Table 7-14 Table 1: "Maintenance required" diagnostics status in the "AFDiSD x - (online)" > "Main line" - T1 or T2 dialog
Error Possible causes of error Corrective measures
Voltage values of
the segment below
the set warning limit
Additional field distributors or field devices were
added to the bus segment.
Remove the additional devices or save the set
topology again (see step 7 "Manually configuring
the extended fieldbus diagnostics (Page 23)").
Cable length changed when last serviced Save the set topology again (see step 7 "Manually
configuring the extended fieldbus diagnostics
(Page 23)").
Terminal resistance is too high (corrosion, miss‐
ing screw)
Check the terminal resistance of the affected field
distributor and, if necessary, of the adjacent field
distributor.
Voltage values of
the segment above
the set warning limit
Cable length changed when last serviced Save the set topology again (see step 7 "Manually
configuring the extended fieldbus diagnostics
(Page 23)").
Current values of
the segment below
the set warning limit
Current consumption of the field distributors or
field devices has changed. This may indicate im‐
minent failure of the field distributor or field device.
Replace the affected field distributor or field de‐
vice.
Current values of
the segment above
the set warning limit
Additional field distributors or field devices were
added to the bus segment.
Check if additional field distributors or field devi‐
ces were added to the bus segment. Remove
these or save the set topology again (see step 7
"Manually configuring the extended fieldbus diag‐
nostics (Page 23)").
Unknown device connected to bus segment or
faulty wiring
Check the environment of the field distributor for
unknown devices on the bus segment (e.g. resis‐
tive load between "+" and "-").
Current consumption of the field distributors or
field devices has changed. This may indicate im‐
minent failure of the field distributor or field device.
Replace the affected field distributor or field de‐
vice.
Table 7-15 Table 2: "Maintenance required" diagnostics status in the "AFDiSD x - (online)" > "Main line" - General dialog
Error Possible causes of error Corrective measures
Signal level below
the set warning limit
Unnecessary terminating resistors were added to
the bus segment.
Remove unnecessary termination resistors.
Terminal resistance is too high (corrosion, miss‐
ing screw)
Check the terminal resistors.
Cable length changed Save the set topology again (see step 7 "Manually
configuring the extended fieldbus diagnostics
(Page 23)").
Signal level above
the set warning limit
Terminal resistance is too high (corrosion, miss‐
ing screw)
Check the terminal resistors.
Bus terminator switch on coupler disconnected Check the coupler to determine if the bus termi‐
nator switch is set to ON.
Cable length changed Save the set topology again (see step 7 "Manually
configuring the extended fieldbus diagnostics
(Page 23)").
Alarm, fault and system messages
7.4 Elimination of errors with the extended fieldbus diagnostics
Extended fieldbus diagnostics in PROFIBUS PA
Operating Instructions, 05/2015, A5E32591680-AA 63