MCR loop-powered isolator, 1-channel, for the electrical isolation of current signals without auxiliary power, with
screw connection
Product Description
The 6.2 mm narrow passive loop-powered isolator MINI MCR-SL-...CP-I-I... is used for the electrical isolation and filtering of 0...20 mA and 4...20 mA
standard current signals without additional supply voltage.
Your advantages
Voltage drop at isolating amplifier of just 1.7 V
Does not require additional auxiliary voltage
Supplied by an input loop
Two channels on a design width of just 6.2 mm
Highly compact 2-conductor passive isolators for the electrical isolation and filtering of standard analog signals
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4017918974848
Weight per Piece (excluding packing) 68.600 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Dimensions
Width 6.2 mm
Height 93.1 mm
https://www.phoenixcontact.com/us/products/2864419
01/17/2021Page2/7
Loop-powered isolators-MINI MCR-SL-1CP-I-I-2864419
Technical data
Dimensions
Depth 101.2 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Input data
Description of the input Current input
Number of inputs 1
Configurable/programmable no
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
max. input voltage 18 V
Max. input current 40 mA
Response current approx. 190 µA
Input voltage limitation < 2 V (20mA)
Voltage dissipation 1.9 V (I = 20 mA)
Output data
Output name Current output
Number of outputs 1
Configurable/programmable no
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output < 600 Ω (at I = 20 mA output signal)
Ripple < 10 mVrms (at 600 Ω)
Transmission Behavior 1:1 to input signal
Power supply
Supply voltage range no separate supply voltage necessary
Power consumption 34 mW
Connection data
Connection method Screw connection
Stripping length 12 mm
https://www.phoenixcontact.com/us/products/2864419
01/17/2021Page3/7
Loop-powered isolators-MINI MCR-SL-1CP-I-I-2864419
Technical data
Connection data
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient ≤ 0.002 %/K (of measured value / 100 Ω load)
Temperature coefficient, typical < 0.002 %/K (of measured value / 100 Ω load)
Cold junction errors
Typical cold point errors
Additional error, load-dependent < 0.03 % (of measured value / 100 Ω load)
Limit frequency (3 dB) 75 Hz
Step response (10-90%) 5 ms (at 600 Ω load)
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 50 V AC/DC
Test voltage input/output 1.5 kV (50 Hz, 1 min.)
Test voltage channel/channel 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color green
Housing material PBT
Mounting position any
Assembly instructions The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN61000-4-3
Evaluation criterion A
Designation Fast transients (burst)
https://www.phoenixcontact.com/us/products/2864419
01/17/2021Page4/7
Loop-powered isolators-MINI MCR-SL-1CP-I-I-2864419
Technical data
EMC data
Standards/regulations EN61000-4-4
Evaluation criterion B
Designation Conducted interferences
Standards/regulations EN61000-4-6
Evaluation criterion A
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
Designation Electromagnetic RF field
Standards/regulations EN61000-4-3
Evaluation criterion A
Standards/regulations EN61000-4-4
EN61000-4-5
Designation Conducted interferences
Standards/regulations EN61000-4-6
Evaluation criterion A
Electrical isolation Basic insulation according to EN 61010
Conformance CE-compliant
ATEX  II 3 G Ex nA II T6 X
UL, USA/Canada UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D
GL GL EMC 2 D
Conformance/approvals
Designation CE
Identification CE-compliant
Designation UL, USA/Canada
Identification UL508 Recognized
Class I, Div. 2, Groups A, B, C, D
Designation Shipbuilding approval
Certificate DNV GL TAA00000BW
Temperature B
Humidity B
Vibration B
EMC B
https://www.phoenixcontact.com/us/products/2864419
01/17/2021Page5/7
Loop-powered isolators-MINI MCR-SL-1CP-I-I-2864419
Technical data
Conformance/approvals
Enclosure A
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Application drawing
I
MINIMCR-SL-1CP-I-I
UE
U =1,7V
V
I
I
I
RB
UB
Block diagram
Zone2
passive
IN
Sensor/Field
OUT
PLC/DCS
4-wire
+
+
GND2
active
GND1
OUTIINI
1 5
26
7
8
3
4
OUTI
GND
US
5
6
1
2
PWR
max.18 VDC
Dimensional drawing
93,1 6,2
102,5
Classifications
eCl@ss
eCl@ss 10.0.1 27210120
eCl@ss 11.0 27210120
eCl@ss 4.0 27210100
https://www.phoenixcontact.com/us/products/2864419
01/17/2021Page6/7
Loop-powered isolators-MINI MCR-SL-1CP-I-I-2864419
Classifications
eCl@ss
eCl@ss 4.1 27210100
eCl@ss 5.0 27210100
eCl@ss 5.1 27210100
eCl@ss 6.0 27210100
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120
ETIM
ETIM 4.0 EC002653
ETIM 5.0 EC002653
ETIM 6.0 EC002653
ETIM 7.0 EC002653
UNSPSC
UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
UNSPSC 18.0 39121008
UNSPSC 19.0 39121008
UNSPSC 20.0 39121008
UNSPSC 21.0 39121008
Approvals
Approvals
Approvals
DNV GL / UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
ATEX / UL Recognized / cUL Recognized / EAC Ex / cULus Recognized
Approval details
https://www.phoenixcontact.com/us/products/2864419
01/17/2021Page7/7
Loop-powered isolators-MINI MCR-SL-1CP-I-I-2864419
Approvals
DNV GL https://approvalfinder.dnvgl.com/ TAA00000BW
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
cULus Recognized
Accessories
Accessories
Marking material
Marking label-MINI MCR-DKL-LABEL-2810272
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
Transparent cover-MINI MCR DKL-2308111
Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack marker
strip 6.2 mm
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com