Enclosure ventilation using a filter fan and exhaust filter
FILTER FAN
FF 018 | 14 - 69 CFM
Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can
be reduced by channeling cooler filtered outside air into the enclosure thus expelling heated internal air. The
resulting air flow prevents formation of localized heat pockets and protects the electronic components from
overheating. The plastic used for the hood of this filter fan series is impact and UV light resistant. These filter fans
are intended for indoor use.
> Very low noise
> Minimal mounting depth
> Functional design
> Time-saving installation
> UV resistant plastic
¹ air volume increases by 15% when operating AC 230 V filter fans at 60 Hz
TECHNICAL DATA
Axial fan, ball bearing service life min. 50,000 h at 77 °F (25 °C) and 65 %RH
aluminum fan body, plastic rotor
Connection 2 wires w/ cage clamps, AWG 14 (2.5 mm²), length 4” (100 mm)
Housing (filter fan and exhaust filter) plastic, UL 94V-0, light grey
Hood (filter fan and exhaust filter) plastic, UL 94V-0, light grey;
UV light resistant according to UL 746C (f1)
Mounting frame with double-sided industrial adhesive for mounting to the
outside of enclosure; certain operating circumstances may
make the additional use of screws necessary; cut-out
template included
Filter media rating G4 acc. to DIN EN 779, filtering degree 94%
Filter material synthetic fiber with progressive construction, temperature
resistant to 212 °F, self-extinguishing class F1;
moisture resistant to 100 %RH, reusable - can be cleaned by
washing or vacuuming
Operating / Storage temperature +14 to +158 °F (-10 to +70 °C ) / -40 to +158 °F (-40 to +70 °C)
Operating / Storage humidity max. 90 %RH (non-condensing)
Protection class / Protection type I (grounded) / IP55 (according to VDE), UL Type 12
Approvals UL File No. E234324 (all), GOST TR (all), VDE (AC 230 V only)
Special features
> The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet.
> Functional design of the intake and exhaust fan hoods very effectively prevents direct infiltration of falling water and
dust. The advantage is that the filter mat does not rapidly become contaminated with dirtand therefore does not need to be
exchanged as often.
> The air channeling makes the filter fan particularly quiet in operation.
> The direction of air flow can easily be switched by reversing the axial fan.
> EMC versions and other voltages are available upon request.
Part No. Operating
voltage
Air volume, free
blowing
Air volume with
exhaust filter
Current
consumption
Power
consumption
Average noise level
(DIN EN ISO 4871)
Mounting
depth
Enclosure
cut-out
Weight (approx.)
01800.0-00 AC 230 V, 50 Hz¹ 12 cfm (21 m³/h) 9 cfm (16 m³/h) 80 mA 13 W 31 dB (A) 1.8” (45 mm) 3.8 x 3.8” 1.3 lbs. (0.6 kg)
01800.0-01 AC 120 V, 60 Hz 14 cfm (24 m³/h) 11 cfm (18 m³/h) 160 mA 13 W 31 dB (A) 1.8” (45 mm) 3.8 x 3.8” 1.3 lbs. (0.6 kg)
01801.0-00 AC 230 V, 50 Hz¹ 32 cfm (55 m³/h) 25 cfm (42 m³/h) 100 mA 15 W 40 dB (A) 2.3” (58 mm) 4.9 x 4.9” 2.2 lbs. (1.0 kg)
01801.0-01 AC 120 V, 60 Hz 37 cfm (63 m³/h) 28 cfm (48 m³/h) 180 mA 15 W 40 dB (A) 2.3” (58 mm) 4.9 x 4.9” 2.2 lbs. (1.0 kg)
01802.0-00 AC 230 V, 50 Hz¹ 60 cfm (102 m³/h) 40 cfm (68 m³/h) 100 mA 15 W 39 dB (A) 3.4” (86 mm) 6.9 x 6.9” 2.9 lbs. (1.3 kg)
01802.0-01 AC 120 V, 60 Hz 69 cfm (117 m³/h) 46 cfm (78 m³/h) 180 mA 15 W 39 dB (A) 3.4” (86 mm) 6.9 x 6.9” 2.9 lbs. (1.3 kg)
www.stegousa.com08.08.2014 | Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com
Time-saving assembly and maintenance
STEGO's filter fans are easily installed by one person from outside the cabinet.
1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and
grease. A template for the enclosure cut-out is included with the filter fan.
2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the
cabinet opening. The frame stays permanently in the cabinet.
3.) Electrically connect the axial fan using the cage clamp connectors. Push the unit into the mounting frame.
Affix using screws if necessary.
4.) Insert the filter mat in the hood. Clip on. Finished.
To change the filter mat, simply remove the filter hood, insert the new mat and snap the hood back again. No
tools are required. Maintenance of the fan can easily be performed without removing the mounting frame (2).
Size 1
TECHNICAL DRAWINGS
DRILLING TEMPLATE FOR MOUNTING FRAME
Installation sketch
Size 2 Size 3
EXHAUST FILTER EF 118
Part No. Mounting depth Enclosure cut-out Weight (approx.) Filter mat Protection type
11800.0-00 0.6” (16 mm) 3.8 x 3.8” 0.6 lbs. (0.3 kg) G4 acc. to DIN EN 779, filtering degree 94% IP552
11801.0-00 0.6” (16 mm) 4.9 x 4.9” 0.8 lbs. (0.4 kg) G4 acc. to DIN EN 779, filtering degree 94% IP552
11802.0-00 0.6” (16 mm) 6.9 x 6.9” 1.3 lbs. (0.6 kg) G4 acc. to DIN EN 779, filtering degree 94% IP552
² according to VDE
FILTER MATS FM 086 / FFM 086
Filter mat 3.5 x 3.5” (89 x 89 mm) 4.6 x 4.6” (118 x 118 mm) 6.6 x 6.6” (168 x 168 mm)
G4 (1 packing unit = 3 pcs.) Part No. 08600.0-00 Part No. 08601.0-00 Part No. 08602.0-00
F5 (1 packing unit = 3 pcs.) Part No. 08603.0-00 Part No. 08604.0-00 Part No. 08605.0-00