s
Preface, Contents
Common HMI Elements 1
Symbols 2
Tag Structures and
Faceplates 3
Action Requests 4
SIMATIC
PCS 7/505
Symbols and Faceplates
Manual
Edition 07/2006
A5E00767202-01
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to
prevent damage to property. The notices referring to your personal safety are highlighted in the manual
by a safety alert symbol, notices referring to property damage only have no safety alert symbol. The
notices shown below are graded according to the degree of danger.
Siemens AG
Automation and Drives
Postfach 4848
90437 NÜRNBERG
GERMANY
Copyright © Siemens AG 2006
A5E00767202-01
Siemens AG 2006
Technical data subject to change.
!Danger
indicates that death or severe personal injury will result if proper precautions are not taken.
!Warning
indicates that death or severe personal injury may result if proper precautions are not taken.
!Caution
with a safety alert symbol indicates that minor personal injury can result if proper precautions are not
taken.
Caution
without a safety alert symbol indicates that property damage can result if proper precautions are not
taken.
Notice
indicates that an unintended result or situation can occur if the corresponding notice is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of
danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a
warning relating to property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning
and operation of a device/system may only be performed by qualified personnel.Within the context of
the safety notices in this documentation qualified persons are defined as persons who are authorized to
commission, ground and label devices, systems and circuits in accordance with established safety
practices and standards.
Prescribed Usage
Note the following:
Warning
This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
Correct, reliable operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.
!
Trademarks
All names identified by ® are registered trademarks of the Siemens AG.
The remaining trademarks in this publication may be trademarks whose use by third parties for their
own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and
software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency.
However, the information in this publication is reviewed regularly and any necessary corrections are
included in subsequent editions.
Preface
Purpose of the Manual
This manual provides the information necessary to use the PCS 7/505 OS
Symbols and Faceplates.
Required Basic Knowledge
Readers are presumed to be knowledgeable in the use of PCS 7.
Where is this Manual valid?
This manual is valid for the software package PCS 7/505 OS Option for V6.1.
Training Centers
Siemens Technical Training Center provides extensive training for all levels of
plant personnel to ensure optimal performance from PCS 7 control systems.
Classes include extensive hands-on activities using appropriate equipment, making
the training directly and immediately applicable.
On-line information is available: http://www.sea.siemens.com/sitrain
Siemens also offers a number of training courses to familiarize you with the
SIMATIC S7 automation system. Please contact your regional training center or
our central training center in D 90327 Nuremberg, Germany for details:
Telephone: +49 (911) 895-3200.
Internet: http://www.sitrain.com
PCS 7/505 Symbols and Faceplates
AE00767202-01 iii
Preface
A&D Technical Support
Worldwide, available 24 hours a day:
Beijing
Nürnberg
Johnson City
United States: Johnson City, TN Worldwide: rnberg Asia / Australia: Beijing
Technical Support
24 hours a day, 365 days a year
Phone:+49 (180) 5050-222
Fax:+49 (180) 5050-223
E-Mail: ad.support@siemens.com
GMT:+1:00
Technical Support and Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Telephone:+1 (423) 262 2522
or +1 (800) 333-7421 (USA only)
Fax:+1 (423) 262 2289
Mail to: techsupport.sea@siemens.com
GMT: -5:00
Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Phone: +49 (180) 5050-222
Fax: +49 (180) 5050-223
Mail to: ad.support@siemens.com
GMT: +1:00
Technical Support and Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Phone:+86 10 64 75 75 75
Fax:+86 10 64 74 74 74
Mail to:ad.support.asia@siemens.com
GMT:+8:00
Automation and Drives Service and Support International
http://www.siemens.com/automation/service&support
The languages of the SIMATIC Hotlines and the authorization hotline are generally German and English.
