Switch Mode Power Supply
S8JX (15/35/50/100/150/300/600-W Models)
Easy-to-use, Widely range from 15 W to 600 W (Output Voltage: 5 V to 48 V)
Easy Mounting:
Front-mounted type, DIN rail-mounted type are
available.
Screw-mount at the top. (except 300-/600-W models)
Safety standards:
UL 508/60950-1
cUL CSA C22.2 No. 107.1
cUR CSA C22.2 No. 60950-1
EN 50178 (= VDE 0160) Over voltage
category III
EN 60950-1 (= VDE 0805 Teil 1)
EMC: Conforms to EN 61204-3.
(EMI:EN55011 ClassA)
Input conditions:
The input voltage range of 15-W, 35-W,
50-W, 100-W, and 150-W models has
been increased to 80 to 370 VDC (EC
Directives and safety standards do not
apply.).
S8JX-P Series with EMI ClassB and Power Factor Correction is newly
added to S8JX Series.
(Applicable to all capacities from 50 W to 600 W)
Limits for harmonic current emissions (conforms to
EN61000-3-2)
Conforms to EMI EN55011 Class B
Applicable to input free voltage: 100 to 240 VAC
Extended DC input voltage range: 80 to 370 VDC
* DC input is not subject to EC directives and safety standards.
Easy mounting: Front-mounting bracket type and
DIN-Rail mounting type are included
as standard with the product.
Screw-mount at the top.
(except 300-/600-W models)
Safety standards
- UL508/60950-1, cUL CSA C22.2 No.107.1,
cUR CSA C22.2 No.60950-1
- EN50178 (=VDE0160) Over voltage category III
EN60950-1 (=VDE0805 Teil1)
<Applicable only for 300 W and 600 W>
High capacity application-covered functions are
included as standard with the product.
Alarm detection function, Remote control function,
Remote sensing function
S8JX-G Series
S8JX-P Series
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Refer to Safety Precautions on page 55.
S8JX
2
S8JX-G S8JX-P
Common Precautions
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information on page 3.
1. Power Ratings
015: 15 W
035: 35 W
050: 50 W
100: 100 W
150: 150 W
2. Output Voltage
05: 5 V
12: 12 V
15: 15 V
24: 24 V
48: 48 V
3. Configuration (15/35/50/100/150 W model)
None: Open type
C: Covered
4. Configuration/mounting
None: Front-mounting
D: DIN Rail-mounting
1. Power Ratings
300: 300 W
600: 600 W
2. Output Voltage
05: 5V
12: 12 V
24: 24 V
48: 48 V
3. Configuration/mounting (covered type)
C: Front-mounting
CD: DIN Rail-mounting
Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
15-/35-/50-/100-/150-W Models
1234
S8JX-G@@@@@@@
300-/600-W Models
1 2 3
S8JX-G@@@@@@
S8JX
3
S8JX-G S8JX-P
Common Precautions
Ordering Information
List of Models
Note: For details on normal stock models, contact your nearest OMRON representative.
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan Model
Covered Power
Supplies
100 to 240 VAC
(free)
(80 to 370 VDC *)
S8JX-G15005@@:
Switchable between 100
to 120 VAC and 200 to
240 VAC. (DC power
cannot be input.)
15 W
5 V 3 A
No
S8JX-G01505CD
12 V 1.3 A S8JX-G01512CD
15 V 1 A S8JX-G01515CD
24 V 0.65 A S8JX-G01524CD
48 V 0.35 A S8JX-G01548CD
35 W
5 V 7 A S8JX-G03505CD
12 V 3 A S8JX-G03512CD
15 V 2.4 A S8JX-G03515CD
24 V 1.5 A S8JX-G03524CD
48 V 0.75 A S8JX-G03548CD
50 W
5 V 10 A S8JX-G05005CD
12 V 4.2 A S8JX-G05012CD
24 V 2.1 A S8JX-G05024CD
48 V 1.1 A S8JX-G05048CD
100 W
5 V 20 A S8JX-G10005CD
12 V 8.5 A S8JX-G10012CD
24 V 4.5 A S8JX-G10024CD
48 V 2.1 A S8JX-G10048CD
150 W
5 V 30 A S8JX-G15005CD
12 V 13 A S8JX-G15012CD
24 V 6.5 A S8JX-G15024CD
48 V 3.3 A S8JX-G15048CD
100 to 120 VAC
200 to 240 VAC
(Switchable)
300 W
5 V 60 A Yes S8JX-G30005CD
12 V 27 A S8JX-G30012CD
24 V 14A No S8JX-G30024CD
48 V 7A S8JX-G30048CD
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan Model
Open type Power
Supplies
100 to 240 VAC
(free)
(80 to 370 VDC *)
S8JX-G15005@@:
Switchable between 100
to 120 VAC and 200 to
240 VAC. (DC power
cannot be input.)
15 W
5 V 3 A
No
S8JX-G01505D
12 V 1.3 A S8JX-G01512D
15 V 1 A S8JX-G01515D
24 V 0.65 A S8JX-G01524D
48 V 0.35 A S8JX-G01548D
35 W
5 V 7 A S8JX-G03505D
12 V 3 A S8JX-G03512D
15 V 2.4 A S8JX-G03515D
24 V 1.5 A S8JX-G03524D
48 V 0.75 A S8JX-G03548D
50 W
5 V 10 A S8JX-G05005D
12 V 4.2 A S8JX-G05012D
24 V 2.1 A S8JX-G05024D
48 V 1.1 A S8JX-G05048D
100 W
5 V 20 A S8JX-G10005D
12 V 8.5 A S8JX-G10012D
24 V 4.5 A S8JX-G10024D
48 V 2.1 A S8JX-G10048D
150 W
5 V 30 A S8JX-G15005D
12 V 13 A S8JX-G15012D
24 V 6.5 A S8JX-G15024D
48 V 3.3 A S8JX-G15048D
DIN Rail-mounting *
DIN Rail-mounting *
S8JX
4
S8JX-G S8JX-P
Common Precautions
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan
Front-
mounting
bracket
Model
Covered Power
Supplies
100 to 240 VAC
(free)
(80 to 370 VDC *)
S8JX-G15005@@:
Switchable between 100
to 120 VAC and 200 to
240 VAC. (DC power
cannot be input.)
15 W
5 V 3 A
No Provided
S8JX-G01505C
12 V 1.3 A S8JX-G01512C
15 V 1 A S8JX-G01515C
24 V 0.65 A S8JX-G01524C
48 V 0.35 A S8JX-G01548C
35 W
5 V 7 A S8JX-G03505C
12 V 3 A S8JX-G03512C
15 V 2.4 A S8JX-G03515C
24 V 1.5 A S8JX-G03524C
48 V 0.75 A S8JX-G03548C
50 W
5 V 10 A S8JX-G05005C
12 V 4.2 A S8JX-G05012C
24 V 2.1 A S8JX-G05024C
48 V 1.1 A S8JX-G05048C
100 W
5 V 20 A S8JX-G10005C
12 V 8.5 A S8JX-G10012C
24 V 4.5 A S8JX-G10024C
48 V 2.1 A S8JX-G10048C
150 W
5 V 30 A S8JX-G15005C
12 V 13 A S8JX-G15012C
24 V 6.5 A S8JX-G15024C
48 V 3.3 A S8JX-G15048C
100 to 120 VAC
200 to 240 VAC
(Switchable)
300 W
5 V 60 A Yes
No
S8JX-G30005C
12 V 27 A S8JX-G30012C
24 V 14A No S8JX-G30024C
48 V 7A S8JX-G30048C
600 W
5 V 120A
Yes
S8JX-G60005C
12 V 53A S8JX-G60012C
24 V 27A S8JX-G60024C
48 V 13A S8JX-G60048C
Front-mounting *
S8JX
5
S8JX-G S8JX-P
Common Precautions
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan
Front-
mounting
bracket
Model
Open type Power
Supplies
100 to 240 VAC
(free)
(80 to 370 VDC *)
S8JX-G15005@@:
Switchable between 100
to 120 VAC and 200 to
240 VAC. (DC power
cannot be input.)
15 W
5 V 3 A
No Provided
S8JX-G01505
12 V 1.3 A S8JX-G01512
15 V 1 A S8JX-G01515
24 V 0.65 A S8JX-G01524
48 V 0.35 A S8JX-G01548
35 W
5 V 7 A S8JX-G03505
12 V 3 A S8JX-G03512
15 V 2.4 A S8JX-G03515
24 V 1.5 A S8JX-G03524
48 V 0.75 A S8JX-G03548
50 W
5 V 10 A S8JX-G05005
12 V 4.2 A S8JX-G05012
24 V 2.1 A S8JX-G05024
48 V 1.1 A S8JX-G05048
100 W
5 V 20 A S8JX-G10005
12 V 8.5 A S8JX-G10012
24 V 4.5 A S8JX-G10024
48 V 2.1 A S8JX-G10048
150 W
5 V 30 A S8JX-G15005
12 V 13 A S8JX-G15012
24 V 6.5 A S8JX-G15024
48 V 3.3 A S8JX-G15048
Front-mounting *
S8JX
6
S8JX-G S8JX-P
Common Precautions
Ratings, Characteristics, and Functions
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 20.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 20.
*7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON.
*8. The weight indicated is for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Input specification 100 to 240 V input
Item Power ratings *115 W 35 W
Efficiency 68% min. 73% min.
Input
Voltage *2100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9)
Frequency *250/60 Hz (47 to 450 Hz)
Current *3100 V input 0.4 A max. 1 A max.
200 V input 0.25 A max. 0.6 A max.
Harmonic current emissions ---
Leakage current *3100 V input 0.5 mA max.
200 V input 1 mA max.
Inrush current (for a
cold start at 25°C) *3
100 V input 20 A max.
200 V input 40 A max.
Output *4
Voltage adjustment range *510% to 15% (with V. ADJ) (48-V models: ±10%)
Ripple *32% (p-p) max.
Input variation influence 0.4% max. with AC input voltage
Load variation influence 0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max. (at rated input and output)
Startup time 500 ms max. (up to 90% of output voltage at rated input and output)
Hold time *320 ms min.
Additional
functions
Overload protection *6105% to 175% of rated load current, voltage drop, intermittent, automatic reset
Overvoltage protection *7Yes
Overheat protection No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator No
Other
Ambient operating temperature Refer to the derating curve in Engineering Data on page 17 (with no icing or
condensation).
Storage temperature 25 to 65°C (with no icing or condensation)
Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (Color: Green)
EMI Conducted Emissions Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9
Radiated Emissions Conforms to EN 55011 Group 1 Class A *9
EMS
Electrostatic Discharge Conforms to EN61000-4-2
Radiated Electromagnetic Field Conforms to EN61000-4-3
Electrical Fast Transient/Burst Conforms to EN61000-4-4
Surge Conforms to EN61000-4-5
Conducted Disturbance Conforms to EN61000-4-6
Voltage Dips/Short Interruptions Conforms to EN61000-4-11
Approved standards *9
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI SEMI F47-0200 (200-VAC input)
Weight *8250 g max.
S8JX
7
S8JX-G S8JX-P
Common Precautions
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 20.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 20.
*7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON.
*8. The weight indicated is for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Input specification 100 to 240 V input
Item Power ratings *150 W 100 W
Efficiency
5 V Models 76% min. 76% min.
12 V Models 81% min. 81% min.
24 V Models 83% min. 83% min.
48 V Models 82% min. 83% min.
Input
Voltage *2100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9)
Frequency *250/60 Hz (47 to 450 Hz)
Current *3100 V input 1.4 A max. 2.5 A max.
