PHOENIX CONTACT Inc., USA Page 1 / 5
http://www.phoenixcon.com May 6, 2011
Extract from the online
catalog
ELR 3- 24DC/500AC- 2
Order No.: 2297196
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297196
Three-phase solid-state contactor with 24 V DC input, 2 A output
current, zero voltage switch, optionally with thermal fuse.
Commercial data
GTIN (EAN)
4 046356 172851
sales group G410
Pack 1 pcs.
Customs tariff 85364900
Catalog page information Page 170 (IF-2009)
Product notes
WEEE/RoHS-compliant since:
02/15/2008
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
Input data
Rated actuating voltage UC24 V DC
Rated actuating voltage range with reference to
UC
0.8 ... 1.25
Rated actuating current IC8.3 mA
ELR 3- 24DC/500AC- 2 Order No.: 2297196
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297196
PHOENIX CONTACT Inc., USA Page 2 / 5
http://www.phoenixcon.com May 6, 2011
Switching threshold "0" signal, voltage 9.6 V
Switching threshold "1" signal voltage 19.2 V
Protective circuit Protection against polarity reversal Suppressor diode
Surge protection
Status display Yellow LED
Indication Red LED
Output data, load relay
Output name AC output
Nominal output voltage 500 V AC
Nominal output voltage range 48 V AC ... 575 V AC
Periodic peak reverse voltage 1200 V
Load current max. 2 A (see derating curve)
Leakage current 6 mA
Residual voltage < 1.5 V
Surge current 200 A (t = 10 ms)
Max. load value 250 A2s
Type of protection RCV circuit
Surge voltage protection > 575 V AC
Connection data
Connection method Screw connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 26
Conductor cross section AWG/kcmil max 12
General data
Width 40 mm
Height 99 mm
Depth 114.5 mm
Test voltage input/output 5 kVrms
Ambient temperature (operation) -25 °C ... 70 °C
Ambient temperature (storage/transport) -25 °C ... 70 °C
Mounting position Vertical (horizontal DIN rail)
ELR 3- 24DC/500AC- 2 Order No.: 2297196
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297196
PHOENIX CONTACT Inc., USA Page 3 / 5
http://www.phoenixcon.com May 6, 2011
Assembly instructions Can be aligned with spacing = 20 mm
Operating mode 100% operating factor
Degree of protection IP20
Name Standards/regulations
Standards/regulations DIN EN 50178
EN 60947
Name Power station requirements
Standards/regulations DWR 1300 / ZXX01/DD/7080.8d
Name Air and creepage distances between the power circuits
Standards/regulations DIN EN 50178
Rated surge voltage / insulation 6 kV / Basic isolation
Rated insulation voltage 500 V
Pollution degree 2
Surge voltage category III
Certificates / Approvals
Certification CUL Listed, UL Listed
Certifications applied for: GL
Diagrams/Drawings
Block diagram
ELR 3- 24DC/500AC- 2 Order No.: 2297196
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297196
PHOENIX CONTACT Inc., USA Page 4 / 5
http://www.phoenixcon.com May 6, 2011
Diagram
ELR 3- 24DC/500AC- 2 Order No.: 2297196
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2297196
PHOENIX CONTACT Inc., USA Page 5 / 5
http://www.phoenixcon.com May 6, 2011
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2011 Phoenix Contact