PCS 7/505 Symbols and Faceplates
iv AE00767202-01
Contents
1 Common HMI Elements 1-1
1.1 Common Faceplate Elements .......................................................................... 1-1
1.2 Analog Edit Dialog Box..................................................................................... 1-3
1.3 Discrete Edit Dialog Box................................................................................... 1-3
1.4 Text Edit Dialog Box ......................................................................................... 1-4
1.5 PCS 7 External Tag Count ............................................................................... 1-5
1.6 Operator Change Confirmation ........................................................................ 1-5
1.7 Synchronization and Persistance of HMI Tag Values ...................................... 1-6
1.8 Disabled Alarm List........................................................................................... 1-7
2 Symbols 2-1
2.1 Symbols ............................................................................................................ 2-1
3 Tag Structures and Faceplates 3-1
3.1 Tag Structures and Faceplates ........................................................................ 3-1
3.2 505_AI............................................................................................................... 3-2
3.3 505_AO............................................................................................................. 3-7
3.4 505_CALC ........................................................................................................ 3-9
3.5 505_CTR ........................................................................................................ 3-11
3.6 505_DI ............................................................................................................ 3-13
3.7 505_DI10 ........................................................................................................ 3-15
3.8 505_DO .......................................................................................................... 3-17
3.9 505_DO10 ...................................................................................................... 3-19
3.10 505_IVAR ....................................................................................................... 3-22
3.11 505_LOOP...................................................................................................... 3-24
3.12 505_MTR1 ...................................................................................................... 3-30
3.13 505_MTR2 ...................................................................................................... 3-32
3.14 505_RMTR ..................................................................................................... 3-32
3.15 505_PLC......................................................................................................... 3-33
3.16 505_TEXT....................................................................................................... 3-36
3.17 505_TMR ........................................................................................................ 3-37
3.18 505_VLV1 ....................................................................................................... 3-39
3.19 505_VLV2 ....................................................................................................... 3-41
4 Action Requests 4-1
4.1 Overview of Action Requests ........................................................................... 4-1
4.2 ACTION_REQUEST......................................................................................... 4-3
PCS 7/505 Symbols and Faceplates
A5E00767202-01 v
1 Common HMI Elements
1.1 Common Faceplate Elements
The @CommonElements.pdl file contains a generic discrete I/O button and a
generic analog I/O edit field. These objects can be manually copied to any user
graphic. If the tag to be edited is part of a tag structure, then standard PCS 7 user
authorization will be enforced. If the tag to be edited is a single tag (not part of a
tag structure), no PCS 7 user authorization will be enforced since a single tag
cannot be assigned to a process area for user authorization enforcement.
At runtime, the discrete I/O button provides the ability to edit any existing BOOL
type tag. All changes to the BOOL tag are recorded in the WinCC operators log.
The tag, along with "On" and "Off" messages, and "On" and "Off" button text are
configured from the object properties dialog in Graphics Designer.
At runtime, the analog I/O field provides the ability to edit any existing analog tag.
All changes to the analog tag are recorded in the WinCC operators log. The tag,
along with range limits, and display format are configured from the object
properties dialog in Graphics Designer.
The @CommonElements.pdl file also contains an example of a button that allows a
trend group created with the PCS 7 Online Trend Configuration Utility to be opened
up directly by name instead of selecting it from a list. The trend group name and
the monitor to display the trend group on are configurable. Use the properties
dialog box to configure the Mouse Action for the object.
Faceplate Overview Window
Key Description
1 Alarm Group Display
2 Lock/unlock messages button
3 Alarm ACK button
4 Go to primary graphic button (display function block's
primary graphic)
PCS 7/505 Symbols and Faceplates
A5E00767202-01 1-1
Common HMI Elements
Faceplate Frame
Key Description
1 Current tagname
2 Pulldown view-selector list
3 Go to loop display mode (all faceplate views, with the option
of selecting a large trend display)
Faceplate View List
The drop-down faceplate view list provides the names of the available faceplate
views. Clicking a name selects a view.
PCS 7/505 Symbols and Faceplates
1-2 A5E00767202-01
Common HMI Elements
1.2 Analog Edit Dialog Box
An analog edit dialog box is displayed whenever you click a user-editable analog
value. Variable Min and Max values are enforced.
To enter a value, you can:
xedit the value directly in the edit field
xtype in a value using the physical keyboard
xtype in a value using the electronic keyboard
xuse the slider control, or
xclick any of the four incremental buttons
File Name: @Common_AnalogInput.PDL
1.3 Discrete Edit Dialog Box
A discrete edit dialog box is displayed whenever you click on a user-editable
discrete value. There are three versions (2 state, 3 state, and 4 state). The number
of possible variable states determines which box is displayed. Examples are shown
below:
2 State Edit Box:
File Name: @Common_MultipleDiscreteInput.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 1-3
Common HMI Elements
3 State Edit Box:
File Name: @Common_DiscreteInput3State.PDL
4 State Edit Box:
File Name: @Common_DiscreteInput4State.PDL
1.4 Text Edit Dialog Box
A text edit box is displayed whenever you click on a user-editable text value.
File Name: @Common_TextInput.PDL
PCS 7/505 Symbols and Faceplates
1-4 A5E00767202-01
Common HMI Elements
1.5 PCS 7 External Tag Count
A single 505 tag is mapped into a PCS 7 tag structure. The PCS 7 tag structure
consists of a collection of internal and external tags. PCS 7 is licensed based on
the external tag count. For estimation purposes, the following table documents the
relationship between a 505 tag type, and the number of external PCS 7 tags that
will be created.
505 Tag Type PCS 7 Tag Structure Number of external tags
per PCS 7 tag structure
A
I 505_AI 16
A
O 505_AO 5
DI 505_DI 4
DI10 505_DI10 5
DO 505_DO 5
DO10 505_DO10 15
VLV1 505_VLV1 10
VLV2 505_VLV2 10
RMTR 505_RMTR 10
MTR1 505_MTR1 10
MTR2 505_MTR2 10
CALC 505_CALC 5
IVAR 505_IVAR 5
TMR 505_TMR 5
CTR 505_CTR 4
LOOP 505_LOOP 21
TEXT 505_TEXT 4
PLC 505_PLC 8
1.6 Operator Change Confirmation
DBA adds a ConfirmChange extended attribute for each function block instance
(See the DBA help file for details). This controls whether operator actions require a
confirmation step or not.
