https://www.phoenixcontact.com/us/products/2864419
01/17/2021Page3/7
Loop-powered isolators-MINI MCR-SL-1CP-I-I-2864419
Technical data
Connection data
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient ≤ 0.002 %/K (of measured value / 100 Ω load)
Temperature coefficient, typical < 0.002 %/K (of measured value / 100 Ω load)
Cold junction errors ≤
Typical cold point errors ≤
Additional error, load-dependent < 0.03 % (of measured value / 100 Ω load)
Limit frequency (3 dB) 75 Hz
Step response (10-90%) 5 ms (at 600 Ω load)
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 50 V AC/DC
Test voltage input/output 1.5 kV (50 Hz, 1 min.)
Test voltage channel/channel 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color green
Housing material PBT
Mounting position any
Assembly instructions The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN61000-4-3
Evaluation criterion A
Designation Fast transients (burst)