FORTL.ZAHLEN-0808765
Zack Marker strip, flat, Strip, white, labeled, Printed vertically: consecutive numbers 1 ... 10, 11 ... 20, etc. up to 91 ...
100, mounting type: snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm,
Number of individual labels: 10
Marker pen
Marker pen-X-PEN 0,35-0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm
Terminal marking
https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page7/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Accessories
Zack Marker strip, flat-ZBF 6:UNBEDRUCKT-0808710
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type:
snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm, Number of individual
labels: 10
Zack Marker strip, flat-ZBF 6/WH-100:UNBEDRUCKT-0808736
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type:
snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm, Number of individual
labels: 10
Additional products
Remote signaling set-TTC-6-FMRS-PT-2907811
Module set for the optical monitoring and floating remote signaling of adjacent surge protective devices in the
TERMITRABcomplete or CLIXTRAB product family. Suitable for directly grounded DIN rails.
Shield connection-SSA 3-6-2839295
Shield fast connection for 3 ... 6 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
Shield connection-SSA 5-10-2839512
Shield fast connection for 5 ... 10 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
https://www.phoenixcontact.com/us/products/2906755
05/19/2021Page8/8
Surge protection device-TTC-6P-2-HC-M-24DC-PT-I-2906755
Accessories
Spare parts
Surge protection plug-TTC-6P-2-HC-24DC-I-P-2907845
Surge protection plug with integrated status indicator on the module for a 2-wire floating signal circuit with high nominal
current. Nominal voltage: 24VDC
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com