ITEMS MODEL JWS480P-24 JWS480P-48
3 Peak Output Current (*1) A40 20
4 Average Output Power W480 480
5 Peak Output Power (*1) W960 960
6 Efficiency (Typ) (*2) %80 80
8 Input Current (100/200VAC)(Typ) (*2) A
9 Inrush Current(Typ) (*4) -
10 PFHC -
11 Power Factor (100/200VAC)(Typ) (*2) -
13 Maximum Ripple & Noise mV 240 480
(*5) mV 360 720
16 Temperature Coefficient Less than 0.02%/°C
17 Over Current Protection (*8) A 40.8 ~ 20.4 ~
19 Hold-up Time (Typ) (*10) -20ms
0.75mA MAX, 0.25mA(Typ) at 100VAC / 0.57mA(Typ) at 230VAC
21 Remote Sensing - Possible
22 Remote ON/OFF control - Possible
PF (Open Collector Output)
24 Parallel Operation -
25 Series Operation - Possible
-10 ~+65°C( -10 ~+50°C:100%, +60°C:70%,+65°C:55%)
27 Operating Humidity - 30 ~ 90%RH (No dewdrop)
31 Withstand Voltage -Input - FG:2kVAC(20mA), Input - Output:3kVAC (20mA)
32 Isolation Resistance -
More than 100Mohm Output - FG...
More than 10Mohm Output - CNT...100VDC at 25°C and 70%Rh
33 Vibration -At no operating, 10-55Hz (Sweep for 1min)
2G Constant, X, Y, Z 1hour each.
35 Safety (*12) -Built to meet UL1950, CSA950, EN60950,VDE0160.
Built to meet DENTORI.
36 Conducted Emission -Built to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A.
37 Radiated Emission -Built to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A.
39 Size (WxHxD) mm 160 x 92 x 200 ( Refer to Outline Drawing )
*Read instruction manual carefully, before using the power supply unit.
=NOTES=
*1. Operating time at peak output is less than 10sec.(Duty<=0.5)
*2. At 100/200VAC, Ta=25°C and average output power.
*3. For cases where conformance to various safety specifications (UL, CSA, EN) are required,
input voltage range will be 100-240VAC(50/60Hz).
*4. First in-rush current. Not applicable for the in-rush current to Noise Filter less than 0.2ms.
*5. Measure with EIAJ RC-9131A probe, Bandwidth of scope :100MHz.
*6. 85 - 265VAC , constant load.
*7. No load - Average load, constant input voltage.
*8. Constant current limit with automatic recovery.
Peak current conditions more than 10 seconds, which could be result of shut down the output voltage.
*9. OVP circuit will shut down output, manual reset (Line recycle).
At 100/200VAC nominal output voltage and average output current.
Measured by the each measuring method of UL, CSA, EN and DENTORI(at 60Hz).
Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or averge output current, whichever is greater.
- As for other mountings, refer to derating curve (A183-01-02_).
As for DENTORI, built to meet at 100VAC.
Output - FG:500VAC(100mA), Output-CNT:100VAC(100mA) for 1min.
20A at 100VAC, 40A at 200VAC
Built to meet EN61000-3-2
A1830101_Pdf.xls