If ConfirmChange is FALSE (its default value) then any type of discrete operator
change (for example, Auto/Manual, Start Motor, Open Valve, etc.) is immediately
made without further confirmation requirements.
If ConfirmChange is TRUE, then any type of discrete operator change displays
either the Discrete Input Dialog box or a Confirmation box, and requires the
operator to select and/or confirm the request. Similarly, any floating-point operator
change can only be made via the Analog Input Dialog, and confirmed with its OK
button.
In either case, an entry in the operator’s log is always made for any operation that
involves a write to the controller.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 1-5
Common HMI Elements
In addition, if ConfirmChange is FALSE, any faceplate bargraph that is editable by
the user also includes a set of four quick-change buttons to make immediate step
changes to the bargraph value. These make step changes of either -5%, -1%, 1%,
or 5% of configured span. The quick-change buttons are not displayed if
ConfirmChange is TRUE.
1.7 Synchronization and Persistance of HMI Tag Values
A feature of the PCS 7 HMI is the ability to synchronize and persist arbitrary
internal WinCC tag values.
The synchronization feature will guarantee that internal tag values remain
consistent between redundant server partners in a redundant OS server
architecture.
The persistence feature will preserve tag values through a restart of the WinCC
runtime, or a reboot of the OS server. Without this feature, internal tag values are
always initialized to their configured "start value". This feature can be used on
single station nodes, single OS server nodes, or redundant OS server nodes.
The synchronization and persistence features are not required for external tag
values since those tag values are already persisted in the controller.
The synchronization and persistence configuration is stored in a CSV file
(SyncPersistTags.csv) in the RuntimeFramework directory in the WinCC project
directory.
PCS 7/505 Symbols and Faceplates
1-6 A5E00767202-01
Common HMI Elements
CSV File Format
The CSV file format allows blank lines and comment lines which are designated by
a leading semicolon (;). The CSV file must have a header with a leading
":TAG"(case does not matter) and at least another column with PERSIST or SYNC
(case does not matter). If the option column is missing, then none of the tags will
be processed for that option. For example, if the PERSIST column exists, but the
SYNC column does NOT, then the tags will only be processed for PERSIST. The
TAG column should contain the full WinCC tagname. The option columns should
have the value of 0, or 1. Any other value including a blank will ENABLE the option
for that tag.
Here is an example:
; This is a comment
: Tag , PERSIST, SYNC
Tag1
Tag2, 1, 0
Tag3, 0, 1
Tag4, 1, 1
In this example:
Tag1 will be persisted and synchronized.
Tag2 will be persisted.
Tag3 will be synchronized.
Tag4 will be persisted and synchronized.
1.8 Disabled Alarm List
A disabled alarm list is available that displays all disabled and locked alarms in the
system.
It is displayed by clicking the disabled alarm list button on the PCS 7 alarm
logging status bar.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 1-7
2 Symbols
2.1 Symbols
Each tag structure and faceplate has an associated symbol. You can place these
symbols on your process graphics to represent a control object. At runtime, when
you click on the symbol, the associated faceplate is displayed and tied to the
corresponding instance of the 505 object.
The PCS 7/505 OS Option symbols are shown in the picture below:
The 505 symbols are provided on picture "@@505Typicals.pdl". PCS 7/505 DBA
uses these symbols as shown to create instances associated with the type found in
the 505. The symbols on this picture can be considered "master" symbols. These
symbols use a naming convention of @505_AI/1. When DBA creates an instance
of this symbol on a picture, the symbol name is set equal to the tagname of the 505
tag. DBA manages these symbol names and they should not be edited.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 2-1
Symbols
When a symbol is copied or cut and then pasted onto the same picture or another
picture, the Graphics Designer changes the name of the symbol. For example
@505_AI becomes 505_AI1; if another instance is pasted, the name becomes
505_AI2. It is important that the symbol names of symbol instances created by
DBA not be changed. DBA manages the creation and deletion of the symbol
instances that it creates. If you cut and paste a symbol instance onto the same
picture created by DBA, the next time DBA runs it adds another instance of this
symbol. If you need to move a symbol, drag and drop it to ensure that the name
does not change.
PCS 7/505 Symbols and Faceplates
2-2 A5E00767202-01
3 Tag Structures and Faceplates
3.1 Tag Structures and Faceplates
Tag structures are the interface between PCS 7 OS and the outside world. Each
tag structure is closely modeled after the attributes of the appropriate 505 tags. In
addition, several tags in each tag structure have been added to support general
PCS 7 OS functions (EventState, EventRaw, EventTrans, etc.).
The table below lists the 505 tag names with their descriptions and their
corresponding tag structures in PCS 7 OS.
