PRODUCT INFORMATION
ÖLFLEX® TRAY II
75 °C WET Rating + Sunlight Resistant Rating: Outdoor use in the USA
Application range
Industrial machinery; plant engineering
Unprotected 600V operation on cable tray in the USA, incl. 6 ft. Exposed Run laying sections
Compliant with Tool machines: (UL) MTW
Outdoor use and Direct Burial in the USA
Generatori Eolici in USA: (WTTC) Wind Turbine Tray Cable
Product features
Flame-retardant according to CSA FT4
UL Vertical-Tray Flame Test
Oil-resistant according to UL OIL RES I & II
Water-resistant, UL 75°C WET rating
UV resistant (SUN RES), Ozone resistant
Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG)
Norm references / Approvals
USA: (UL) TC-ER [E171371], (UL) MTW [E155920], (UL) WTTC [E323700], Submersible Pump (14 - 2 AWG), (UL) PLTC-ER
(18 - 12 AWG) [E216027], (UL) ITC-ER (18 - 12 AWG) [E196134], (UL) DP-1 [E233406], UL AWM (18 - 2 AWG) [E100338]
UL OIL RES I/ II, 75°C WET, 90°C DRY, SUN RES, DIR BUR, NEC/NFPA 70, NFPA 79
CAN: c(UL) CIC/ TC 600V FT4 (< 250 kcmil) [E171371], CSA AWM I/II A/B FT1
Product Make-up
Fine-wire strand made of bare copper wires
Insulation: PVC+nylon sheath (PA skin)
Outer jacket: Specially formulated thermoplastic polymer
Color of the outer jacket: Black
Technical Data
Classification ETIM 5: ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: Control cable
Classification ETIM 6: ETIM 6.0 Class-ID: EC000104
ETIM 6.0 Class-Description: Control cable
Core identification code: Black with white numbers
Conductor stranding: Fine copper wire strands
Torsion movement in WTG: TW-0 & TW-2, refer to Appendix T0
Minimum bending radius: Static/Occ. moved: 5/15 x OD*
Nominal voltage: UL/CSA: 600 V (TC, MTW, CIC), WTTC 1000 V
UL/CSA: 1000 V (AWM)
IEC: U0/U = 600/1000 V
Protective conductor: G = with GN-YE protective conductor
X = without protective conductor
Temperature range: -40°C (static)/ -25°C (occ. moved) to +90°C (AWM: +105°C)
Note
Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon
request.
Last Update (05.07.2019) 2 / 5
©2019 Lapp Group - Technical changes reserved
Product Management www.lappkabel.de
You can find the current technical data in the corresponding data sheet.