TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
1
PMF
Highlights & Features
Universal AC input voltage
Built-in active PFC and fan sp eed control
Full corrosion r esistant aluminium chassis
Conforms to harmonic current IEC/EN 61000-3-2, Class A
and Class D
Cold start -20°C at 100% load (231W)
Remo te ON/OFF is available as an option
Safety Standards
CB Certified for worldwide use
Model Number : PMF-4V320WC☐☐
Unit Weight: 0.86 kg
Dimensions (L x W x D): 215 x 115 x 50 mm
General Description
The PMF panel mount power supply series currently offers nominal output voltages of 4.2V. These power supply units come with
universal AC input from 85Vac to 264Vac and wide operating temperature of -10°C to +70°C. The built-in active PFC provides high
power factor and conforms to harmonic current IEC/EN 61000-3-2, Class A and Class D. This versatile series has two different
connector options (Front Face and Terminal Block) to satisfy different application needs. Remote ON/OFF function is also available for
the PMF series. All PMF power supplies conform to major international safety standards including IEC/EN/UL 60950-1 standards and
are fully compliant with RoHS Directive 2011/65/EU for env ironme ntal prot ect ion.
Model Information
PMF Pan el Mount Power Supply
Model
Number
Input Voltage Range Output
V
oltage
Output Curr
ent
PMF-4V320WC☐☐ 85-264Vac 4.2Vdc 55.0A
Model Number ing
CC Code
PM F 4V
320W
C
Panel Mount Product Series
F PFC Series Output Voltage Output Power
(320 W series
model)
Package Type
C Enclosed Connector Type
G Front Face
A – Terminal Block*
Variable
B – No Remote ON/OFF
R With Remote ON/OFF
*
*Options
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
2
Specifications
Input Ratings / Characteristics
Nominal Input Voltage 100-240Vac
Input Voltage Range 85-264Vac
Nominal Input Frequency 50-60Hz
Input Frequency Range 47-63Hz
Input Current < 5.00A @ 115Vac, < 2.50A @ 230Vac
Efficiency at 100% Loa d 76.5% typ. @ 230Vac
Max Inrush Current < 20A @ 115Vac, < 40A @ 230Vac
Power Factor 0.97 typ. @ 115V ac, 0.94 typ. @ 230Vac
Leakage Current < 1mA @ 240Vac
Output Ratings / Characteris tics
Nominal Output Voltage 4.2Vdc
Output Voltage Tolerance ± 2% (initial set point tolerance from factory)
Output Voltage Adjustment Range 3.78-4.62Vdc
Output Current 55.0A
Output Power 231W
Line Regulation ± 0.5% typ. (@ 115Vac & 230Vac)
Load Regulation ± 1.5% typ. (@ 115Vac & 230Vac)
PARD (20MHz) < 150mVpp @ 25°C
Rise Time 50ms typ. @ 115Vac & 230Vac (100% load)
Start-up Time 2500ms typ. @ 115Vac,
1000ms typ. @ 230Vac (100% load)
Hold-up Time 16ms typ. @ 115Vac & 230Vac
Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 5% (0.5V pk-pk) @ 115Vac & 230Vac (0-100% load)
Start-up with Capacitive Loads 8,000µF Max
Remote ON/OFF Function (Option) CN102 Output ON: 5-12.5V
Output OFF: 0-0.5V
(For more information, please refer to the details in the
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
3
Mechanical
Case Chassis Aluminium
Case Cover Aluminium
Dimensions (L x W x D) 215 x 115 x 50 mm
Unit Wei ght 0.86 kg
Indicator Green LED (DC OK)
Cooling System Forced Cooling
Terminal
PMF-4V320WCG
M3.5 x 9 Pins (Rated 300V/20A)
PMF-4V320WCA
M3.5 x 9 Pins (Rated 300V/15A)
Wire AWG 14-12*
*Only use wire tha t ca n wit hst an d ope r at in g temp er ature of more th an 12 5°C.
