1
CSM_G3NE_DS_E_3_3
Solid State Relays
G3NE
Compact, Low-cost, SSR Switching 5 to 20 A
Wide load voltage range: 75 to 264 VAC. Both 100-V and
200-V loads can be handled with the same model.
Dedicated, compact aluminum PCB and power elements used.
Built-in varistor effectively absorbs external surges.
Quick-connect #110 input terminals and #250 output
connections. (#187 input terminals and #250 output
connections are available.)
“-US” models certified by UL, CSA, and IEC/EN (TÜV).
Refer to Safety Precautions for All Solid State
Relays.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
1. Basic Model Name
G3NE: Solid State Relay
2. Rated Load Power Supply Voltage
2: 200 VAC
3. Rated Load Current
05: 5 A
10: 10 A
20: 20 A
4. Terminal Type
T: Quick-connect terminals
5. Zero Cross Function
Blank: Equipped with zero cross function
L: Not equipped with zero cross function
6. Special Specifications
Blank: Standard models
2: #187 input terminals
7. Certification
US: Certified by UL, CSA, and TÜV
1234 567
G3NE-@@@@-@-@
G3NE
2
Ordering Information
List of Models
Note: 1. The rated input voltage depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 4.
2. When ordering, specify the input voltage.
3. Refer to List of Certified Models for a list of products that comply with safety standards. When ordering a UL, CSA, and EN(TÜV) certified
model, add “-US” to the model number.
Accessories (Order Separately)
Heat Sinks
The following heat sinks are thin and can be DIN-track mounted.
See Dimensions for details.
Isolation Zero cross
function
Indicator Rated output load Rated input voltage
(See note 1, 2.)
Model
Phototriac Yes No 5 A at 100 to 240 VAC 5VDC G3NE-205T-US DC5
G3NE-205T-2-US DC5
12VDC G3NE-205T-US DC12
G3NE-205T-2-US DC12
24VDC G3NE-205T-US DC24
G3NE-205T-2-US DC24
10 A at 100 to 240 VAC 5VDC G3NE-210T-US DC5
G3NE-210T-2-US DC5
12VDC G3NE-210T-US DC12
G3NE-210T-2-US DC12
24VDC G3NE-210T-US DC24
G3NE-210T-2-US DC24
20 A at 100 to 240 VAC 5VDC G3NE-220T-US DC5
G3NE-220T-2-US DC5
12VDC G3NE-220T-US DC12
G3NE-220T-2-US DC12
24VDC G3NE-220T-US DC24
G3NE-220T-2-US DC24
No 5 A at 100 to 240 VAC 5VDC G3NE-205TL-US DC5
G3NE-205TL-2-US DC5
12VDC G3NE-205TL-US DC12
G3NE-205TL-2-US DC12
24VDC G3NE-205TL-US DC24
G3NE-205TL-2-US DC24
10 A at 100 to 240 VAC 5VDC G3NE-210TL-US DC5
G3NE-210TL-2-US DC5
12VDC G3NE-210TL-US DC12
G3NE-210TL-2-US DC12
24VDC G3NE-210TL-US DC24
G3NE-210TL-2-US DC24
20 A at 100 to 240 VAC 5VDC G3NE-220TL-US DC5
G3NE-220TL-2-US DC5
12VDC G3NE-220TL-US DC12
G3NE-220TL-2-US DC12
24VDC G3NE-220TL-US DC24
G3NE-220TL-2-US DC24
Model Applicable SSR
Y92B-N50 G3NE-205T(L)(-2)-US/-210T(L)(-2)-US
Y92B-N100 G3NE-220T(L)(-2)-US
G3NE
3
Specifications
Ratings (at an Ambient Temperature of 25°C)
Input
Note: Each model has 5-VDC, 12-VDC, and 24-VDC input versions.
Output
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data
for details on page 4.
2. These values apply when using a dedicated heat sink or a radiation plate of specified size.
Characteristics
Rated voltage Operating voltage Voltage level Input impedance
Must operate Must release With zero cross function Without zero cross function
5 VDC 4 to 6 VDC 4 VDC max. 1 VDC min. 250 Ω±20% 300 Ω±20%
12 VDC 9.6 to 14.4 VDC 9.6 VDC max. 600 Ω±20% 800 Ω±20%
24 VDC 19.2 to 28.8 VDC 19.2 VDC max. 1.6 kΩ±20%
Model Applicable load
Rated load voltage Load voltage range Load current
(See note 1.)