505 Tag Name Description PCS 7 Tag Structure
AI Analog Input 505_AI
AO Analog Output 505_AO
CALC Calc Variable 505_CALC
CTR Counter 505_CTR
DI Digital Input (including 1 bit and multiple bit) 505_DI
DI10 10 bit Discrete Input 505_DI10
DO Discrete Output 505_DO
DO10 10 Bit Discrete Output 505_DO10
IVAR Integer Variable 505_IVAR
LOOP Loop 505_LOOP
MTR1 Non-reversible Motor 505_MTR1
MTR2 Two Speed Motor 505_MTR2
RMTR Reversible Motor 505_RMTR
TEXT Three text strings 505_TEXT
TMR Timer 505_TMR
VLV1 Single Feedback Valve 505_VLV1
VLV2 Dual Feedback Valve 505_VLV2
N/A 505 PLC 505_PLC
N/A Action Request ACTION_REQUEST
Each tag structure in PCS 7 OS is represented by a faceplate that displays the
appropriate attributes for that tag. Faceplates that include live analog values also
include a trend display with pre-configured online trend variables that require no
further user configuration. Multiple faceplates can be viewed simultaneously.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-1
Tag Structures and Faceplates
3.2 505_AI
Standard View
The standard view for the 505_AI faceplate displays information on PV, Target,
and alarm limits.
Description Type Tag
Description Static Text .#comment
PV Value Customized Object .PV
PV Units Static Text .PV#unit
Target Value Customized Object .Target
Target Units Static Text .PV#unit
Alarm Bar Graphs Customized Object .HD_Lim, .LD_Lim, .HH_Lim,
.H_Lim, .L_Lim, .LL_Lim,
PV Target Bar Graphs Customized Object .PV, .Target
File Name: @PG_505_AI_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
3-2 A5E00767202-01
Tag Structures and Faceplates
Limits View
The limits view for the 505_AI faceplate displays information on alarm limits.
Description Type Tag
High High Alarm Enable Customized Object .DisableRaw
High High Alarm Limit Customized Object .HH_Lim
High High Alarm Units Static Text .PV#unit
High Alarm Enable Customized Object .DisableRaw
High Alarm Limit Customized Object .H_Lim
High Alarm Units Static Text .PV#unit
Low Alarm Enable Customized Object .DisableRaw
Low Alarm Limit Customized Object .L_Lim
Low Alarm Units Static Text .PV#unit
Low Low Alarm Enable Customized Object .DisableRaw
Low Low Alarm Limit Customized Object .LL_Lim
Low Low Alarm Units Static Text .PV#unit
High Deviation Alarm Enable Customized Object .DisableRaw
High Deviation Alarm Limit Customized Object .HD_Lim
High Deviation Alarm Units Static Text .PV#unit
Low Deviation Alarm Enable Customized Object .DisableRaw
Low Deviation Alarm Limit Customized Object .LD_Lim
Low Deviation Alarm Units Static Text .PV#unit
Rate Of Change Alarm Enable Customized Object .DisableRaw
Rate Of Change Alarm Limit Customized Object .ROC_Lim
Rate Of Change Alarm Units Static Text .PV#unit
Bad Transmitter Alarm Customized Object .DisableRaw
File Name: @PCS7_505_ALARM_CONFIG.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-3
Tag Structures and Faceplates
Alarm View
The alarm view for the 505_AI faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
File Name: @PCS7_ALARM.PDL
PCS 7/505 Symbols and Faceplates
3-4 A5E00767202-01
Tag Structures and Faceplates
Trend View
The trend view for the 505_AI faceplate displays information in graph form on PV
and Target.
The trend view is the standard view for displaying trends for the function block. For
the 505_AI function block the trend view displays the process value (PV), and
target (Target). Only one trend window is needed for each function block type. A
script assigns proper tags to the trend control at runtime.
The trend control itself is actually the standard PCS 7 OS Trend Control. See the
PCS 7 OS User Documentation for details on its operation.
File Name: @PCS7_505_TREND_PV_TARGET.PDL
Loop Display (Small Trend)
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-5
Tag Structures and Faceplates
Loop Display (Large Trend)
PCS 7/505 Symbols and Faceplates
3-6 A5E00767202-01
Tag Structures and Faceplates
3.3 505_AO
Standard View
The standard view for the 505_AO faceplate displays information on Out and
Mode.
Description Type Tag
Description Static Text .#comment
Out Value Customized Object .Out
Out Units Static Text .Out#unit
Mode Customized Object .Mode
Out Bar Graph Customized Object .Out
File Name: @PG_505_AO_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-7
Tag Structures and Faceplates
Trend View
The trend view for the 505_AO faceplate displays information in graph form on Out.
The trend view is the standard view for displaying trends for the function block. For
the 505_AO function block the trend view displays the Out value (Out). Only one
trend window is needed for each function block type. A script assigns proper tags
to the trend control at runtime.