Environment
Surrounding Air Temperature Operating -10°C to +70°C (Cold start at -20°C)
Storage -25°C to +85°C
Power De-rating > 55°C de-rate power by 3.33% / °C
< 90Vac de-rate power by 2.5% / 1V
Operating Humidity 5 to 95% RH (Non-Condensing)
Operating Altitude 0 to 5,000 Meters
Shock Test (Non-Operating) IEC 60068-2-27, Half Sine: 50G for a duration of 11ms,
3 shocks for each 3 directions
Vibration (Non-Operating) IEC 60068-2-6, Random: 5Hz to 500Hz (2.09Grms);
20 min per axis for all X, Y, Z direction
Pollution Degree
2
Protections
Overvoltage 4.83-6.50V, Latch Mode
(AC power is recycled)
Overload / Overcurrent 105-135%, Hiccup Mode, Non-Latching
(Auto-Recovery)
Over Temperature Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Short Circuit Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Protection Against Shock Class I with PE* connection
*PE: Primary Earth
Reliability Data
MTBF > 700,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
Expected Cap Life Time 10 years (115Vac & 230V ac, 50% load @ 40°C)
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
4
Safety Standards / Directives
Electrical Safety TUV Bauart to EN 60950-1, UL/cUL recognized to UL
60950-1 and CSA C22.2 No. 60950-1, CB scheme to
IEC 60950-1, CCC to GB4943
CE In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
Material and Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolat i on Input to Output 3.0KVac
Input to Ground 2.0KVac
Output to Ground 0.5KVac
EMC
EMC / Emissions CISPR 22, EN 55022, FCC Title 47: Class B
Immunity to EN 55024
Electrostatic Discharge IEC 61000-4-2 Criteria A
1)
Level 3 Air Discharge: 8kV
Level 2 Contact Discharge: 4kV
Radiated Field IEC 61000-4-3 Level 2 Criteria A
1)
80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation
Electrical Fast Transient / Burst IEC 61000-4-4 Level 3 Criteria A
1)
1kV
Surge IEC 61000-4-5 Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Conducted IEC 61000-4-6 Level 2 Criteria A
1)
150kHz-80MHz, 3Vrms
Power Frequency Magnetic Fields IEC 61000-4-8 Criteria A
1)
1A/Meter
Voltage Dips IEC 61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable
Harmonic Current Emission IEC/EN 61000-3-2, Class A and Class D
Voltage Fluctuation and Flicker IEC/EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
5
Block Diagram
Device Descriptions
1) Input & Output terminal block connector
2) DC voltage adjustment potentiometer
3) DC OK control LED (Green)
4) Remote ON/OFF function connector (Option)
PMF-4V320WCG: Front Face
PMF-4V320WCA: Terminal Blo c k
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
6
Dimensions
L x W x D: 215 x 115 x 50 mm (PMF-4V320WCG: Front Face)
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
7
L x W x D: 215 x 115 x 50 mm (PMF-4V320WCA: Terminal Block)
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
8
Engineering Data
De-rating
Output De-rati ng VS. Input Voltage
Note
1. Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2. If the output capacity is not reduced when the
surrounding air temperature >55
°C, the
device will run into Over Temperature
Protection. When activated, the output
voltage will go into bouncing mode and will
recover when the surrounding air
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
3.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 20mm with adjacent units
while the device is in operation.
4.
Depending on the surrounding air
temperature and output load delivered by the
power supply, the device can be very hot!
5. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com f or more detai ls.
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation
> 55°C de-rate power by 3.33% / °C
No output power de-rating for the input
voltage from 90Vac to 264Vac
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
9
Assembly & Installation
Side Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw of maximum 5mm length (Refer to Fig. 4). This
is to maintain a safety distance between the screw and internal components.
Base Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw of maxi mum 4mm length (Refer to Fig. 4). This
is to maintain a safety distance between the screw and internal components.
Connector
This surface belongs to customer’s end system or panel where the power supply is mounted.
Base Mounting (Horizontal) Base Mounting (Vertical) Side Mounting (Horizontal)
Fig. 2 Recommended Mounting Orientations
Use flexible cable (stranded or solid) of AWG No. 14-12. The input/output connectors’ allowable current is 23A max per pin. User
should calculate and select the suitable wire specification (type/quantity/diameter) according to actual output current. The torque at
the connector shall not exceed 13Kgf.cm. The insulation stripping length should not exceed 0.275” or 7mm.
Recommended mounti ng t orq ue of the produ ct and its mounting acces sori es is 9~12K gf.cm.
Fig. 4 Assembly Reference
Only use M4 screw 5mm through the base mounting holes at
. This
is to keep a safe distance between the screw and internal components.
Only use M4 screws ≤ 4mm through the base mounting holes at . This
is to keep a safe distance between the screw and internal components.
