23/06/2014 www.crouzet.com FN filling or emptying with alarm FN Part number 84870503 Automatic control and regulation of liquid levels. 2 sensitivity ranges. Filling or emptying function selected via dip switch. High or low alarm selected via dip switch. Memory can be selected. LEDs indicate state of power supply, output relay and alarm relay. Part numbers 84 870 503 Type Voltages FN 120 VAC Specifications Supply voltage Un Operating range Nominal power Maximal power Immunity from micro power cuts Delay on pick-up Response time on power up Insulation coordination 230, 120, 48 and 24 V AC 50/60 Hz galvanic isolation via transformer 0.85 to 1.15 Un except 120 V AC : 0.85 to 1.1 Un 3 VA at Un 4 VA at Un + 15 % 10 ms T1 = approx. 2 s T4 = 500 ms Category III, degree of pollution 2 conforming to IEC/EN 60664-1 : 4 kV/2 Sensitivity range FN Sensitivity range FHLS Display precision Electrode voltage Electrode current Response time on immersion Response time on emersion 5 k100 k 250 5 k 30 % with maximum sensitivity 15 V AC (50/60 Hz) 1 mA T2 = 400 ms T3 = 700 ms Output Breaking capacity 2 AgCdO changeover FN LS : 2000 VA FN : 80 W FN LS : 8 A AC FN : 8 A DC FN LS : 100 mA AC FN : 100 mA DC FN LS : 250 V AC FN : 250 V DC Maximum breaking current Minimum breaking current Max. breaking voltage Mechanical life (operations) 2 x 106 Electrical life AC 12 2000 VA - 105 operations Cos = 0,3 - 6000 operations L/R = 300 ms - 6000 operations Electrical life AC 15 Electrical life AC 13 Housing material Terminal capacity Temperature limit operation (IEC 68.1.14) (C) Temperature limits stored (IEC 68.1.1/2) (C) Relative humidity (no condensation) Weight (g) Self-extinguishing 2 x 1,5 mm2 with ferrule 2 x 2,5 mm2 without ferrule -20 +60 -30 +70 93 % (+2 % ; -3 %) 280 * Creation * TRADOS Empty Field Principles Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 23/06/2014 www.crouzet.com On power-up, probe AI. is submerged, relays R1 and R2 are energised and the pump is ON : filling starts, the LED for relay R1 is lit. When the level reaches the Max probe, relay R1 de-energises and the pump is OFF : filling stops, the LED for relay R1 goes off. Relay R1 re-energises when the Min probe emerges. In the event of a fault (level continues to fall) probe AI. emerges, relay R2 deenergises ans the alarme is triggered : the LED for relay R2 is lit. This fault can be stored No Legend Memory OFF Memory ON T1 : Delay on pick-up T2 : Response time on immersion T3 : Response time on emersion T4 : Response time on power-down Principles On power-up, the level in the tank is low, relays R1 and R2 are energised and the pump is ON : filling starts, the LED for relay R1 is lit. When the level reaches the Max probe, relay R1 de-energises and the pump is OFF : filling stops, the relay LED goes off. If, in the event of a fault, the level continues to rise and reaches proble AI., relay R2 de-energises and the alarme is triggered : the LED for relay R2 is lit. This fault can be stored. Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 23/06/2014 No www.crouzet.com Legend Memory OFF Memory ON T1 : Delay on pick-up T2 : Response time on immersion T3 : Response time on emersion Principles On power-up, probes Min, Max and AI. are submerged, relays R1 and R2 are energised and the pump is ON : emptying starts, the LED for relay R1 is lit. When the Min probe emerges, relay R1 goes off. If, in the event of a fault, the level continues to fall and probe AI. emerges, relay R2 de-energises and the alarm is triggered : the LED relay R2 is lit. This fault can be stored. No Legend Memory OFF Memory ON T1 : Delay on pick-up T2 : Response time on immersion T3 : Response time on emersion Principles Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 23/06/2014 www.crouzet.com On power-up, probes Min, Max are submerged and probe AI. is above the level of the liquid. Relays R1 and R2 are energised and the pump is ON : emptying starts, the LED for relay R1 is lit. When the Min probe emerges, relay R1 de-energises and the pump if OFF : emptying stops, the LED for relay R1 goes off. If, in the event of a fault, the level continues to rise a nd reaches proble AI., relay R2 de-energises and the alarm is triggered : the LED for relay R2 is lit. This fault can be stored. No Legend Memory OFF Memory ON T1 : Delay on pick-up T2 : Response time on immersion T3 : Response time on emersion T4 : Response time on power-down Principles Operating principle Control of the level of a conductive liquid at specific points (high and low levels) with an alarm for a level which is abnormally high or low. The principle is based on measurement of the apparent resistance of the liquid between submerged probes. When this value is lower than the present threshold on the unit front face, the output relay R1 and/or the alarm relay R2 change state. The avoid electrolytic phenomena, an AC current runs across the probes. Adjusting sensitivity Set the sensitivity so that the relay will change state when the probes are in contact with the liquid. Then check that the relay returns to its initial position as soon as the probes emerge. In certain applications, fine-tuning the sensitivity prevents inappropriate detection, such as the presence of foam or bubbles on the surface or the occurrence of leakage impedance between probes (extended line capacity, humidity, etc). Note : Latching of the alarm relay R2 in de-energised state if a fault occurs can the programmed via a switch on the underside of the underside of the unit (only when the unit is switched off). To reset alarm relay R2, cut the power, as long as the levels are reset. Programming The FN level controller can be programmed using 3 switches on the lower panel : Note : Memory, Alarme and Function must only be selected when the unit is switched off. No Legend Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 23/06/2014 www.crouzet.com Memory Alarm Function Low Emptying High Filling Dimensions (mm) FN / FN LS Connections Regulating with "up" filling control Note : Dans le cas ou le reservoir est conducteur (metal), il peut etre utilise comme electrode de reference (C). Une LED verte visualise l'alimentation Une LED jaune visualise l'etat du relais de sortie Une LED rouge visualise l'etat du relais d'alarme Legend A1 - A2 : Supply voltage Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 23/06/2014 11 - 12 - 14 : Output relay (R1) 21 - 22 - 24 : Alarm output relay (R2) C - Min - Max - Al. : Probe inputs Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected www.crouzet.com Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Crouzet: 84870503