The trend control itself is actually the standard PCS 7 OS Trend Control. See the
PCS 7 OS User Documentation for details on its operation.
File Name: @PCS7_505_TREND_OUT.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-8 A5E00767202-01
Tag Structures and Faceplates
3.4 505_CALC
Standard View
The standard view for the 505_CALC faceplate displays information on Value.
Description Type Tag
Description Static Text .#comment
Value Customized Object .Value
Value Units Static Text .Value#unit
Value Bar Graph Customized Object .Value
File Name: @PG_505_CALC_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-9
Tag Structures and Faceplates
Trend View
The trend view for the 505_CALC faceplate displays information in graph form on
Value.
The trend view is the standard view for displaying trends for the function block. For
the 505_CALC function block the trend view displays the Value tag (Value). Only
one trend window is needed for each function block type. A script assigns proper
tags to the trend control at runtime.
The trend control itself is actually the standard PCS 7 OS Trend Control. See the
PCS 7 OS User Documentation for details on its operation.
File Name: @PCS7_505_TREND_VALUE.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-10 A5E00767202-01
Tag Structures and Faceplates
3.5 505_CTR
Standard View
The standard view for the 505_CTR faceplate displays information on Value and
Preset.
Description Type Tag
Description Static Text .#comment
Value Customized Object .Value
Value Units Static Text .Value#unit
Preset Customized Object .Value_EUMax
Preset Units Static Text .Value#unit
Value Bar Graph Customized Object .Value
File Name: @PG_505_CTR_STANDARD.PDL
Trend View
The trend view for the 505_CTR faceplate displays information in graph form on
Value.
The trend view is the standard view for displaying trends for the function block. For
the 505_CTR function block the trend view displays the Value tag (Value). Only
one trend window is needed for each function block type. A script assigns proper
tags to the trend control at runtime.
The trend control itself is actually the standard PCS 7 OS Trend Control. See the
PCS 7 OS User Documentation for details on its operation.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-11
Tag Structures and Faceplates
File Name: @PCS7_505_TREND_VALUE.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-12 A5E00767202-01
Tag Structures and Faceplates
3.6 505_DI
Standard View
The standard view for the 505_DI faceplate displays information on Input Value
and alarm settings.
Description Type Tag
Description Static Text .#comment
DI Static Text .EventRaw#1
Alarm Enable Customized Object .DisableRaw
File Name: @PG_505_DI_STANDARD.PDL
Alarm View
The alarm view for the 505_DI faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-13
Tag Structures and Faceplates
File Name: @PCS7_ALARM.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-14 A5E00767202-01
Tag Structures and Faceplates
3.7 505_DI10
Standard View
The standard view for the 505_DI10 faceplate displays information on Inputs and
alarm settings.
Description Type Tag
Description Static Text .#comment
DI1 Static Text .EventRaw#1
DI2 Static Text .EventRaw#1
DI3 Static Text .EventRaw#1
DI4 Static Text .EventRaw#1
DI5 Static Text .EventRaw#1
DI6 Static Text .EventRaw#1
DI7 Static Text .EventRaw#1
DI8 Static Text .EventRaw#1
DI9 Static Text .EventRaw#1
DI10 Static Text .EventRaw#1
Alarm Enable1 Customized Object .DisableRaw
Alarm Enable2 Customized Object .DisableRaw
Alarm Enable3 Customized Object .DisableRaw
Alarm Enable4 Customized Object .DisableRaw
Alarm Enable5 Customized Object .DisableRaw
Alarm Enable6 Customized Object .DisableRaw
Alarm Enable7 Customized Object .DisableRaw
Alarm Enable8 Customized Object .DisableRaw
Alarm Enable9 Customized Object .DisableRaw
Alarm Enable10 Customized Object .DisableRaw
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-15
Tag Structures and Faceplates
File Name: @PG_505_DI10_STANDARD.PDL
Alarm View
The alarm view for the 505_DI10 faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
File Name: @PCS7_ALARM.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-16 A5E00767202-01
Tag Structures and Faceplates
3.8 505_DO
Standard View
The standard view for the 505_DO faceplate displays information on Output Value
and alarm settings.
Description Type Tag
Description Static Text .#comment
DO (status) Static Text .EventRaw#1
DO (command) Customized Object .DO
Alarm Enable Customized Object .DisableRaw
File Name: @PG_505_DO_STANDARD.PDL
Alarm View
The alarm view for the 505_DO faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-17
Tag Structures and Faceplates
File Name: @PCS7_ALARM.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-18 A5E00767202-01
Tag Structures and Faceplates
3.9 505_DO10
Standard View
The standard view for the 505_DO10 faceplate displays information on Outputs
and alarm settings.