Fig. 3 Mounting Hole Locatio ns an d the Safety Distance
Ensure the mounted device is kept at 4mm safety distance at all sides from other components and equipments. In addition, to ensure
sufficient convection cooling, always maintain a distance of ≥ 20mm from ventilated surfaces while the device is in operation.
Safety Distance
D1 = 4.0mm Min.
D2 = 20.0mm Min.
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
10
Safety Instructions
If user’s mounting orientation is not according to the recommended mounting orientations, please consult Delta for further
information.
The device is not recommended to be placed on low thermal conductive surface. For exampl e, plastics.
The enclosure of the device can become very hot depending on the ambient temperature and load of the power supply. Do not
touch the device while it is in operation or immediately after power is turned OFF. Risk of burning !
Do not touch the terminals while power is being supplied. Risk of electric shock.
Prevent any foreign metal, particles or conductors from entering the device through the openings during installation.
It may cause electric shock, safety hazard, fire and/or product failure.
Warning: When connecting the device, secure Earth connection before connecting L and N. When disconnecting the device,
remove L and N connections before removing the Earth connection. The power supply must be mounted by metal screws onto a
grounded metal surface. It is highly recommended that the Earth terminal on the connector be connected to the grounded metal
surface.
Accessories
LM-01: Top Fixing Bracket
This bracket is used to fix the power supply onto a flat
surface from the top.
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
11
Functional Manual
Remote ON/OFF Function You can remotely control the power supply unit
to turn ON/OFF by using an external DC source.
Follow the DC power source voltage and current
limiting defined in the table below.
Built-in Resistor Ri (ohm) Voltage Between RC+ and RC- (V) Input Current (mA)
Output ON Output OFF
820 5-12.5 0-0.5 20 Max
Notes
1. Remote ON/OFF circuits are isolated from input, output and PE.
2. Please check if the polarity of the wire connector is the same as the external DC source. If not, the power would not turn on and
the internal components may be damaged.
3. You do not need an external resistance RO for current limit while the output voltage of external DC source is within the range of
5-12.5V. If the output voltage exceeds 12.5V, please use the following equation for the value of current limit resistance RO.
𝑅𝑂=
𝑉𝑐𝑐 (3.5 + 0.006𝑅𝑖)
0.006
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
12
Functions
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time
required for the output to reach 95% of its set value, after the input voltage is removed.
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Inrush Current
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak
value decreases exponentially during subsequent cycles of AC
voltage.
Dynamic Response
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 0 to
100% of its rated current.
TECHNICAL DATASHEET
PMF Panel Mount Power
Supply
4.2V 23 1W 1
Phase
/ PMF-4V320WC
□□
All parameters are specified at 25°C ambient unl es s otherwise indicat ed.
www.DeltaPSU.com (June 2014, Rev. 00)
13
Overload & Overc ur rent Protections
The power supply’s Overload (OLP) and Overcurrent (OCP)
Protections will be activated when output current exceeds
105-135% of IO (Max load). In such occurrence, the VO will start
to droop and once the power supply has reached its maximum
power limit, the protection is activated and the power supply will
go into “Hiccup mode” (Auto-Recovery). The power supply will
recover once the fault condition of the OLP and OCP is removed
and IO is back within the speci f icat ion s.
It is not recommended to prolong the duration of IO when it is
<105% but >100%, since it may cause damage to the PSU.
Short Circuit Protection
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied,
the output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power
supply will return to normal operation after the short circuit is
removed.
Overvolt age Prot ec tio n
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”.
The power supply should be latch.
Over Temperature Protection
As mentioned above, the power supply also has Over
Temperature Protection (OTP). In the event of a higher operating
temperature at 100% load, the power supply will run into OTP
when the operating temperature is beyond what is recommended
in the de-rating graph. When activated, the output voltage will go
into bouncing mode until the temperature drops to its normal
operating tem perat ur e as reco mmended in the de-rating gra ph.
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and ele ctr on ic equ ip ment”.
This product conforms to this standard.
PFC Norm EN 61000-3-2
Line Current Harmonic content
Typically, the input current waveform is not sinusoidal due to the periodical peak charging of the input capacitor.
In industrial environment, complying with EN 61000-3-2 is only necessary under special conditions. Complying
to this standard can have some technical drawbacks, such as lower efficiency as well as some commercial
aspects such as higher purchasing costs. Frequently, the user does not profit from fulfilling this standard,
therefore, it is important to know whether it is mandatory to meet this standard for a specific application.
Mouser Electronics
Authorized Distributor