L Page 2 SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE © 2008 TELEDYNE RELAYS
L\072008\Q2
Series L
Single Output to 25A, 280 Vac
DC Control
ENVIRONMENTAL SPECIFICATION
Min Max Unit
Operating Temperature –55 100 °C
Storage Temperature –55 100 °C
Input-Output Isolation 4000 Vrms
Output-Case Isolation 3300 Vrms
Rated Impulse Voltage 3300 Vrms
NOTES:
1. Electrical speci cations at 25 °C unless otherwise speci ed.
2. An external MOV is recommended for transient voltage protection
3. For 800Hz applications, contact factory.
4. For additional/custom options, contact factory.
OPTIONAL ADD-ONS
Please order add-ons separately:
• -12 — Themal pad installed.
Figure 3 — Series L
BLOCK DIAGRAM
AC
AC
+
–
Rc
Uc
Ic
024681012141618202224
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
Load Current (Arms)
Power Dissipation (W)
0 102030405060708090100
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
Ambient Temperature (°C)
8°C/W
6°C/W
4°C/W
2°C/W
Pd = Vd x I
with Vd =1.08 + 0.016 x I
THERMAL CHARACTERISTICS
Figure 4 — Current derating curves
OUTPUT (LOAD) SPECIFICATION
Min Max Unit
Operating Range
All Relays 24 280 V
Peak Voltage
All Relays 600 Vpeak
Load Current Range
L24D25C .05 25 Arms
L24D25G .05 25 Arms
L24D40G .05 40 Arms
Maximum Surge Current Rating
(Non-Repetitive)
L24D25 250 A
L24D40 350 A
On-State Voltage Drop 1.08 + (0.016xl) V
Synchronizing Level ± 25 V
O -State Leakage Current 1 mA
Turn-On Time 8.3 ms
Turn-O Time 8.3 ms
O -State dv/dt 500 A/μs
Operating Frequency 47 440 Hz
I2t for Match Fusing (<8.3 ms) 260 A2S