200 V input 0.8 A max. 1.5 A max.
Harmonic current emissions ---
Leakage current *3100 V input 0.5 mA max.
200 V input 1 mA max.
Inrush current (for a
cold start at 25°C) *3
100 V input 20 A max.
200 V input 40 A max.
Output *4
Voltage adjustment range *510% to 15% (with V. ADJ) (48-V models: ±10%)
Ripple *32% (p-p) max.
Input variation influence 0.4% max. (with AC input voltage)
Load variation influence 0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max. (at rated input and output)
Startup time 500 ms max. (up to 90% of output voltage at rated input and output)
Hold time *320 ms min.
Additional
functions
Overload protection *6105% to 175% of rated load current, voltage drop, intermittent, automatic reset
Overvoltage protection *7Yes
Overheat protection No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator No
Other
Ambient operating temperature Refer to the derating curve in Engineering Data on page 17 (with no icing or
condensation).
Storage temperature 25 to 65°C (with no icing or condensation)
Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (Color: Green)
EMI Conducted Emissions Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9
Radiated Emissions Conforms to EN 55011 Group 1 Class A *9
EMS
Electrostatic Discharge Conforms to EN61000-4-2
Radiated Electromagnetic Field Conforms to EN61000-4-3
Electrical Fast Transient/Burst Conforms to EN61000-4-4
Surge Conforms to EN61000-4-5
Conducted Disturbance Conforms to EN61000-4-6
Voltage Dips/Short Interruptions Conforms to EN61000-4-11
Approved standards *9
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI SEMI F47-0200 (200-VAC input)
Weight *8300 g max. 550 g max.
S8JX
8
S8JX-G S8JX-P
Common Precautions
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 20.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 20.
*7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON.
*8. The weight indicated is for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Input specification 100/200 V switchable 100 to 240 V input
Item Power ratings *1150 W at 5 V 150 W at 12 V 150 W at 24 or 48 V
Efficiency
5 V Models 78% min. --- ---
12 V Models --- 79% min. ---
24 V Models --- --- 86% min.
48 V Models --- --- 85% min.
Input
Voltage *2
Switchable between 100 to
120 VAC (allowable range:
85 to 132 VAC) and 200 to
240 VAC (allowable range:
170 to 264 VAC).
100 to 240 VAC
(allowable range: 85 to 264 VAC, 80 to 370 VDC *9)
Frequency *250/60 Hz (47 to 450 Hz)
Current *3100 V input 3.5 A max. 3.6 A max. 3.5 A max.
200 V input 2.1 A max. 2.2 A max. 2.1 A max.
Harmonic current emissions ---
Leakage current *3100 V input 0.5 mA max.
200 V input 1 mA max.
Inrush current (for a
cold start at 25°C) *3
100 V input 20 A max.
200 V input 40 A max.
Output *4
Voltage adjustment range *510% to 15% (with V. ADJ) (48-V models: ±10%)
Ripple *32% (p-p) max.
Input variation influence 0.4% max. (with AC input voltage)
Load variation influence 0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max. (at rated input and output)
Startup time 500 ms max. (up to 90% of output voltage at rated input and output)
Hold time *320 ms min.
Additional
functions
Overload protection *6
105% to 175% of rated load
current, voltage drop,
automatic reset
105% to 175% of rated load current, voltage drop,
intermittent, automatic reset
Overvoltage protection *7Yes
Overheat protection No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator No
Other
Ambient operating temperature Refer to the derating curve in Engineering Data on page 17 (with no icing or
condensation).
Storage temperature 25 to 65°C (with no icing or condensation)
Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (Color: Green)
EMI Conducted Emissions Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9
Radiated Emissions Conforms to EN 55011 Group 1 Class A *9
EMS
Electrostatic Discharge Conforms to EN61000-4-2
Radiated Electromagnetic Field Conforms to EN61000-4-3
Electrical Fast Transient/Burst Conforms to EN61000-4-4
Surge Conforms to EN61000-4-5
Conducted Disturbance Conforms to EN61000-4-6
Voltage Dips/Short Interruptions Conforms to EN61000-4-11
Approved standards *9
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI --- SEMI F47-0200 (200-VAC input)
Weight *8800 g max. 700 g max. 600 g max.
S8JX
9
S8JX-G S8JX-P
Common Precautions
Input specification 100/200 V (Selected)
Item Power ratings *1300 W 600 W
Efficiency
5 V models 71% min. 72% min.
12 V models 75% min. 78% min.
24 V models 82% min. 80% min.
48 V models 82% min. 80% min.
Input
Voltage *2
100 to 120 VAC (allowable range: 85 to 132 VAC)
200 to 240 VAC (allowable range: 170 to 264 VAC)
(Switchable)
Frequency *250/60 Hz (47 to 450 Hz)
Current *3
100 V input 8A max. 16 A max.(5V, 12V, 48V)
14 A max.(24V)
200 V input 4.5 A max. 9 A max.(5V, 12V, 48V)
8 A max.(24V)
Harmonic current emissions ---
Leakage current *3100 V input 0.5 mA max.
200 V input 1 mA max.
Inrush current (for a
cold start at 25°C) *3
100 V input 25 A max. 30 A max.
200 V input 50 A max. 60 A max.
Output *4
Voltage adjustment range *510% to 15% (with V. ADJ) (48-V models: ±10%)
Ripple *32.8% (p-p) max.(5V) *6
2% (p-p) max.(12V, 24V, 48V)
3.8% (p-p) max.(5V) *6
2% (p-p) max.(12V) *6
2% (p-p) max.(24V, 48V)
Input variation influence 0.4% max.
Load variation influence 0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max.
Startup time 650 ms max. 500 ms max.
Hold time *320 ms min.
Additional
functions
Overload protection *7
105% to 175%
of rated load current, Inverted L voltage drop,
the circuit will be shut OFF when the
overload exceeds 5 s.
(5V, 12V)
*
10
voltage drop, intermittent, automatic reset.
(24V, 48V)
105% to 175% of rated load current, Inverted
L voltage drop, the circuit will be shut OFF
when the overload exceeds 5 s.
*
10
Overvoltage protection *8Yes (5V, 12V)
*
10
Yes (24V, 48V)
*
10
Yes *10
Overheat protection Yes (5V, 12V)
*
10
N0 (24V, 48V)
*
10
Yes *10
Parallel operation Yes (up to 5 units)
Series operation Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator Yes (color: red) (5V, 12V)
No (24V, 48V)
Yes (color: red)
Other
Ambient operating temperature
Refer to the derating curve in Engineering Data on page 17 (with no icing or condensation).
Storage temperature 25 to 65°C (with no icing or condensation)
Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA)
Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (Color: Green)
EMI Conducted Emissions *3Conforms to EN 55011 Group 1 Class A and based on FCC Class A
*
11
Radiated Emissions Conforms to EN 55011 Group 1 Class A
*
11
*
12
EMS
Electrostatic Discharge Conforms to EN61000-4-2
Radiated Electromagnetic Field Conforms to EN61000-4-3
Electrical Fast Transient/Burst Conforms to EN61000-4-4
Surge Conforms to EN61000-4-5
Conducted Disturbance Conforms to EN61000-4-6
Voltage Dips/Short Interruptions Conforms to EN61000-4-11
Approved standards *13
UL UR: UL 508 (Recognition), UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
Weight *91,800 g max. (5V, 12V)
1,600 g max. (24V, 48V) 2,500 g max.
S8JX
10
S8JX-G S8JX-P
Common Precautions
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 20.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. Measurement methods are based on JEITA standard RC-9131A. Refer to Ripple Noise Voltage on page 57.
*7. For details, refer to Overload Protection on page 20.
*8. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*9. The weight indicated is for Front-mounting Power Supply.
*10.The protection-ON alarm indicator will light as soon as the output is interrupted. For resetting, turn OFF the input power, leave for more than
three minutes , and then turn it back ON again.
*11.Noise values depend on the wiring methods and other factors. Insert noise filters and cores in the input and output lines.
300 W, 5 V: Two E04SR401938 (manufactured by SEIWA) on the output line.
300 W, 12 V: One E04SR401938 (manufactured by SEIWA) on the output line.
600 W, 5 V or 12 V: One FN2450G-16-61 (manufactured by Schaffner) on the input line.
One E04RC613620 (manufactured by SEIWA) on the output line.
*12.For the 600-W, 5-V and 12-V models, class A compliance was met with an aluminum plate placed under the Power Supply.
*13.The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
S8JX
11
S8JX-G S8JX-P
Common Precautions
Connections
Block Diagrams
Voltage
detection
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Noise
filter
Inrush current
protection
Fuse
2.0 A
AC (L)
INPUT
AC (N)
Rectifier Smoothing
circuit
Rectifier/
Smoothing circuit
Overvoltage
detection circuit
Voltage
detection circuit
Photocoupler
Overvoltage
detection circuit
Drive control
circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Rectifier/
smoothing circuit
Noise
filter
Inrush current
protection
Fuse:
2.0 A
AC (L)
INPUT
AC (N)
Rectifier Smoothing
circuit
Voltage
detection
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Noise
filter
Inrush current
protection
Fuse
3.15 A
AC (L)
INPUT
AC (N)
Rectifier Smoothing
circuit
Rectifier/
Smoothing circuit
Overvoltage
detection circuit
Voltage
detection circuit
Photocoupler
Overvoltage
detection circuit
Drive control
circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Rectifier/
smoothing circuit
Noise
filter
Inrush current
protection
Fuse:
3.15 A
AC (L)
INPUT
AC (N)
Rectifier Smoothing
circuit
S8JX
12
S8JX-G S8JX-P
Common Precautions
Voltage
detection
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Noise
filter
Inrush current
protection
Fuse
6.3 A
AC (L)
INPUT
AC (N)
Rectifier Smoothing
circuit
Rectifier/
Smoothing circuit
Overvoltage
detection circuit
Voltage
detection circuit
Photocoupler
Overvoltage
detection circuit
Drive control
circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Rectifier/
smoothing circuit
Noise
filter
Inrush current
protection
Fuse:
6.3 A
AC (L)
INPUT
AC (N)
Rectifier Smoothing
circuit
S8JX-G05048@@ (50 W)
DC OUTPUT
INPUT
Voltage
detection
+V
V
Noise
filter
Inrush current
protection
Fuse
8 A
AC (L)
AC (N)
Rectifier
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
Smoothing
circuit
Rectifier/
Smoothing circuit
Overvoltage
detection circuit
S8JX-G100@@@@ (100 W)
S8JX
13
S8JX-G S8JX-P
Common Precautions
Voltage
detection circuit
Photocoupler
Input voltage switch
100/200 V switching
Overvoltage
detection circuit
Noise
filter
Fuse:
8 A
AC (L)
INPUT
AC (N)
Drive control
circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Inrush current protection Rectifier/
smoothing circuit
Rectifier/
smoothing circuit
S8JX-G15005@@ (150 W)
Note: Set the input voltage switch to "115V" for 100 to 120 VAC and to "230V" for 200 to 240 VAC.
