EMC CHARACTERISTICS
Conducted emissions EN55022 (See Note 7) Level A
EN55022 (See Note 7) Level B
Radiated emissions EN55022 Level A
(See Longform Datasheet)
Immunity:
ESD air EN61000-4-2 8 kV,15 kV
ESD contact EN61000-4-2 6 kV,8kV
Radiated field enclosure EN61000-4-3 10 V/m
Conducted (DC power) EN61000-4-6 10 V
Conducted (signal) EN61000-4-6 10 V (See Note 5)
Input transients ETS 300 132-2, ETR 283
GENERAL SPECIFICATIONS
Efficiency See table
Basic insulation Input/output 1500 Vdc
Switching frequency 5 V 300 kHz typ.
(Fixed) 3.3 V 220 kHz typ.
Approvals and TÜV Product Service
standards (See Note 8) UL/cUL60950
Material flammability UL94V-0
Weight 45 g (1.59 oz)
MTBF MIL-HDBK-217F 1,034,000 hours
Representative model: 100% load, ground benign
BELLCORE 332 591,000 hours
ENVIRONMENTAL SPECIFICATIONS
Thermal performance Operating ambient -40 °C to +90 °C
temperature
Non-operating -40 °C to +125 °C
Altitude derating 3,000 m 20%
(above sea level) 10,000 m 50%
DC-DC CONVERTERS 100 W DC-DC Isolate d C onv ert ers 1
2 YEAR WARRANTY
EXB100 Series
Single output
•Ultra wide trim range, 60% to 110% (1.08 Vdc to 5.5 Vdc)
•High efficiency, 91.5% @ 5 Vdc, 90.5% @ 3.3 Vdc
•Basic insulation (input to output)
•Industry standard half-brick pin-out
•No minimum load
•Overvoltage and overtemperature protection
•Remote ON/OFF
•Available RoHS compliant
The EXB100 series of 100 W single output isolated dc-dc converters are specially
designed to meet the power needs of low voltage silicon. Housed in an open-frame
package with standard footprint, these latest generation converters offer efficiencies as
high as 91.5% (typical on 5 V at 20 A). The series comprises two 48 V input models
with 5 V and 3.3 V outputs. The 3.3 V model features a wide input range, trimmable
output voltage and 30 A output (the 5 V model is limited to 20 A). Remote sense and
remote ON/OFF facilities are included as standard, and the converters are
comprehensively protected against overcurrent, overvoltage and overtemperature
conditions.
NEW Product
All specifications are typical at nominal input, full load at 25 °C unless otherwise stated SPECIFICATIONS
File Name: exb100s.pdf Rev: 18 Apr 2006
OUTPUT SPECIFICATIONS
Voltage adjustability 60% to 110%
Output setpoint accuracy 1.5%
Line regulation Low line to high line ±0.2% max.
Load regulation Full load to min. load ±0.4% max.
Total error band 3.0%
Minimum load 0%
Overshoot At turn-on and turn-off None
Undershoot None
Ripple and noise (See Note 1) 100 mV pk-pk
5 Hz to 20 MHz 50 mV rms
Transient response Deviation 150 mV
(See Note 2) 300 µs recovery to
within total error band
INPUT SPECIFICATIONS
Input voltage range 36-75 Vdc
Input current No load 150 mA
Remote OFF 20 mA
Input current (max.) (See Note 3) 3.15 A max. @ Io max.
and Vin = 36-75 Vdc
Input reflected ripple (See Note 4) 60 mA (pk-pk)
Remote ON/OFF (See Note 5)
Logic compatibility Open collector ref to -input
ON >2 Vdc
OFF <1.2 Vdc
Undervoltage lockout Power up 36 V
Power down 30 V
Start-up time Power up 40 ms
(See Note 6) Remote ON/OFF 35 ms