Inrush current
With heat sink Without heat sink
G3NE-205T(L)(-2)-US 100 to 240 VAC 75 to 264 VAC 0.1 to 5 A at 40°C 0.1 to 5 A at 40°C 60 A (60 Hz, 1 cycle)
G3NE-210T(L)(-2)-US 0.1 to 10 A at 40°C
(See note 2.) 0.1 to 5 A at 40°C 150 A (60 Hz, 1 cycle)
G3NE-220T(L)(-2)-US 0.1 to 20 A at 40°C
(See note 2.) 0.1 to 5 A at 40°C 220 A (60 Hz, 1 cycle)
Item G3NE-2@@T(-2)-US G3NE-2@@TL(-2)-US
Operate time 1/2 of load power source cycle + 1 ms max. 1 ms max.
Release time 1/2 of load power source cycle + 1 ms max.
Output ON voltage drop 1.6 V (RMS) max.
Leakage current 2 mA max. (at 100 VAC)
5 mA max. (at 200 VAC)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance Destruction: 1,000 m/s2
Ambient temperature Operating: –30°C to 80°C (with no icing or condensation)
Storage: –30°C to 100°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Certified standards UL508 File No.E64562/CSA C22.2 (No.0, No.14) File No. LR35535
TÜV R9051064 (VDE0435) (EN60950)
EMC Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Weight Approx. 37 g
G3NE
4
Engineering Data
Load Current vs. Ambient Temperature
One Cycle Surge Current: Non-repetitive
Note: Keep the inrush current to half the rated value if it occurs repetitively.
G3NE-205T(L)(-2)-US G3NE-210T(L)(-2)-US G3NE-220T(L)(-2)-US
Ambient temperature (°C) Ambient temperature (°C) Ambient temperature (°C)
Load current (A)
Load current (A)
Load current (A)
Without heat sink
Without heat sink
Without heat sink
With standard heat sink (Y92B-N50)
or aluminum plate measuring 100 mm
x 100 mm x t2 mm (W x H x D)
With standard heat sink (Y92B-N100) or
aluminum plate measuring 300 mm x
300 mm x t3 mm (W x H x D)
G3NE-205T(L)(-2)-US G3NE-210T(L)(-2)-US G3NE-220T(L)(-2)-US
Inrush current (A. Peak)
Energized time (ms)
Inrush current (A. Peak)
Energized time (ms)
Inrush current (A. Peak)
Energized time (ms)
G3NE
5
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Safety Precautions
Refer to Safety Precautions for All Solid State Relays.
Precautions for Correct Use
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
Do not apply excessive force to the terminals. Be careful when
pulling or inserting the terminal clips for the Quick Connector (QC).
When attaching a heat sink to the G3NE, in order to facilitate heat
dissipation, apply heat-conductive grease on the heat sink.
For DIN Track mounting, use a separately sold Heat Sink. Refer to
information on the G3NA.
G3NE-210T(L): Y92B-N50
G3NE-220T(L): Y92B-N100
Tighten the mounting screws of the heat sink with a torque of 0.59 to
0.98 N·m.
Thermal Resistance Rth (Back
of Junction SSR)
EMC Directive Compliance
The G3NE complies with EMC Directives under the following
conditions ("-US" models only).
30±0.2
3 +
4
1
2
14.5
6.5
7.1
2.9 7.95
3
6
30+0.5
G3NE-205T(L)/210T(L)/220T(L)(-2)-US
Mounting Holes
Two, 3.5-dia. or M3 holes
Output Load
Input
37.5 max.
3.5 dia. hole
11.5 max.
* G3NE-2@@T(L)-2-US: Two, #187 (t=0.5) (Faston tab or equivalent)
47.5
max.
Two #110 (t = 0.5) (Faston
tab or equivalent)*
Two #250 (t = 0.8) (Faston
tab or equivalent)
Terminal Arrangement/
Internal Connections
(Top View)
Input
voltage
Load power
supply
5.6
47.6
90±0.3
35 30.5±0.3 30
54.5
6
35±0.2
90±0.4
35 30.5±0.3
47.6
90±0.3
5.6
30
5 4.5
28 13
35±0.2
90±0.4
Mounting Holes
Y92B-N100
4.6 dia. hole Two, M3 holes
Two, M4 holes
77 max.
100 max.
44 max. 47 max.
51 max.
4.6 dia. hole Two, M3 holes
77 max.
100 max.
71 max.
100 max.
75 max.
Two, 3.2-dia. holes
Mounting Holes
Weight: approx. 200 g
Weight: approx. 400 g
Heat Sink
Y92B-N50
Two, 3.2-dia.
holes
Two, M4
holes
Two, 4.4-dia.
or M4 holes
Two, 4.4-dia.
or M4 holes
Model Thermal resistance (°C/W)
G3NE-205T (L) 2.72
G3NE-210T (L) 2.12
G3NE-220T (L) 2.22
OutputInput G3NE-US
Load
10 m max.
Connect a film capacitor to the load power supply.
The input cable must be less than 10 m.
Film capacitor:
1 μF, 250 VAC
G3NE
6
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omrons analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyers application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2015.9
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2015 All Right Reserved.