INPUT DC OUTPUT
Voltage
detection
+V
V
Noise
filter
Inrush current
protection
Fuse
10 A
AC (L)
AC (N)
Rectifier
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
Smoothing
circuit
Overvoltage
detection circuit
Rectifier/
Smoothing circuit
S8JX-G15012@@ (150 W)
S8JX-G15024@@ (150 W)
S8JX-G15048@@ (150 W)
INPUT DC OUTPUT
Voltage
detection
+V
V
Noise
filter
Inrush current protection
Fuse
10 A
AC (L)
AC (N)
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
Overvoltage
detection circuit
Rectifier/Smoothing circuit
Rectifier/
Smoothing circuit
Parallel operation selector
100/200V (Selectable)
Rectifier/Smoothing circuit
Fan
Overheat
detection circuit
Overheat
detection
circuit
S8JX-G30005@@ (300 W)
S8JX-G30012@@ (300 W)
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC.
Keep the terminals open if the input is 200 to 240 VAC.
S8JX
14
S8JX-G S8JX-P
Common Precautions
INPUT DC OUTPUT
Voltage
detection
+V
V
Noise
filter
Inrush current protection
Fuse
10 A
AC (L)
AC (N)
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
Overvoltage
detection circuit
Rectifier/
Smoothing circuit
Rectifier/
Smoothing circuit
Parallel operation selector
100/200V (Selectable)
S8JX-G30024@@ (300 W)
S8JX-G30048@@ (300 W)
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC.
Keep the terminals open if the input is 200 to 240 VAC.
AC(L)
INPUT
AC(N)
DC OUTPUT
Fan
Voltage
detection
Overheat
detection circuit
+V
V
Noise
filter
Inrush current protection
Fuse
20 A
Photocoupler
Control
Circuit
Overcurrent
detection
circuit
Overheat
detection
circuit
Overvoltage
detection circuit
Rectifier/
Smoothing circuit
Rectifier/
Smoothing circuit
Parallel operation selector
100/200V (Selectable)
Rectifier/Smoothing circuit
S8JX-G60005@ (600 W)
S8JX-G60012@ (600 W)
S8JX-G60048@ (600 W)
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC.
Keep the terminals open if the input is 200 to 240 VAC.
Fan
INPUT DC OUTPUT
Voltage
detection
+V
V
Noise
filter
Inrush current protection
Fuse
20 A
AC (L)
AC (N)
Photocoupler
Drive control
Circuit
Overcurrent
detection
circuit
Overheat
detection
circuit
Overvoltage
detection circuit
Rectifier/
Smoothing circuit
Rectifier/
Smoothing circuit
Parallel operation selector
100/200V (Selectable)
S8JX-G60024@ (600 W)
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC.
Keep the terminals open if the input is 200 to 240 VAC.
S8JX
15
S8JX-G S8JX-P
Common Precautions
Construction and Nomenclature
Nomenclature
15-/35-/50-/100-/150-W Models
E
D
A
C
B
+V
V
AC (L)
AC (N)
100 to 120 VAC 200 to 240 VAC
E
F
D
A
C
B
+V
V
AC (L)
Bottom
AC (N)
*1. The fuse is located on the (L) side. It is NOT user-replaceable. For a DC
power input, connect the low side to the positive (+) terminal.
*2. This is the protective earth terminal specified in the safety standards.
Always ground this terminal.
*3. This item is applicable only to the S8JX-G15005@@.
No. Name Function
1DC Output
Terminals (V), (+V) Connect the load lines to these terminals.
2AC Input Terminals
(L), (N) Connect the input lines to these terminals. *1
3Protective Earth
Terminal (PE) ( ) Connect the ground line to these terminals. *2
4Output Voltage
Adjuster (V. ADJ)
It is possible to increase or decrease the output
voltage.
5Output Indicator
(DC ON: Green) Lights green while a direct current (DC) output is ON.
6Input voltage switch
*3
Switches the internal circuits according to the input
voltage.
"115V": 100 to 120 VAC
"230V": 200 to 240 VAC
Note: The S8JX-G05024CD is
shown above.
Note: The S8JX-G15005C is shown
above.
+V
+V
V
V
AC(L)
AC(N)
Bottom
Note: The S8JX-G30005C is shown above.
*1. The fuse is located on the (L) side. It is NOT user-replaceable.
*2. This is the protective earth terminal specified in the safety standards.
Always ground this terminal.
*3. This is not applicable to 24-V and 48-V models.
No. Name Function
1DC Output
Terminals (+V), (V) Connect the load lines to these terminals.
2AC Input Terminals
(L), (N) Connect the input lines to these terminals. *1
3Protective Earth
Terminal (PE) ( ) Connect the ground line to these terminals. *2
4Input Voltage
Selector Terminals
Short-circuit the terminals if the input is 100 to 120
VAC and open the terminals if the input is 200 to 240
VAC.
5Output Indicator
(DC ON: Green) Lights green while a direct current (DC) output is ON.
6Output Voltage
Adjuster (V. ADJ)
It is possible to increase or decrease the output
voltage.
7
Protection-ON
Alarm Indicator
(ALM: Red)
The red indicator will be lit if the overvoltage or
overheat protection circuit is triggered. This indicator
will also be lit when overload is detected. *3
8Selector of Parallel
Operation
Set the selector to PARALLEL if the Units are in
parallel operation.
300-W 24V, 48V Model
AC (L)
AC (N)
Bottom
+V
+V
V
V
E
F
D
C
H
AB
Note: The S8JX-G30024C is shown above.
300-W 5V, 12V Model 300-W Model
S8JX
16
S8JX-G S8JX-P
Common Precautions
Reference Values
Reliability (MTBF)
S8JX-G15012@@ and
S8JX-G15005@@
S8JX-G30005@@ and
S8JX-G300012@@ S8JX-G6000@@@ Other models
240,000 hrs 200,000 hrs 170,000 hrs 250,000 hrs
Definition
MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device
failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
Life expectancy 10 yrs. min.
Definition The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load rate of 50%.
Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.
Side
AC (L)
AC (N)
+V+V
VV
Note: The S8JX-G60005C
is shown above.
600-W 24V, 48V Model
AC (L)
AC (N)
Side
+V+V
VV
GEF
D
A
C
H
B
Note: The S8JX-G60024C
is shown above.
*1. The fuse is located on the (L) side. It is NOT user-replaceable.
*2. This is the protective earth terminal specified in the safety standards.
Always ground this terminal.
No. Name Function
1DC Output
Terminals (+V), (V) Connect the load lines to these terminals.
2AC Input Terminals
(L), (N) Connect the input lines to these terminals. *1
3Protective Earth
Terminal (PE) ( ) Connect the ground line to these terminals. *2
4Input Voltage
Selector Terminals
Short-circuit the terminals if the input is 100 to 120
VAC and open the terminals if the input is 200 to 240
VAC.
5Output Indicator
(DC ON: Green) Lights green while a direct current (DC) output is ON.
6Output Voltage
Adjuster (V. ADJ)
It is possible to increase or decrease the output
voltage.
7
Protection-ON
Alarm Indicator
(ALM: Red)
The red indicator will be lit if the overvoltage or
overheat protection circuit is triggered. This indicator
will also be lit when overload is detected.
8Selector of Parallel
Operation
Set the selector to PARALLEL if the Units are in
parallel operation.
600-W 5V, 12V Model 600-W Model
S8JX
17
S8JX-G S8JX-P
Common Precautions
Engineering Data
Derating Curves (Standard Mounting)
Open type Power Supplies Covered Power Supplies
Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the
area shown by shading in the above graph).
2. If there is a derating problem, use forced air-cooling.
3. For Customers Using a DC Input
When using an input voltage of less than 100 VDC, reduce the load calculated with the above derating curve by at least the following
coefficients.
35-W and 100-W (5-V or 12-V output) models: 0.8
50-W/150-W models: 0.85 (DC power cannot be input only to the S8JX-G15005@@.)
15-W and 100-W (24-V or 48-V output): 0.9
Single Unit Operation Parallel Operation
Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the
area shown by shading in the above graph).
2. If there is a derating problem, use forced air-cooling.
Single Unit Operation Parallel Operation
Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the
area shown by shading in the above graph).
15-/35-/50-/100-/150-W Models
300-/600-W 24V, 48V Models
600-W 5V, 12V Models
20 10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Load rate (%)
20 10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Load rate (%)
Ambient Temperature (°C) Ambient Temperature (°C)
AA
1
Solid line
Dotted line
Front-mounting,
Bottom-mounting,
DIN Rail mounting,
Side mounting
(300W 5V, 12V/
600W 24V, 48V Models)
Side mounting
(300W 24V, 48V Models)
20 10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Load rate (%)
20 10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Load rate (%)
Ambient Temperature (°C) Ambient Temperature (°C)
1
20 10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
20 10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Load rate (%)
Load rate (%)
Ambient Temperature (°C) Ambient Temperature (°C)
1
S8JX
18
S8JX-G S8JX-P
Common Precautions
Mounting
The following three mounting methods are possible.
.
Front-mounting: Refer to Mounting Bracket Provided with Front-mounting Power Supplies on page 26.
. Bottom-mounting
. Side-mounting
Note: Additional mounting methods are also available using DIN Rail-mounting models.
Standard Mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the
standard mounting method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended.
3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply is designed to radiate heat by
means of natural air flow.
ë
15-/35-/50-/100-/150-W Models
15-/35-/50-/100-/150-W Models
300-W 5V, 12V Model
300-W 24V, 48V Model
B
C
Front-mounting
*
DIN Rail-mounting Bottom-mounting
*
Vertical Side-mounting
*
Horizontal Side-mounting
*
Front-mounting Bottom-mounting
20mm min.20mm min. 20mm min.20mm min.
Side-mounting
DIN Rail mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or
damage of internal parts. Use the standard mounting method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended.
3. Do not cover the air holes (provided at fan mounted side and the opposite side) to have enough air-
cooling.
Front-mounting
20mm min. 20mm min. 20mm min.20mm min.
Bottom-mounting Side-mounting
DIN Rail mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or
damage of internal parts. Use the standard mounting method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended.
3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply
is designed to radiate heat by means of natural air flow.
S8JX
19
S8JX-G S8JX-P
Common Precautions
600-W Model
Front-mounting
20mm min.20mm min. 20mm min.
20mm min.
Bottom-mounting
Side-mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally
result in deterioration or damage of internal parts. Use the standard mounting
method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is
recommended.
3. Do not cover the air holes (provided at fan mounted side and the opposite
side) to have enough air-cooling.
S8JX
20
S8JX-G S8JX-P
Common Precautions
Overload Protection
The Power Supply is provided with an overload protection function that protects the power supply from possible damage by overcurrent. When the
output current rises above 105% to 175% min. of the rated current, the protection function is triggered, decreasing the output voltage. When the
output current falls within the rated range, the overload protection function is automatically cleared.
Note: 1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the power supply may
not start.
2. Internal parts may occasionally deteriorate or be damaged if a short-circuited or overcurrent state continues during operation.
3. Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with frequent inrush current or
overloading at the load end. Do not use the Power Supply for such applications.
(Reference value)
If an excessive current flows for 5 s or more, the output will be turned
OFF and simultaneously the protection-ON alarm indicator will be lit.
To reset the S8JX, turn OFF the power, leave the S8JX for at least
three minutes, and then turn it ON again.
15-/35-/50-/100-/150-W (12-/24-/48-V) Models
150-W, 5-V Models
300-W 24V, 48V Model
50
Intermittent operation
0
Load rate (%)
100
Output voltage (V)
0 Load rate (%)
100 50
Output voltage (V)
500
Load rate (%)
100
Output voltage (V)
Intermittent operation
300-W 5V, 12V/600-W Model
50
Output interrupted
0
Load rate (%)
100
Output voltage (V)
S8JX
21
S8JX-G S8JX-P
Common Precautions
Overvoltage Protection
Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback
circuit in the power supply fails. When an excessive voltage that is approximately 130% of the rated voltage or more is output, the output voltage
is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least seven minutes and then turning
it back ON again.
Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback
circuit in the Power Supply fails. When an excessive voltage that is approximately 120% of the rated voltage or more is output, the output voltage
is shut OFF, preventing damage to the load due to overvoltage (Except 300-W 24V, 48V models ). Reset the input power by turning it OFF for at
least three minute and then turning it back ON again.
(Reference value)
Note: Do not turn ON the power again until the cause of the overvoltage has been removed.
Overheat Protection
If the internal temperature rises excessively as a result of fan failure or any other reason, the overheat protection circuit will be triggered to shut
OFF the output voltage and simultaneously the protection-ON alarm indicator will be lit. Reset the input power by turning it OFF for at least three
minutes and then turning it back ON again.
Inrush Current, Startup Time, Output Hold Time
Note: A maximum startup time of 500 ms is required (650 ms for 300 W). Construct a system configuration that considers the startup time of other
devices.
15-/35-/50-/100-/150-W Models
300-/600-W Models
300-W 5V, 12V/600-W Model
Output voltage (V)
Overvoltage protection
Operating
Variable range
Rated output
Voltage
0 V
Startup time Hold time (20 ms min.)
AC input
voltage
AC input
current
Output
voltage
Inrush current on input application
90%96.5%
Input ONInput OFF
S8JX
22
S8JX-G S8JX-P
Common Precautions
Dimensions (Unit: mm)
Front-mounting Models
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
Two, M3
75
±0.5
82
±0.5
Two, M3
78
±0.5
10 max. 90
4.5
3.5
(for mounting)
3.5
(for mounting)
3.5 dia.
(for mounting)
3.5 dia.
(for mounting)
91±1
7.5
8.2
9.5
35.5
Five, M3.5
Cover
Label
Two, M3 (Depth: 4 mm max.)
39.5±1
75±0.5
82±0.5
26.5
17.5
15 50±0.5
8.5 78±0.5
26.5
S8JX-G015@@ (15 W)
S8JX-G015@@C (15 W)
S8JX-G035@@ (35 W)
S8JX-G035@@C (35 W)
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
Two, M3
75±0.5
92±0.5
Two, M3
92±0.5
40±1
36
8.2
9.5
Five, M3.5
Label
Cover
10 max. 100
4.5
3.5 dia.
(for mounting)
92±1
8
75±0.5
92±0.5
3.5
(for mounting)
3.5 dia.
(for mounting)
Two, M3 (Depth: 4 mm max.)
26.5
20
20 65±0.5
4.5 92±0.5
3.5
(for mounting)
S8JX-G050@@ (50 W)
S8JX-G050@@C (50 W)
100·150W
Two, M3
(Depth: 4 mm max.)
100W150W
50±1
48
8.2
9.5
Five, M3.5
Label
Cover
10 max. 150
92±1
8
75±0.5
5
5
3.5 dia.
(for mounting)
141±0.5
3.5
(for mounting)
28
3.5 dia.
(for mounting)
16 122±0.5
141±0.5
3.5
(for mounting)
S8JX-G100@@ (100 W)
S8JX-G100@@C (100 W)
S8JX-G15024 (150 W)
S8JX-G15024C (150 W)
S8JX-G15048 (150 W)
S8JX-G15048C (150 W)
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
Two, M3
75
±0.5
141
±0.5
Two, M3
141
±0.5
S8JX
23
S8JX-G S8JX-P
Common Precautions
5
5
230V
Input voltage switch
60±1
10
13
8.2
9.5
Three, M3.5
Label
Two, M4
Cover
12 max. 178
92±1
8
68±0.5
169±0.5
Two, M3
(Depth:
4 mm max.) 3.5
(for mounting)
36
33.5
3.5 dia.
(for mounting)
3.5 dia.
(for mounting)
14 140±0.5
169±0.5
3.5
(for mounting)
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
169
±0.5
68
±0.5
Two, M3
169±0.5
Two, M3
S8JX-G15005 (150 W)
S8JX-G15005C (150 W)
5
Label
8.2
9.5
Five, M3.5
Cover
10 max. 178
92±1
8
68±0.5
5
3.5 dia.
(for mounting)
169±0.5
169±0.5
140±0.5
3.5
(for mounting)
36
33.5
60±1
Two, M3
(Depth:
4 mm max.)
3.5 dia.
(for mounting)
14
3.5
(for mounting)
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
169
±0.5
68
±0.5
Two, M3
169±0.5
Two, M3
S8JX-G15012 (150 W)
S8JX-G15012C (150 W)
S8JX
24
S8JX-G S8JX-P
Common Precautions
17
Four, M4 holes (Depth: 8 max.)
Eight, M4 holes (Depth: 8 max. on both sides)
Five, M4 terminal screwsFour, M5 terminal screws
110±1
92±1
26
10
8.6
16
13
164.5
22.5 max.
136±0.5
17 136±0.5
21
50±0.5
10
90±0.5
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
50±0.5
136±0.5
Four, 4.5 dia.
90±0.5
136±0.5
Four, 4.5 dia.
S8JX-G30005C (300 W)
S8JX-G30012C (300 W)
Nine, M4 terminal screws
Four, M4 holes
(Depth: 8 max.)
Eight, M4 holes
(Depth: 8 max. on both sides)
19
110±1
92±1
10
8.6
167.1
20 max.
136±0.5
19 136±0.5
21
50±0.5
10
90±0.5
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
50±0.5
136±0.5
Four, 4.5 dia.
90±0.5
136±0.5
Four, 4.5 dia.
S8JX-G30024C (300 W)
S8JX-G30048C (300 W)
S8JX
25
S8JX-G S8JX-P
Common Precautions
124±05
16
26
13
26 max. 159.8
2.5
Five, M4 terminal screws
11
137±0.5 14.8
92±1
14.8
16.9
150±1 Eight, M4 holes
(Depth: 8 max. on both sides)
Four, M4 holes (Depth: 8 max.)
42
100±0.5
20.9
50±0.5
Four, M5 terminal screws
10 8.6
S8JX-G60005@ (600 W)
S8JX-G60012@ (600 W)
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
50±0.5
124±0.5
Four, 4.5 dia.
100±0.5
137±0.5
Four, 4.5 dia.
OPERATION
PARALLEL SINGLE
Short bar
Nine, M4 terminal screws
70
16
92±1
38.6 (38.84)
10
150±1
(14.2)
(14.2)
108.6 (23.8)124±0.5
26 max. 159.8
11
137±0.5 14.8
Eight, M4 holes
(Depth: 8 max. on both sides)
Four, M4 holes (Depth: 8 max.)
42
100±0.5
50±0.5
70
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
50±0.5
124±0.5
Four, 4.5 dia.
100±0.5
137±0.5
Four, 4.5 dia.
S8JX-G60024C (600 W)
S8JX-G60048C (600 W)
S8JX
26
S8JX-G S8JX-P
Common Precautions
Mounting Bracket Provided with Front-mounting Power Supplies a
15-/35-/50-/100-/150-W Models
S82Y-J00F Front-mounting
Bracket Front-mounting Method
Temporarily attach the enclosed mounting
bracket as shown in the illustration on the right,
hook the holes (parts a) in the Power Supply on
hooks on the mounting bracket (parts b), and
secure the Power Supply with two mounting
screws.
300-/600-W Models
Front-mounting Bracket (S82Y-J30F) Dimensions with
Mounting Brackets
Attaching the Mounting Brackets
Dimensions Mounting
dimensions
11
9
1.5
60
11
20
5
31.5
20.5
15
4.7
4.6
4.6 15±0.2
74
Two, 3.5 dia.
t = 1.0
Material: Stainless steel
Two, M3
20
60
b
b
a
a
Power Supply Mounting bracket
Note: Mounting screws are
not provided.
48
15 30
7.5 7.5
160
32±0.2
92
145±0.3
R2.5
10 dia.
Two, 5 dia. t = 1.6
Note: Mounting Brackets are provided in a set, one
for the right side and one for the left side.
145±0.3
80±0.5 Four, M4
300-W Model
300-W Model
Note: To provide ventilation space, the body
will shift forward by 21.6 mm from the
mounting surface.
145±0.3
120±0.5 Four, M4
600-W Model
600-W Model
Note: To provide ventilation space, the body
will shift forward by 23.6 mm from the
mounting surface.
S8JX
27
S8JX-G S8JX-P
Common Precautions
Separately purchasable mounting brackets (Please ask your dealer for details of delivery.)
Bracket for changeover from S82J-series
The mounting-hole pitch of mounting brackets A - I below is identical to that of our product S82J. These brackets can be used for
switchover with the S82J-series.
Note: Mounting brackets (A, B, C, D, E, F, G, H, I) are compatible with S82J mounting holes.
For 30-W/50-W/100-W/150-W/300-W/600-W models (separately purchasable)
Models compatible with the
S82J-series
Mounting
Orientation Products names Model
50-W models
Underside mounting
Mounting bracket A (For S8JX-G-series 50-W models) S82Y-JX05B
100-W 24 V models Mounting bracket B (For S8JX-G-series 100-W 24 V models) S82Y-JX10B
100-W 5 V, 12 V, 150-W 24 V models
Mounting bracket C (For S8JX-G-series 100-W 5 V, 12V, 150 W models)
S82Y-JX15B
100-W 5 V, 12 V, 150-W 24 V models Front mounting
Mounting bracket D (For S8JX-G-series 100-W 5 V, 12 V, 150 W models)
S82Y-JX15F
25-W models Underside mounting Mounting bracket E (For S8JX-G-series 30-W models) S82Y-JX03B
300-W models Underside mounting Mounting bracket F (For S8JX-G-series 300-W models) S82Y-JX30B
Front mounting Mounting bracket G (For S8JX-G-series 300-W models) S82Y-JX30F
600-W models Underside mounting Mounting bracket H (For S8JX-G-series 600-W models) S82Y-JX60B
Front mounting Mounting bracket I (For S8JX-G-series 600-W models) S82Y-JX60F
28
40
3.5
R2
R1.75 R0.5
161
150.5±0.5
6.5
Thickness = 2
3.5 dia.
A
B
B
A
Mounting Bracket A
S82Y-JX05B
Screws used
A: Accessories (2 locations)
Be sure to use the accessory screws.
Mounting screw tightening torque
(recommended): 0.49 N · m
B: M3 (2 locations)
Method of Mounting
28
50
4.5
R2
R2.25 R0.5
170
6.5
4.5 dia.
160±0.5
Thickness = 2
B
A
B
A
Mounting Bracket B
S82Y-JX10B
Screws used
A: Accessories (2 locations)
Be sure to use the accessory screws.
Mounting screw tightening torque
(recommended): 0.49 N · m
B: M4 (2 locations)
Method of Mounting
S8JX
28
S8JX-G S8JX-P
Common Precautions
35
50
4.5
R2
R2.25
R0.5
188
178±0.5 3
4.5 dia.
Thickness = 2
B
A
A
B
Mounting Bracket C
S82Y-JX15B
Screws used
A: Accessories (2 locations)
Be sure to use the accessory screws.
Mounting screw tightening torque
(recommended): 0.49 N · m
B: M4 (2 locations)
Method of Mounting
119
110±0.5
4.5 25
45
45.6
54
5 dia.