Description Type Tag
Description Static Text .#comment
DO1 (status) Static Text .EventRaw#1
DO2 (status) Static Text .EventRaw#1
DO3 (status) Static Text .EventRaw#1
DO4 (status) Static Text .EventRaw#1
DO5 (status) Static Text .EventRaw#1
DO6 (status) Static Text .EventRaw#1
DO7 (status) Static Text .EventRaw#1
DO8 (status) Static Text .EventRaw#1
DO9 (status) Static Text .EventRaw#1
DO10 (status) Static Text .EventRaw#1
DO1 (command) Customized Object .DO1
DO2 (command) Customized Object .DO2
DO3 (command) Customized Object .DO3
DO4 (command) Customized Object .DO4
DO5 (command) Customized Object .DO5
DO6 (command) Customized Object .DO6
DO7 (command) Customized Object .DO7
DO8 (command) Customized Object .DO8
DO9 (command) Customized Object .DO9
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-19
Tag Structures and Faceplates
DO10 (command) Customized Object .DO10
Alarm Enable1 Customized Object .DisableRaw
Alarm Enable2 Customized Object .DisableRaw
Alarm Enable3 Customized Object .DisableRaw
Alarm Enable4 Customized Object .DisableRaw
Alarm Enable5 Customized Object .DisableRaw
Alarm Enable6 Customized Object .DisableRaw
Alarm Enable7 Customized Object .DisableRaw
Alarm Enable8 Customized Object .DisableRaw
Alarm Enable9 Customized Object .DisableRaw
Alarm Enable10 Customized Object .DisableRaw
File Name: @PG_505_DO10_STANDARD.PDL
Alarm View
The alarm view for the 505_DO10 faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
File Name: @PCS7_ALARM.PDL
PCS 7/505 Symbols and Faceplates
3-20 A5E00767202-01
Tag Structures and Faceplates
Loop Display
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-21
Tag Structures and Faceplates
3.10 505_IVAR
Standard View
The standard view for the 505_IVAR faceplate displays information on Value.
Description Type Tag
Description Static Text .#comment
Value Customized Object .Value
Value Units Static Text .Value#unit
Value Bar Graph Customized Object .Value
File Name: @PG_505_IVAR_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
3-22 A5E00767202-01
Tag Structures and Faceplates
Trend View
The trend view for the 505_IVAR faceplate displays information in graph form on
Value.
The trend view is the standard view for displaying trends for the function block. For
the 505_IVAR function block the trend view displays the Value tag (Value). Only
one trend window is needed for each function block type. A script assigns proper
tags to the trend control at runtime.
The trend control itself is actually the standard PCS 7 OS Trend Control. See the
PCS 7 OS User Documentation for details on its operation.
File Name: @PCS7_505_TREND_VALUE.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-23
Tag Structures and Faceplates
3.11 505_LOOP
Standard View
The standard view for the 505_LOOP faceplate displays information on PV, SP,
Out, Mode, and alarm limits.
Description Type Tag
Description Static Text .#comment
PV Value Customized Object .PV
PV Units Static Text .PV#unit
SP Value Customized Object .SP
SP Units Static Text .PV#unit
Out Value Customized Object .Out
Out Units Static Text .Out#unit
Mode Customized Object .Mode
Out Bar Graph Customized Object .Out
Alarm Bar Graphs Customized Object .HD_Lim, .LD_Lim, .HH_Lim,
.H_Lim, .L_Lim, .LL_Lim,
PV SP Bar Graphs Customized Object .PV, .SP
File Name: @PG_505_LOOP_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
3-24 A5E00767202-01
Tag Structures and Faceplates
Limits View
The limits view for the 505_LOOP faceplate displays information on alarm limits.
Description Type Tag
High High Alarm Enable Customized Object .DisableRaw
High High Alarm Limit Customized Object .HH_Lim
High High Alarm Units Static Text .PV#unit
High Alarm Enable Customized Object .DisableRaw
High Alarm Limit Customized Object .H_Lim
High Alarm Units Static Text .PV#unit
Low Alarm Enable Customized Object .DisableRaw
Low Alarm Limit Customized Object .L_Lim
Low Alarm Units Static Text .PV#unit
Low Low Alarm Enable Customized Object .DisableRaw
Low Low Alarm Limit Customized Object .LL_Lim
Low Low Alarm Units Static Text .PV#unit
High Deviation Alarm Enable Customized Object .DisableRaw
High Deviation Alarm Limit Customized Object .HD_Lim
High Deviation Alarm Units Static Text .PV#unit
Low Deviation Alarm Enable Customized Object .DisableRaw
Low Deviation Alarm Limit Customized Object .LD_Lim
Low Deviation Alarm Units Static Text .PV#unit
Rate Of Change Alarm Enable Customized Object .DisableRaw
Rate Of Change Alarm Limit Customized Object .ROC_Lim
Rate Of Change Alarm Units Static Text .PV#unit
Bad Transmitter Alarm Customized Object .DisableRaw
File Name: @PCS7_505_ALARM_CONFIG.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-25
Tag Structures and Faceplates
Alarm View
The alarm view for the 505_LOOP faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
File Name: @PCS7_ALARM.PDL
PCS 7/505 Symbols and Faceplates
3-26 A5E00767202-01
Tag Structures and Faceplates
Tuning View
The tuning view for the 505_LOOP faceplate displays information on tuning
parameters.
