2-channel repeater power supply for operating 2-wire measuring transducers, input: 4…20 mA (powered), output:
4…20 mA (active), bidirectional transmission of digital HART communication signals, with screw connection
Key Commercial Data
Packing unit 1 STK
Weight per Piece (excluding packing) 160.000 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 12.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
https://www.phoenixcontact.com/us/products/2904089
09/06/2016Page2/6
Signal isolator-MACX MCR-SL-RPSS-2I-2I-2904089
Technical data
Ambient conditions
Degree of protection IP20
Input data
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (at 20 mA)
Output data
Signal output Current output
Current output signal 4 mA ... 20 mA (active)
Transmission Behavior 1:1 to input signal
Load/output load current output ≤ 450 Ω (20 mA)
≤ 375 Ω (24 mA)
Output behavior in the event of an error < 3.6 mA (In the event of cable break at the input (as per NE 43))
> 22.5 mA (In the event of cable short circuit at the input (as per NE 43))
Power supply
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption < 100 mA (24 V / 20 mA)
Power consumption < 1.4 W (at 24 V DC / 20 mA)
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Screw thread M3
Connection method Screw connection
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
General
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 1.3 ms (for 4 mA ... 20 mA step)
Status display Green LED (supply voltage)
https://www.phoenixcontact.com/us/products/2904089
09/06/2016Page3/6
Signal isolator-MACX MCR-SL-RPSS-2I-2I-2904089
Technical data
General
Flammability rating according to UL 94 V0
Degree of pollution 2
Overvoltage category II
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Interference emission EN 61000-6-4
Housing material PA 66-FR
Color green
Designation Input/output, power supply
Electrical isolation 300 Vrms (Rated insulation voltage (overvoltage category II; degree of
pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output 1/output 2/ power supply
Electrical isolation 1.5 kV (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Data communication (bypass)
HART function Yes
Protocols supported HART
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 61000-6-4
Flammability rating according to UL 94 V0
Conformance CE-compliant, additionally EN 61326
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Drawings
https://www.phoenixcontact.com/us/products/2904089
09/06/2016Page4/6
Signal isolator-MACX MCR-SL-RPSS-2I-2I-2904089
Block diagram
Zone 2
GND +24V
PLC / DCS
Sensor / Field
IN OUT
CH1
CH2
AI
passive
3.2
3.1
+
-
HHT
passive
2.1
2.2 -
+
HHT
+
-
CH2
3.2
3.1
2.2
2.1
GND 1.2
1.1
+24V
Power
active
active
5.2
5.1
4.2
4.1
+
-
CH1
5.2
5.1
HHT
4.2
4.1
HHT
Pictogram
POWER
OUT
OUT
IN
POWER
IN
POWER
II
II
Classifications
eCl@ss
eCl@ss 4.0 27210120
eCl@ss 4.1 27210120
eCl@ss 5.0 27210120
eCl@ss 5.1 27210120
eCl@ss 6.0 27210120
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120
ETIM
ETIM 3.0 EC001485
ETIM 4.0 EC002498
ETIM 5.0 EC002653
UNSPSC
UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Approvals
Approvals
https://www.phoenixcontact.com/us/products/2904089
09/06/2016Page5/6
Signal isolator-MACX MCR-SL-RPSS-2I-2I-2904089
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htmFILE E 330267
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htmFILE E 330267
Functional SafetyBVS Pb 04/13
cULus Listed
Accessories
Accessories
DIN rail connector
DIN rail bus connectors-ME 6,2 TBUS-2 1,5/5-ST-3,81 GN-2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Power module
https://www.phoenixcontact.com/us/products/2904089
09/06/2016Page6/6
Signal isolator-MACX MCR-SL-RPSS-2I-2I-2904089
Accessories
Power and error message module-MACX MCR-PTB-2865625
Power and fault signaling module with screw connection, including corresponding ME 17,5 TBUS 1,5/ 5-ST-3,81 GN DIN
rail connector
Power and error message module-MACX MCR-PTB-SP-2924184
Power and fault signaling module with push-in connection, including corresponding ME 17,5 TBUS 1,5/ 5-ST-3,81 GN
DIN rail connector
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com