Thickness = 1.6
B
B
A
A
Mounting Bracket D
S82Y-JX15F
Screws used
A: Accessories (2 locations)
Be sure to use the accessory screws
Mounting screw tightening torque
(recommended): 0.49 N · m
B: M4 (2 locations)
Method of Mounting
112±0.5
3.5 dia.
Thickness = 2
28
40
3.5
R0.5
R2
R1.75
124
6.5
B
B
A
A
Mounting Bracket E
S82Y-JX03B
Screws used
A: Accessories (2 locations)
Be sure to use the accessory screws.
Mounting screw tightening torque
(recommended): 0.49 N · m
B: M3 (2 locations)
Method of Mounting
S8JX
29
S8JX-G S8JX-P
Common Precautions
7
Front
Thickness = 3.2
Four, M4
150±0.1
167
100±0.1
110
A
A
A
BB
B
Mounting Bracket F
S82Y-JX30B
Screws used
A: Accessories (4 locations)
Be sure to use the accessory screws.
B: M4 (4 locations)
Screws of a length that will not project
beyond the fixture (thickness: 3.2 mm)
should be selected.
Method of Mounting
7.5 7.5
145±0.3
160
32±0.2
92
Two, 5 dia.
11.6
R2.5
10 dia.
29.6
48
Thickness = 1.6
145±0.3
90±0.5 Four, M4
A
A
A
A
Mounting Bracket G
S82Y-JX30F
Screws used
A: Accessories (4 locations)
Be sure to use the accessory screws.
Note: For ventilation of the back surface,
the body should be placed 21.6 mm
in front of the mounting side.
Method of Mounting
Front
Thickness = 3.2
169
150±0.1 9
45
100±0.1 170
Eight, M4
A
A
A
B
B
B
Mounting Bracket H
S82Y-JX60B
Screws used
A: Accessories (4 locations)
Be sure to use the accessory screws.
B: M4 (4 locations)
Screws of a length that will not project beyond the
fixture (thickness: 3.2 mm) should be selected.
(Although there are 8 holes in the bracket body,
only 4 of these are used.)
Method of Mounting
145±0.3
140±0.5 Four, M4
Two, 5 dia.
6.6
10 dia. R2.5
21.6
32±0.2
92
145±0.3
160
7.5
48
Thickness = 3.2
7.5
A
A
A
A
Mounting Bracket I
S82Y-JX60F
Screws used
A: Accessories (4 locations)
Be sure to use the accessory screws.
Note: For ventilation of the back surface, the
body should be placed 23.6 mm in front of
the mounting side.
Method of Mounting
S8JX
30
S8JX-G S8JX-P
Common Precautions
DIN Rail-mounting Models
S8JX-G015@@D (15 W)
S8JX-G015@@CD (15 W)
S8JX-G035@@D (35 W)
S8JX-G035@@CD (35 W)
14.510 max.
8.2
9.5
35.5
Five, M3.5
Cover
Label
39.5
44±1 90
98.6
91±1
47
7 (Sliding: 16.6 max.)
S8JX-G050@@D (50 W)
S8JX-G050@@CD (50 W)
8.2
9.5
36
Five, M3.5
Cover
Label
40
44±1 14.510 max. 100
108.6
92±1
47
7 (Sliding: 16.6 max.)
S8JX-G100@@D (100 W)
S8JX-G100@@CD (100 W)
S8JX-G15024D (150 W)
S8JX-G15024CD (150 W)
S8JX-G15048D (150 W)
S8JX-G15048CD (150 W)
100W150W100·150W
8.2
9.5
48
Five, M3.5
Cover
Label
50
±1
14.510 max. 150
158.6
92
±1
47
7 (Sliding: 16.6 max.)
S8JX
31
S8JX-G S8JX-P
Common Precautions
230V
Input voltage switch
10
13
8.2
9.5
Three, M3.5
Cover
Label
Two, M4 60±1 14.512 max. 178
186.6
7 (Sliding: 16.6 max.)
92±1
47
S8JX-G15005D (150 W)
S8JX-G15005CD (150 W)
8.2
9.5
Five, M3.5
Cover
Label
186.6
60±1
7 (Sliding: 16.6 max.)
92±1
47
14.510 max. 178
S8JX-G15012D (150 W)
S8JX-G15012CD (150 W)
S8JX
32
S8JX-G S8JX-P
Common Precautions
4.4
(Sliding: 10 max.)
Five, M4 terminal screws
8.6 10
92±1
26
16
13
110±1 179.3
22.5 max. 175.3
46.6
7.5
S8JX-G30005CD (300W)
S8JX-G30012CD (300W)
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
Nine, M4 terminal screws
4.4 (Sliding: 10 max.)
92±1
110±1
110±
1
8.6 10
181.3
20 max. 177.3
46.6
7.5
S8JX-G30024CD (300 W)
S8JX-G30048CD (300 W)
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
S8JX
33
S8JX-G S8JX-P
Common Precautions
DIN Rail (Order Separately)
Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit.
Terminal Cover (Order Separately)
Replacement Fan (sold separately)
Terminal Cover model Applicable Power Supply and applicable location
S82Y-JX-C4P S8JX-G-300W, 24-V or 48-V output
S8JX-G-600W, 24-V or 48-V output
S82Y-JX-C5P S8JX-G-300W, input
S8JX-G-600W, input
S82Y-JTC1
S8JX-G-15W
S8JX-G-30W
S8JX-G-50W
S8JX-G-100W
S8JX-G-150W, 12-V, 24-V or 48-V model
Model
S82Y-JXFAN
Mounting Rail
(Material: Aluminum)
4.5
15 25 25
10 10
1,000 (500)
25 25 15 (5) *
35
±0.3
7.3
±0.15
27
±0.15
1
* Value in parentheses are for PFP-50N.
Model
PFP-100N
PFP-50N
Mounting Rail
(Material: Aluminum)
4.5
15 25 25
10 10
1,000
25 25 15 1 1.5
29.2242735
±0.3
16
Model
PFP-100N2
1.3
4.8
35.5 35.5
1.8
1.8
M4 spring
washer
10
6.2
1
50
M4 × 8
panhead
screw
11.5
10
End Plate
Model
PFP-M
MEMO
34
S8JX
35
S8JX-G S8JX-P
Common Precautions
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information on page 36.
1. Power Ratings
050: 50 W
100: 100 W
150: 150 W
2. Output Voltage
05: 5 V
12: 12 V
24: 24 V
48: 48 V
3. Configuration (50/100/150 W model)
None: Open type
C: Covered
4. Configuration/mounting
None: Front-mounting
D: DIN Rail-mounting
1. Power Ratings
300: 300 W
600: 600 W
2. Output Voltage
05: 5V
12: 12 V
24: 24 V
48: 48 V
3. Configuration/mounting (covered type)
C: Front-mounting
CD: DIN Rail-mounting
N: Without mounting bracket
Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
50-/100-/150-W Models
1234
S8JX-P@@@@@@@
300-/600-W Models
123
S8JX-P@@@@@@
S8JX
36
S8JX-G S8JX-P
Common Precautions
Ordering Information
List of Models
Note: For details on normal stock models, contact your nearest OMRON representative.
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan Model
Covered Power
Supplies
100 to 240 VAC (free)
(80 to 370 VDC *)
050 W
05 V 10 A
No
S8JX-P05005CD
12 V 4.2 A S8JX-P05012CD
24 V 2.1 A S8JX-P05024CD
48 V 1.1 A S8JX-P05048CD
100 W
05 V 20 A S8JX-P10005CD
12 V 8.5 A S8JX-P10012CD
24 V 4.5 A S8JX-P10024CD
48 V 2.1 A S8JX-P10048CD
150 W
05 V 30 A S8JX-P15005CD
12 V 13 A S8JX-P15012CD
24 V 6.5 A S8JX-P15024CD
48 V 3.3 A S8JX-P15048CD
300 W
5 V 60 A
Yes
S8JX-P30005CD
12 V 27 A S8JX-P30012CD
24 V 14 A peak current
16.5 A (200 VAC) S8JX-P30024CD
48 V 7 A S8JX-P30048CD
600 W
5 V 120 A S8JX-P60005CD
12 V 53 A S8JX-P60012CD
24 V 27 A peak current
31 A (200 VAC) S8JX-P60024CD
48 V 13 A S8JX-P60048CD
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan Model
Open type Power
Supplies
100 to 240 VAC (free)
(80 to 370 VDC *)
050 W
05 V 10 A
No
S8JX-P05005D
12 V 4.2 A S8JX-P05012D
24 V 2.1 A S8JX-P05024D
48 V 1.1 A S8JX-P05048D
100 W
05 V 20 A S8JX-P10005D
12 V 8.5 A S8JX-P10012D
24 V 4.5 A S8JX-P10024D
48 V 2.1 A S8JX-P10048D
150 W
05 V 30 A S8JX-P15005D
12 V 13 A S8JX-P15012D
24 V 6.5 A S8JX-P15024D
48 V 3.3 A S8JX-P15048D
DIN Rail-mounting *
DIN Rail-mounting *
S8JX
37
S8JX-G S8JX-P
Common Precautions
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan
Front-
mounting
bracket
Model
Covered Power
Supplies
100 to 240 VAC (free)
(80 to 370 VDC *)
050 W
05 V 10 A
No
Provided
S8JX-P05005C
12 V 4.2 A S8JX-P05012C
24 V 2.1 A S8JX-P05024C
48 V 1.1 A S8JX-P05048C
100 W
05 V 20 A S8JX-P10005C
12 V 8.5 A S8JX-P10012C
24 V 4.5 A S8JX-P10024C
48 V 2.1 A S8JX-P10048C
150 W
05 V 30 A S8JX-P15005C
12 V 13 A S8JX-P15012C
24 V 6.5 A S8JX-P15024C
48 V 3.3 A S8JX-P15048C
300 W
5 V 60 A
Yes
S8JX-P30005C
12 V 27 A S8JX-P30012C
24 V 14 A
peak current
16.5 A
(200 VAC) S8JX-P30024C
48 V 7 A S8JX-P30048C
600 W
5 V 120 A S8JX-P60005C
12 V 53 A S8JX-P60012C
24 V 27 A peak current
31 A (200 VAC) S8JX-P60024C
48 V 13 A S8JX-P60048C
300 W
5 V 60 A
No
S8JX-P30005N
12 V 27 A S8JX-P30012N
24 V 14 A peak current
16.5 A (200 VAC) S8JX-P30024N
48 V 7 A S8JX-P30048N
600 W
5 V 120 A S8JX-P60005N
12 V 53 A S8JX-P60012N
24 V 27 A peak current
31 A (200 VAC) S8JX-P60024N
48 V 13 A S8JX-P60048N
Configuration Input voltage Power ratings
Output voltage
(VDC)
Output current Built-in fan
Front-
mounting
bracket
Model
Open type Power
Supplies
100 to 240 VAC (free)
(80 to 370 VDC *)
050 W
05 V 10 A
No Provided
S8JX-P05005
12 V 4.2 A S8JX-P05012
24 V 2.1 A S8JX-P05024
48 V 1.1 A S8JX-P05048
100 W
05 V 20 A S8JX-P10005
12 V 8.5 A S8JX-P10012
24 V 4.5 A S8JX-P10024
48 V 2.1 A S8JX-P10048
150 W
05 V 30 A S8JX-P15005
12 V 13 A S8JX-P15012
24 V 6.5 A S8JX-P15024
48 V 3.3 A S8JX-P15048
Front-mounting *
Front-mounting *
S8JX
38
S8JX-G S8JX-P
Common Precautions
Ratings, Characteristics, and Functions
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 46.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 46.