Description Type Tag
Gain Customized Object .Gain
Gain Units Static Text .Gain#unit
Rate Customized Object .Rate
Rate Units Static Text .Rate#unit
Reset Customized Object .Reset
Reset Units Static Text .Reset#unit
File Name: @PG_505_LOOP_ TUNING.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-27
Tag Structures and Faceplates
Trend View
The trend view for the 505_LOOP faceplate displays information in graph form on
PV, SP, and Out.
The trend view is the standard view for displaying trends for the function block. For
the 505_LOOP function block the trend view displays the process value (PV),
setpoint (SP), and output value (Out). Only one trend window is needed for each
function block type. A script assigns proper tags to the trend control at runtime.
The trend control itself is actually the standard PCS 7 OS Trend Control. See the
PCS 7 OS User documentation for details on its operation.
File Name: @PCS7_505_TREND_PV_SP_OUT.PDL
Loop Display (Small Trend)
PCS 7/505 Symbols and Faceplates
3-28 A5E00767202-01
Tag Structures and Faceplates
Loop Display (Large Trend)
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-29
Tag Structures and Faceplates
3.12 505_MTR1
Standard View
The standard view for the 505_MTR1 faceplate displays information on Mode,
Setpoint, Status, Override, and alarm settings.
Description Type Tag
Description Static Text .#comment
Mode Customized Object .Mode
Setpoint Customized Object .Setpoint
State Customized Object .EventRaw#1
Override Customized Object .Override
Start Timeout Customized Object .Timeout1
Stop Timeout Customized Object .Timeout2
Not Running Alarm Enable Customized Object .DisableRaw
Not Stopped Alarm Enable Customized Object .DisableRaw
File Name: @PG_505_MTR1_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
3-30 A5E00767202-01
Tag Structures and Faceplates
Alarm View
The alarm view for the 505_MTR1 faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
File Name: @PCS7_ALARM.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-31
Tag Structures and Faceplates
3.13 505_MTR2
The 505_MTR2 faceplate is identical to the 505_MTR1 faceplate in all respects
except filenames, and the fact that the Setpoint value has 3 possible states instead
of just 2, the Override value has 4 possible states instead of just 2, and there are 3
alarms to disable instead of just 2.
3.14 505_RMTR
The 505_RMTR faceplate is identical to the 505_MTR1 faceplate in all respects
except filenames, and the fact that the Setpoint value has 3 possible states instead
of just 2, the Override value has 4 possible states instead of just 2, and there are 3
alarms to disable instead of just 2.
PCS 7/505 Symbols and Faceplates
3-32 A5E00767202-01
Tag Structures and Faceplates
3.15 505_PLC
Standard View
The standard view for the 505_PLC faceplate displays information on State, Scan,
MainConnStat, AltConnStat, and alarm settings.
Description Type Tag
Description Static Text .#comment
State Static Text .State
Scan Static Text .Scan
Main Connection Status Static Text .MainConn
Alt Connection Status Static Text .AltConn
Connection Lost Alarm Enable Customized Object .DisableRaw
RBE Full Alarm Enable Customized Object .DisableRaw
Program Mode Alarm Enable Customized Object .DisableRaw
File Name: @PG_505_PLC_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-33
Tag Structures and Faceplates
Status text will be colorized according to the following table:
Tag Value Color
State Unknown Magenta
Run Green
Program Yellow
Fault Red
Scan Off Red
On Green
MainConn Unavailable Yellow
A
vailable Green
Scan On Green
Fail Red
A
ltConn Unavailable Yellow
A
vailable Green
Scan On Green
Fail Red
Alarm View
The alarm view for the 505_PLC faceplate displays alarm messages.
File Name: @PCS7_ALARM.PDL
PCS 7/505 Symbols and Faceplates
3-34 A5E00767202-01
Tag Structures and Faceplates
Loop Display
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-35
Tag Structures and Faceplates
3.16 505_TEXT
Standard View
The standard view for the 505_TEXT faceplate displays information on the three
text values.
Description Type Tag
Description Static Text .#comment
Text1 Customized Object .Text1
Text2 Customized Object .Text2
Text3 Customized Object .Text3
File Name: @PG_505_TEXT_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
3-36 A5E00767202-01
Tag Structures and Faceplates
3.17 505_TMR
Standard View
The standard view for the 505_TMR faceplate displays information on Value and
Preset.
Description Type Tag
Description Static Text .#comment
Value Customized Object .Value
Value Units Static Text .Value#unit
Preset Customized Object .Preset
Preset Units Static Text .Value#unit
Value, Preset Bar Graph Customized Object .Value, .Preset
File Name: @PG_505_TMR_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-37
Tag Structures and Faceplates
Trend View
The trend view for the 505_TMR faceplate displays information in graph form on
Value.