*7. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*8. The weight indicated is for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Input specification 100 to 240 V input
Item Power ratings *150 W 100 W 150 W
Efficiency
5 V Models 73% min. 78% min. 79% min.
12 V Models 76% min. 78% min. 78% min.
24 V Models 77% min. 81% min. 81% min.
48 V Models 80% min. 81% min. 82% min.
Input
Voltage *2100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9)
Frequency *250/60 Hz (47 to 63 Hz)
Current *3100 V input 0.75 A max. 1.4 A max. 2.1 A max.
200 V input 0.4 A max. 0.75 A max. 1.1 A max.
Power factor 0.9 min.
Harmonic current emissions Conforms to EN61000-3-2
Leakage current *3100 V input 0.5 mA max.
200 V input 1 mA max.
Inrush current (for a
cold start at 25°C) *3
100 V input 17.5 A max.
200 V input 35 A max.
Output *4
Voltage adjustment range *510% to 15% (with V. ADJ) (48-V models: ±10%)
Ripple *32% (p-p) max.
This shall be 3% (p-p) or less when the ambient temperature is less than 0
°
C (for only 5 V type).
Input variation influence 0.4% max. with AC input voltage
Load variation influence 0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max. (at rated input and output)
Startup time 1,000 ms max.
Hold time *320 ms min.
Additional
functions
Overload protection *6
105% to 160% of rated load
current, voltage drop,
intermittent, automatic reset
105% to 160% of rated load current, voltage drop,
automatic reset
Overvoltage protection *7Yes
Overheat protection No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (For up to two Power Supplies; external diodes required.)
Alarm indicator No
Other
Ambient operating temperature Refer to the derating curve in Engineering Data on page 44 (with no icing or
condensation).
Storage temperature 25 to 75°C (with no icing or condensation)
Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (Color: Green)
EMI Conducted Emissions Conforms to EN 55011 Group 1 Class B and based on FCC Class B *9
Radiated Emissions Conforms to EN 55011 Group 1 Class B *9
EMS
Electrostatic Discharge Conforms to EN61000-4-2
Radiated Electromagnetic Field Conforms to EN61000-4-3
Electrical Fast Transient/Burst Conforms to EN61000-4-4
Surge Conforms to EN61000-4-5
Conducted Disturbance Conforms to EN61000-4-6
Voltage Dips/Short Interruptions Conforms to EN61000-4-11
Approved standards *9
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI SEMI F47-0706 (200-VAC input)
Weight *8370 g max. 550 g max. 590 g max.
S8JX
39
S8JX-G S8JX-P
Common Precautions
Input specification 100 to 240 V input
Item Power ratings *1300 W 600 W
Efficiency
5 V models 75% min. 76% min.
12 V models 77% min. 76% min.
24 V models 79% min. 78% min.
48 V models 78% min. 79% min.
Input
Voltage *2100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *8)
Frequency *250/60 Hz (47 to 63 Hz)
Current *3100 V input 4.5 A max. 8.7 A max.
200 V input 2.2 A max. 4.3 A max.
Power factor 0.9 min.
Harmonic current emissions Conforms to EN61000-3-2
Leakage current *3100 V input 0.5 mA max.
200 V input 1 mA max.
Inrush current (for a
cold start at 25°C) *3
100 V input 17.5 A max.
200 V input 35 A max.
Output *4
Voltage adjustment range *510% to 15% (with V. ADJ) (5 V, 48 V models: ±10%)
Ripple *32% (p-p) max.
3% (p-p) max. (for only 5 V type) *12
Input variation influence 0.4% max.
Load variation influence 0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max.
Startup time 1,000 ms max.
Hold time *320 ms min.
Additional
functions
Overload protection *6105% to 160%
of rated load current,
voltage drop, intermittent, automatic reset.
Overvoltage protection *7Yes
Overheat protection Yes
Parallel operation Yes (up to 5 Power Supplies)
Series operation Yes (For up to two Power Supplies; external diodes required.)
Remote sensing Supported
Remote control Supported
Alarm detection indication Yes (color: red)
Alarm output Provided, open-collector output, 30 VDC max, 50 mA max.
Other
Ambient operating temperature
Refer to the derating curve in Engineering Data on page 44 (with no icing or condensation).
Storage temperature 25 to 75°C (with no icing or condensation)
Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 100 mA)
100 VAC for 1 min. (between all outputs and RC terminals; detection current: 100 mA)
500 VAC for 1 min. (between all outputs and ALM terminals; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions *10
Output indicator Yes (Color: Green)
EMI Conducted Emissions *3Conforms to EN 55011 Group 1 Class B and based on FCC Class B *11
Radiated Emissions Conforms to EN 55011 Group 1 Class B *11
EMS
Electrostatic Discharge Conforms to EN61000-4-2
Radiated Electromagnetic Field Conforms to EN61000-4-3
Electrical Fast Transient/Burst Conforms to EN61000-4-4
Surge Conforms to EN61000-4-5
Conducted Disturbance Conforms to EN61000-4-6
Voltage Dips/Short Interruptions Conforms to EN61000-4-11
Approved standards *8
UL UR: UL 508 (Recognition)
*
13
UL Listed: UL508 (Listing)
*
14
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No.107.1, CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160) Over voltage category III,
EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI SEMI F47-0706 (200-VAC input)
Weight 1,200 g max.
*
91,800 g max.
*
9
S8JX
40
S8JX-G S8JX-P
Common Precautions
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 46.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 46.
*7. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*8. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*9. The weight is of the type without a mounting bracket.
*10.S8JX-P600@@CD: 100 m/s2
*11.The noise value will vary depending on wiring methods and other characteristics.
300-W/600-W models conform to Class B with an aluminum plate set under the product.
For the 300-W 5V and 600-W 5V and 12V models, insert a noise filter (TDK-Lambda RSEN-2016) in the input line.
*12.Measurement method conform to RC-9131A of the JEITA standards. For details, refer to Ripple Noise Voltage on page 57.
*13.Applicable to the 300-W/600-W 5V and 12V models
*14.Applicable to the 300-W/600-W 24V and 48V models
S8JX
41
S8JX-G S8JX-P
Common Precautions
Connections
Block Diagrams
Voltage
detection
Photocoupler
Overvoltage
detection circuit
Drive control
Circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Noise
filter
Inrush current
protection
Fuse
2.5 A
AC(L)
INPUT
AC(N)
Rectifier
Smoothing
circuit
Rectifier/
Smoothing circuit
High-frequency
current regulation
S8JX-P050@@@@ (50 W)
Voltage
detection
Photocoupler
Overvoltage
detection circuit
Drive control
Circuit
Overcurrent
detection
circuit
+V
V
DC OUTPUT
Noise
filter
Inrush current
protection
Fuse
6.3 A
AC(L)
INPUT
AC(N)
Rectifier
Smoothing
circuit
Rectifier/
Smoothing circuit
High-frequency
current regulation
S8JX-P100@@@@ (100 W)
S8JX-P150@@@@ (150 W)
S8JX
42
S8JX-G S8JX-P
Common Precautions
INPUT
AC(L)
AC(N)
Current balance
circuit
DC OUTPUT
-V
+V
-V
+V
Output voltage monitor
Remote sensing
-S
+S
Power supply balance
CB
CBG
Remote control
+RC
-RC
Fan
Auxiliary power
supply circuit
Overheating
detection
Alarm detection
Fan detection
Alarm display ALM
ALMC
ALME
Alarm output
Fuse
10 A Noise
filter
Rectifier
Inrush current
protection
High-frequency
current regulation
Smoothing
circuit
Rectifier/
Smoothing circuit
Rectifier/
Smoothing circuit
Control
circuit
Drive
circuit
Photocoupler
Photocoupler
Photocoupler
Photocoupler
Overcurrent
detection circuit
Rectifier/
Smoothing circuit
Voltage
detection
Overvoltage
detection circuit
S8JX-P300@@@@ (300 W)
INPUT
AC(L)
AC(N)
DC OUTPUT
-V
+V
-V
+V
-S
+S
CB
CBG
+RC
-RC
ALM
ALMC
ALME
Fuse
20 A Noise
filter
Rectifier
Inrush current
protection
High-frequency
current regulation
Smoothing
circuit
Rectifier/
Smoothing circuit
Rectifier/
Smoothing circuit
Control
circuit
Drive
circuit
Photocoupler
Photocoupler
Photocoupler
Photocoupler
Overcurrent
detection circuit
Rectifier/
Smoothing circuit
Voltage
detection
Overvoltage
detection circuit
Current balance
circuit
Output voltage monitor
Remote sensing
Power supply balance
Remote control
Fan
Auxiliary power
supply circuit
Overheating
detection
Alarm detection
Fan detection
Alarm display
Alarm output
S8JX-P600@@@@ (600 W)
S8JX
43
S8JX-G S8JX-P
Common Precautions
Construction and Nomenclature
Nomenclature
Reference Values
50-/100-/150-W Models
Reliability (MTBF)
50 W: 190,000 hrs
100 W: 160,000 hrs
150 W: 160,000 hrs
300 W: 160,000 hrs
600 W: 150,000 hrs
Definition MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device
failures, and indicates reliability of devices. Therefore, it does not necessarily represent a life of the product.
Life expectancy 10 yrs. min.
Definition The life expectancy indicates average operating hours under the ambient temperature of 40ºC and a load rate of 50%.
Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.
+V
V
AC(L)
AC(N)
+V
V
AC(L)
AC(N)
1
1
4
5
33
22
4
5
*1. The fuse is located on the (L) side. It is NOT user-replaceable. For a DC
power input, connect the low side to the positive (+) terminal.
*2.
This is the protective earth terminal specified in the safety standards. Always ground this terminal.
No. Name Function
1DC Output
Terminals (V), (+V) Connect the load lines to these terminals.
2AC Input Terminals
(L), (N) Connect the input lines to these terminals. *1
3Protective Earth
Terminal (PE) ( ) Connect the ground line to these terminals. *2
4Output Voltage
Adjuster (V. ADJ)
It is possible to increase or decrease the output
voltage.
5Output Indicator
(DC ON: Green) Lights green while a direct current (DC) output is ON.
Note: The S8JX-P05005CD is
shown above.
Note: The S8JX-P15005C is shown
above.
57
6
4
2
1
3
3
5
4
6
7
12
*1. The fuse is located on the (L) side. Ensure that the (L) side is set to (+).
*2. This is a PE (Protective Earth) terminal defined in safety standards and
must be grounded.
*3. Signal input/output connectors are included as standard and
implemented in the CN1 before shipment.
In this connector, the circuits of 1-2, 3-4, and 7-8 are shorted. Removal
of the connector may deteriorate the output stability and accuracy, so be
sure to perform the connection of +S and -S terminals.
Never connect a load to the output voltage monitor terminal (+V, -V).
No. Name Function
1 Input Terminals (L), (N) Connect the input lines to these
terminals. *1
2 Protective Earth Terminal (PE) ( ) Connect the ground line to these termi-
nals. *2
3 DC Output Terminals (V), (+V) Connect the load lines to these
terminals.
4 Output Indicator (DC ON: Green) Lights green while a direct current (DC)
output is ON.
5 Output Voltage Adjuster (V. ADJ) It is possible to increase or decrease
the output voltage.
6 Alarm indicator (ALM: Red)
This lamp lights up at the time of output
voltage deterioration or fan stoppage,
and in standby mode by remote control
function.