The trend view is the standard view for displaying trends for the function block. For
the 505_TMR function block the trend view displays the Value tag (Value). Only
one trend window is needed for each function block type. A script assigns proper
tags to the trend control at runtime.
The trend control itself is actually the standard PCS 7 OS Trend Control. See the
PCS 7 OS User Documentation for details on its operation.
File Name: @PCS7_505_TREND_VALUE.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-38 A5E00767202-01
Tag Structures and Faceplates
3.18 505_VLV1
Standard View
The standard view for the 505_VLV1 faceplate displays information on Mode,
Setpoint, Status, Override, and alarm settings.
Description Type Tag
Description Static Text .#comment
Mode Customized Object .Mode
Setpoint Customized Object .Setpoint
State Customized Object .EventRaw#1
Override Customized Object .Override
Open Timeout Customized Object .Timeout1
Close Timeout Customized Object .Timeout2
Not Closed Alarm Enable Customized Object .DisableRaw
Not Opened Alarm Enable Customized Object .DisableRaw
File Name: @PG_505_VLV1_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-39
Tag Structures and Faceplates
Alarm View
The alarm view for the 505_VLV1 faceplate displays alarm messages.
The alarm view uses a standard WinCC Active X control. No modifications were
made to it for the PCS 7 OS option.
File Name: @PCS7_ALARM.PDL
Loop Display
PCS 7/505 Symbols and Faceplates
3-40 A5E00767202-01
Tag Structures and Faceplates
3.19 505_VLV2
The 505_VLV2 faceplate is identical to the 505_VLV1 faceplate in all respects
except filenames, and the fact that the Override value has 4 possible states instead
of just 2, and there are 3 alarms to disable instead of just 2.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 3-41
4 Action Requests
4.1 Overview of Action Requests
An Action Request consists of a configuration mechanism to annunciate an event,
and a procedure that you must perform to clear the event.
The ACTION_REQUEST faceplate displays basic information about the Action
Request. This information varies based on the AnswerFormat that was configured
for the Action Request. There are six types of AnswerFormat:
xAcknowledge: The user enters a comment and presses the Commit button.
xView: The Action Request is automatically acknowledged simply by displaying
the faceplate. No further user action is required.
xEvent Log: A message is automatically entered into the alarm logging system
when the Action Request is triggered. No further annunciation is made to the
user, and no user action is required from the faceplate.
xEnter Value: The user enters a value to be written to the AnswerTag, enters a
comment, and presses the Commit button.
xMultiple Choice: The user selects a value to be written to the AnswerTag from
the pre-configured list, enters a comment, and presses the Commit button.
xMultiple Choice (OSx Style): The user selects a value to be written to the
AnswerTag from the pre-configured list, enters a comment, and presses the
Commit button. The text displayed in the list is for informational purposes only.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 4-1
Action Requests
Fixed values are always written to the AnswerTag according to the following
table:
-Choice 1: 0x1000
-Choice 2: 0x2000
-Choice 3: 0x4000
-Choice 4: 0x8000
Note
The 505 PLC must be configured such that a write to the Action Request’s reset
tag will clear the trigger tag. In a system architecture that has redundant PCS 7 OS
Servers, the Action Request status will not be cleared on the redundant server until
the trigger tag is cleared. If there is a delay between the writing of the reset tag and
a clearing of the trigger tag, the Action Request status on the redundant PCS 7 OS
Server will not agree during this delay period.
PCS 7/505 Symbols and Faceplates
4-2 A5E00767202-01
Action Requests
4.2 ACTION_REQUEST
Standard View
The standard view for the ACTION_REQUEST faceplate displays information on
current value, new value, and answer format.
Key Type Description Tag
1 Static Text Time .TimeStamp
2 Static Text Description .Message
3 Static Text Comment .Comment
4 Customized Object Answer Tag Current Value
(Shown only for "EnterValue" and "Multi-choice"
AnswerFormats)
.AnswerTag
5 Customized Object Answer Tag New Value
(Shown only for "EnterValue"AnswerFormat.
"Multi-choice" AnswerFormat displays 4 radio
buttons)
.AnswerTag
6 Static Text Answer Format .AnswerFormat
7 Button Commit Button N/A
8 Button Cancel Button N/A
The radio buttons are only displayed in the Multiple Choice case. The Enter Value
I/O field is only displayed in the Enter Value case.
xTo confirm the Action Request, you enter a comment and select (or enter) a
value to be written to the AnswerTag, if configured.
PCS 7/505 Symbols and Faceplates
A5E00767202-01 4-3
Action Requests
xWhen you click the Commit button, the following actions take place:
-The chosen value is written to the AnswerTag.
-The configured ResetTag is reset.
-The Action Request is acknowledged (ACKed), clearing the alarm
annunciators.
-A record of the action is written to the Operator Log.
File Name: @PG_ ACTION_REQUEST_STANDARD.PDL
PCS 7/505 Symbols and Faceplates
4-4 A5E00767202-01