7
Signal output connector *3 1: Output voltage monitor terminal
(+V)
2: Remote sensing terminal (+S)
3: Output voltage monitor terminal (-V)
4: Remote sensing terminal (-S)
5: Current balance terminal (CB)
6: Current balance ground terminal
(CBG)
7: Remote control terminal (+RC)
8: Remote control terminal (-RC)
9: (Not connected)
10: (Not connected)
11: Alarm detection output terminal
(ALMC) (Collector side)
12: Alarm detection output terminal
(ALME) (Emitter side)
11
9
7
5
3
1
12
10
8
6
4
2
CN 1/2
Note: The S8JX-P30024N is shown above.
Note: The S8JX-P60024N is shown above.
600-W Models
300-W Models
S8JX
44
S8JX-G S8JX-P
Common Precautions
Engineering Data
Derating Curves (Standard Mounting)
Front-mounting, DIN Rail mounting, Bottom-mounting,
Side-mounting
Note: 1.
Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading in the above graph).
2. If there is a derating problem, use forced air-cooling.
3. (For Customers using 100-W type for a DC Input)
When using an input voltage of less than 100 VDC, reduce
the load calculated with the above derating curve by at least
the following coefficients.
When using a voltage exceeding 340 VDC, the ambient
temperature should be 60°C or less.
Note: 1.
Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading in the above graph).
2. The ambient temperature is defined at a location 50 mm
forward from the center of the front surface of the product.
3. (For Customers using 300-/600-W type for a DC Input)
Reduce the load calculated with the above derating curve
by at least the following coefficients.
Front-mounting, DIN Rail mounting, Bottom-mounting
Horizontal-side-mounting
Note: 1. Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading in the above
graph).
2. If there is a derating problem, use forced air-cooling.
3. (For customers using 150-W type for a DC Input)
When using an input voltage of less than 100 VDC, reduce
the load calculated with the above derating curve by at least
the following coefficients.
When using a voltage exceeding 340 VDC, the ambient
temperature should be 60°C or less.
50-/100-W Models
300-/600-W Models
–20 –10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Ambient Temperature (°C)
Covered type
Open-frame type
1
Load rate (%)
1
0
0
Input voltage (VDC)
100
0.9
1.0
340 37080
Coefficient
Maximum operating
temperature 60°C
S8JX-P 100-W Models
–20 –10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Ambient Temperature (°C)
Load rate (%)
1
1
0
0
Input voltage (VDC)
Coefficient
100
1.0
0.8
37080
S8JX-P 300-/600-W Models
150-W Models
–20 –10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Ambient Temperature (°C)
Covered type
Open-frame type
1
Load rate (%)
–20 –10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Ambient Temperature (°C)
1
Load rate (%)
Covered type
Open-frame type
1
0
0
Input voltage (VDC)
100
1.0
0.8
340 37080
Coefficient
Maximum operating
temperature 60°C
S8JX-P 150-W Models
S8JX
45
S8JX-G S8JX-P
Common Precautions
Mounting
The following three mounting methods are possible.
. Front-mounting: Refer to Mounting Bracket Provided with Front-mounting Power
Supplies on page 54.
. Bottom-mounting
. Side-mounting
Note: Additional mounting methods are also available using DIN Rail-mounting
models.
Standard Mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the
standard mounting method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended.
3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply is designed to radiate heat by
means of natural air flow.
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the
standard mounting method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended.
3. Do not cover the air holes (provided at fan mounted side and the opposite side) to have enough air-cooling.
50-/100-/150-W Models
50-/100-/150-W Models
300-/600-W Models
C
B
Front-mounting
*
DIN Rail-mounting Bottom-mounting
*
Vertical Side-mounting
*
Horizontal Side-mounting
*
300W 600W
300W 600W
300W 600W
Front-mounting Bottom-mounting Side-mounting
S8JX
46
S8JX-G S8JX-P
Common Precautions
Remote sensing function
Use this function when it is desirable to automatically compensate for
voltage drops in the load line.
The remote sensing function is operated by connecting +S terminal (2
pin on CN) to +side of the load terminal and -S terminal (4 pin on CN)
to -side of the load terminal.
When the remote sensing function is not used, using a connector
provided as standard enables the connection between +S and +V
terminals (1 pin on CN) and between -S and -V terminals (3 pin on
CN) respectively.
Note: 1. Use a two-core shield wire for connection line (*1).
2. If the voltage drop on a load line (*2) is large, the output
voltage of the power supply may rise by the voltage drop
amount and activate the overvoltage protection. Therefore,
be sure to use as thick a wire as possible.
3. The voltage drop in the load line must be 0.3 V or less.
4. If the load line is long, be sure to use an electrolytic
capacitor between the load terminals. As the used
electrolytic capacitor may be heated by ripple current due to
the connected load, be sure to use an electrolytic capacitor
having an allowable ripple current exceeding the used ripple
current.
5. Opening status of +S and -S terminals may deteriorate the
output stability and accuracy. Therefore, be sure to connect
+S and -S terminals.
6. Remove a connector provided as standard and prepare a
harness separately.
Remote control function
This function is to turn ON/OFF the output by an external signal using
+RC terminal (7 pin on CN) and -RC terminal (8 pin on CN) while input
voltage remains applied. To use this function, connect a switch or a
transistor to +RC and -RC terminals.
When not in use, use the standard supplied connector to short-circuit
+RC and -RC terminals.
Max. applied voltage: 12 V max., Counter voltage: -1 V max.,
Sink current: 3.5 mA
Note: 1. If counter voltage is applied to remote control terminals,
output voltage cannot be turned ON/OFF.
Please remember this when wiring.
2. Use a twist wire or a two-core shield wire for connection line.
3. Remote control circuit is disconnected from input and output
circuits.
4. Remove a connector provided as standard and prepare a
harness separately.
Alarm detection function
When output voltage drops due to overcurrent protection, overvoltage
protection, or overheat protection in operation or input voltage drop,
when the built-in fan stops, or when the Power Supply goes standby
by remote control, the alarm indicator (LED: red) lights up to indicate
the output voltage trouble. In addition, the transistor outputs that
outside.
Transistor output: 30 VDC max., 50 mA max.
Residual voltage when the function is ON: 2 V max., leakage current
when the function is OFF: 0.1 mA max.
Detection voltage: approximately 80% of the output voltage setting
value
When trouble is detected, the transistor output is turned OFF
(nonconductive pins 11-12 on CN) and the LED (red) lights up.
Note: 1. The alarm detection function monitors the voltage at the
Power Supply output end. To check an accurate voltage,
measure a voltage at the load end.
2. Remove the standard supplied connector and prepare a
connector separately.
Overload Protection
The Power Supply is provided with an overload protection function
that protects the power supply from possible damage by overcurrent.
When the output current rises above 105% to 160% min. of the rated
current, the protection function is triggered, decreasing the output
voltage. When the output current falls within the rated range, the
overload protection function is automatically cleared.
Note: 1. When a load is connected that has a built-in DC-DC
converter, the overload protection may operate at startup
and the power supply may not start.
2. Internal parts may occasionally deteriorate or be damaged
if a short-circuited or overcurrent state continues during
operation.
3. Internal parts may possibly deteriorate or be damaged if the
Power Supply is used for applications with frequent inrush
current or overloading at the load end. Do not use the Power
Supply for such applications.
(Reference value)
Level Output voltage Built-in fan
Short or L (0-0.8 V) ON Rotation
Open or H (2.4-12 V) OFF Stop
+V*2
+
V
*1
V–S
S8JX
CN
+V+S
TR
SW
+RC
–RC
S8JX CN
50-W Models
100-/150-W Models 300-/600-W Models
ALMC
ALME
S8JX
CN
Vce max : DC30V
Ic max : 50mA
50
Intermittent operation
0
Load rate (%)
100
Output voltage (V)
0
Load rate (%)
10050
Output voltage (V)
500
Load rate (%)
100
Intermittent operation
Output voltage (V)
S8JX
47
S8JX-G S8JX-P
Common Precautions
Overvoltage Protection
Consider the possibility of an overvoltage and design the system so
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the power supply fails. When an excessive voltage
that is approximately 130% of the rated voltage or more is output, the
output voltage is shut OFF, preventing damage to the load due to
overvoltage. Reset the input power by turning it OFF for at least three
minutes and then turning it back ON again.
Consider the possibility of an overvoltage and design the system so
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails. When an excessive voltage
that is approximately 130% of the rated voltage or more is output, the
output voltage is shut OFF, preventing damage to the load due to
overvoltage and simultaneously the alarm indicator will be lit. Reset
the input power by turning it OFF for at least three minute and then
turning it back ON again.
(Reference value)
Note: Do not turn ON the power again until the cause of the
overvoltage has been removed.
Output peak current (300-W 24V, 600-W 24V
Models)
The following conditions should be satisfied for the peak current
value.
Note: 1. Do not hold peak load current over 10 seconds.
In addition, you should not use duty cycle under conditions
beyond above figure.
It may cause damage in its power supply.
2. Please derate peak load current depending on ambient
temperature and mounting orientation.
3. Please keep the average current of peak load cycle from
becoming more than the rated value.
Overheat Protection
If the internal temperature rises excessively as a result of fan failure
or any other reason, the overheat protection circuit will be triggered to
shut OFF the output voltage.
The alarm indicator lights at the same time. Reset the input power by
turning it OFF for at least three minutes and then turning it back ON
again.
Inrush Current, Startup Time, Output Hold Time
Note: A maximum startup time of 1,000 ms is required. Construct a
system configuration that considers the startup time of other
devices.
50-/100-/150-W Models
300-/600-W Models
Output voltage (V)
Overvoltage protection
Operating
Variable range
Rated output
Voltage
0 V
[A]
t1
Ip
lave
10 s
rated peak current
rated current
Ip: peak current
lave: average current
t2
t1
Duty= t1+t2
t1 ×100 [%] 35% (180 to 240 VAC)
output current
300-/600-W Models
Startup time Hold time (20 ms min.)
AC input
voltage
AC input
current
Output
voltage
Inrush current on input application
90%96.5%
Input ONInput OFF
S8JX
48
S8JX-G S8JX-P
Common Precautions
Dimensions (Unit: mm)
Front-mounting Models
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
Two, M3
78.5±0.5
118±0.5
Two, M3
120
±0.5
S8JX-P050@@ (50 W)
S8JX-P050@@C (50 W)
5
15
11.5 max. 129
118±0.5
120±0.5
86±0.5
78.5±0.5
92±1
36
7
22
5
8.2
9.5
42±1
Label
3.5 dia.
(for mounting)
3.5
(for mounting)
3.5
(for mounting)
Cover 3.5 dia.
(for mounting)
Two, M3 (Depth: 4 mm max.)
Five, M3.5
8.2
9.5
42±1
Five, M3.5
Label
Cover
11.5 max. 159
78.5±0.5
92±1
7
3.5
(for mounting)
5
5
15
148±0.5
150±0.5
98±0.5
36
22
Two, M3 (Depth: 4 mm max.)
3.5 dia.
(for mounting)
3.5 dia.
(for mounting)
3.5
(for mounting)
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
Two, M3
78.5
±0.5
148
±0.5
Two, M3
150
±0.5
S8JX-P100@@ (100 W)
S8JX-P100@@C (100 W)
S8JX-P15012 (150 W)
S8JX-P15012C (150 W)
S8JX-P15024 (150 W)
S8JX-P15024C (150 W)
S8JX-P15048 (150 W)
S8JX-P15048C (150 W)
S8JX
49
S8JX-G S8JX-P
Common Precautions
S8JX-P15005 (150 W)
S8JX-P15005C (150 W)
Two, M4
10
13
8.2
9.5
42±1
Three, M3.5
Label
Cover
13.5 max. 159
148±0.5
78.5±0.5
92±1
7
5
3.5
(for mounting)
3.5 dia.
(for mounting)
5
15
150±0.5
98±0.5
36
22
Two, M3 (Depth: 4 mm max.)
3.5 dia.
(for mounting)
3.5
(for mounting)
Panel mounting holes dimensions
Surface screw mounting
Side
Mounting
Bottom
Mounting
Two, M3
78.5
±0.5
148
±0.5
Two, M3
150
±0.5
S8JX
50
S8JX-G S8JX-P
Common Precautions
Panel mounting holes dimensions
Rear surface screw
mounting
Front
Mounting
113.5±0.5
48±0.5
Three, 4.5 dia.
S8JX-P300@@C (300 W)
4.5 Three, M4
Four, M5
22.5 max.
10
8.5
5
165
13
16
13.5
26
124.3±1 113.5±0.5
5
77.6±1
217.3
110.8
48±0.5 5
5
70
Two, 4.5 dia.
Three, M4
Four, M5 20
Four, M4 (Depth: 6 mm max.)
Four, M4 (Depth: 6 mm max.)
13
16
26
92±1
5
71±1
8.5
10
22.5 max. 5
165
24.1
46±0.5
14
35±0.5
110±0.5
41.5 max. 120±0.5
Panel mounting holes dimensions
Rear surface screw mounting
Standard
Mounting
Side
Mounting
120±0.5
Four, 4.5 dia.
35±0.5
110±0.5
Four, 4.5 dia.
46±0.5
S8JX-P300@@N (300 W)
S8JX
51
S8JX-G S8JX-P
Common Precautions
5
10 4.5
8.5
Three, M4
110.8
124.3±1
13.5
116.6±1
Two, 4.5 dia.
Four, M5
113.5±0.5
22.5 max. 164.8
217.3
109
93±0.5
26
13
16
Panel mounting holes dimensions
Rear surface screw mounting
Front
Mounting
113.5±0.5
93±0.5 Three,
4.5 dia.
S8JX-P600@@C
(600 W)
Three, M4
Four,
M5
Four, M4 (Depth: 6 mm max.)
Four, M4 (Depth: 6 mm max.)
50±0.5 92±1
21
64±0.5
25
25
125±0.5
40.5 max.
112±0.5
22.5 max.
164.8
10
8.5
110±1
26 1316
Panel mounting holes dimensions
Rear surface screw mounting
Standard
Mounting
Side
Mounting
112±0.5
Four, 4.5 dia.
64±0.5
125±0.5
Four, 4.5 dia.
50±0.5
S8JX-P600@@N (600 W)
S8JX
52
S8JX-G S8JX-P
Common Precautions
DIN Rail-mounting Models
14.5
8.2
9.5
Label
42
Five, M3.5
Cover
43.4±1 11.5 max. 129
92±1
47
7 (Sliding: 16.6 max.)
137.6
S8JX-P050@@D (50 W)
S8JX-P050@@CD (50 W)
14.5
8.2
9.5
Label
42
Five, M3.5
Cover
43.4±1 11.5 max. 159
167.6
92±1
47
7 (Sliding: 16.6 max.)
S8JX-P100@@D (100 W)
S8JX-P100@@CD (100 W)
S8JX-P15012D (150 W)
S8JX-P15012CD (150 W)
S8JX-P15024D (150 W)
S8JX-P15024CD (150 W)
S8JX-P15048D (150 W)
S8JX-P15048CD (150 W)
10
13
8.2
9.5
42
Three, M3.5
Label
Two, M4
Cover
43.4±1 14.5
13.5 max. 159
167.6
92±1
47
7 (Sliding: 16.6 max.)
S8JX-P15005D (150 W)
S8JX-P15005CD (150 W)
S8JX
53
S8JX-G S8JX-P
Common Precautions
Three, M4
8.9
26 13
16
77.6±1
Four, M5
110.8±1
46
8.5
6.6
(Sliding: 12 max.)
10
22.5 max. 217.3
70
222.8
S8JX-P300@@CD (300 W)
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
10
8.5
26
13
16
116.6±1
Four, M5
109
Three, M4
110.8±1
6.6
(Sliding: 12 max.)
8.9
46
217.3
222.8
22.5 max.
S8JX-P600@@CD (600 W)
Note: Use a metal DIN Rail when mounting a 600-W model to a DIN Rail.
S8JX
54
S8JX-G S8JX-P
Common Precautions
Mounting Bracket Provided with Front-mounting Power Supplies a
50-/100-/150-W Models
DIN Rail (Order Separately)
Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit.
Terminal Cover (Order Separately)
Replacement Fan (sold separately)
S82Y-J00F Front-mounting
Bracket Front-mounting Method
Temporarily attach the enclosed mounting
bracket as shown in the illustration on the right,
hook the holes (parts a) in the Power Supply on
hooks on the mounting bracket (parts b), and
secure the Power Supply with two mounting
screws.
Terminal Cover model Applicable Power Supply and
applicable location
S82Y-JTC1
S8JX-P50W
S8JX-P100W
S8JX-P150W 12-V, 24-V or 48-V output
S82Y-JX-C4P1 S8JX-P 300 W output side
S82Y-JX-C5P1 S8JX-P 300 W input side
Product Model
Replacement fan unit for 300-W models S82Y-JXP30FAN
Replacement fan unit for 600-W models S82Y-JXP60FAN
Dimensions Mounting
dimensions
11
9
1.5
60
11
20
5
31.5
20.5
15
4.7
4.6
4.6 15
±0.2
74
Two, 3.5 dia.
t = 1.0
Material: Stainless steel
Two, M3
20
60
b
b
a
a
Mounting
bracket
Note: Mounting screws are not
provided.
Mounting Rail
(Material: Aluminum)
4.5
15 25 25
10 10
1,000 (500)
25 25 15 (5) *
35±0.3
7.3±0.15
27±0.15
1
* Value in parentheses are for PFP-50N.
Model
PFP-100N
PFP-50N
Mounting Rail
(Material: Aluminum)
4.5
15 25 25
10 10
1,000
25 25 15 1 1.5
29.2242735±0.3
16
Model
PFP-100N2
1.3
4.8
35.5 35.5
1.8
1.8
M4 spring
washer
10
6.2
1
50
M4 × 8
panhead
screw
11.5
10
End Plate
Model
PFP-M
S8JX
55
S8JX-G S8JX-P
Common Precautions
Safety Precautions
Refer to Safety Precautions for All Power Supplies.
Minor electric shock, fire, or Product failure may
occasionally occur. Do not disassemble, modify, or
repair the Product to touch the interior of the
Product.
Minor burns may occasionally occur. Do not touch
the Product while power is being supplied or
immediately after power is turned OFF.
Fire may occasionally occur. Tighten terminal screws
to the specified torque.
M3.5, M4:1.13 N·m.
(The DC output terminal of S8JX-G15005@@ and
S8JX-P15005:1.56 N·m.)
M5:2.25 N·m.
Minor injury due to electric shock may occasionally
occur. Do not touch the terminals while power is
being supplied. Always close the terminal cover after
wiring.
Minor electric shock, fire, or Product failure may
occasionally occur. Do not allow any pieces of metal
or conductors or any clippings or cuttings resulting
from installation work to enter the Product.
Mounting
Take adequate measures to ensure proper heat dissipation to
increase the long-term reliability of the Product.
The 300 W 24V, 48V models of S8JX-G series are designed to
radiate heat by means of natural air-flow. Be sure to allow
convection in the atmosphere around devices when mounting. Do
not use in locations where the ambient temperature exceeds the
range of the derating curve.
The 300 W 5V, 12V, 600 W models of S8JX-G series, and 300 W,
600 W models of S8JX-P series are designed to radiate heat by
means of forced air-flow. Do not cover the air holes (provided at fan
mounted side and the opposite side) to have enough air-cooling.
The screws must not protrude beyond the following values inside
the Power Supply when screw holes provided on the chassis are
used.
15 W, 35 W, 50 W, 100 W, or 150 W: 4 mm
300 W or 600 W of S8JX-P series: 6 mm
300 W or 600 W of S8JX-G series: 8 mm
Mounting screw tightening torque (recommended value) : 0.54 N
·
m.
Front mounting is possible using provided mounting bracket.
When cutting out holes for mounting, make sure that cuttings do
not enter the interior of the Products.
Improper mounting will interfere with heat dissipation and may
occasionally result in deterioration or damage of internal parts. Use
the standard mounting method only.
The internal parts may occasionally deteriorate and be broken due
to adverse heat radiation. Do not loosen the screw on the side face
of the main body.
When mounting two or more Power Supplies side-by-side, allow at
least 20 mm for S8JX-G series and 15 mm for S8JX-P series
spacing between them.
Provide a space of at least 20 mm back and forth for S8JX-G
series, and 50 mm back and forth for S8JX-P series when
mounting 300-W and 600-W models as well.
Use the metal plate as the mounting panel.
Minor fire may occasionally occur. Set the input voltage switch to
the input voltage that is to be used (150-W, 5-V models of S8JX-G
series only).
*1. Convection of air
*2. 20 mm min. (15 mm min. for S8JX-P series)
*3. Use a metal plate as the mounting surface.
CAUTION
Precautions for Safe Use
15-/35-/50-/100-/150-W Models
S8JX-G Series 300-W 5V, 12V Model
S8JX-G Series 300-W 24V, 48V Model
Standard Mounting
(Horizontal Mounting)
*1
*1
*2
*3
Standard Mounting
(Bottom-mounting)
*1
*1
*2
*3
*1
*2
*1
Standard Mounting
(Front-mounting and DIN Rail-mounting)
*1
*1
*1
*3*2
*2
Standard Mounting
(Bottom-mounting)
Standard Mounting
(Front-mounting and DIN Rail-mounting)
S8JX
56
S8JX-G S8JX-P
Common Precautions
*1. Convection of air
*3. Use a metal plate as the mounting surface.
Wiring
Connect the ground completely. A protective earthing terminal
stipulated in safety standards is used. Electric shock or malfunction
may occur if the ground is not connected completely.
Minor fire may possibly occur. Ensure that input and output
terminals are wired correctly.
Do not apply more than 75 N force to the terminal block when
tightening it.
Be sure to remove the sheet covering the Product for machining
before power-ON so that it does not interfere with heat dissipation.
Use the following material for the wires to be connected to the
S8JX to prevent smoking or ignition caused by abnormal loads.
Recommended Wire Type
*The rated current for the output terminals on the S8JX-G30005@@, S8JX-
G30012@@, S8JX-G60005@, S8JX-G60012@, S8JX-P300@@ and S8JX-
P600@@ is 60A for each terminal. The rated current for the output terminals
on the S8JX-G30024@@, S8JX-G30048@@, S8JX-G60024@, and S8JX-
G60048@ is 20 A for each terminal. Use two terminals together if the current
flow is higher than the rated terminal current.
Method of Manufacturing Connector Harness for
Signal I/O
For S8JX-P Series 300-/600-W models, PHD connectors
manufactured by JST Mfg. Co., Ltd. should be used.
To ensure correct wiring, the following points should be borne in mind
when manufacturing the connector. It is recommended that the JST
Mfg. Co., Ltd. catalog be read for further details.
Electric cable size AWG26 to AWG22 should be used.
The electric cable sheath stripping length should be approximately
2.3 mm.
Dedicated tool YC (Manufactured by JST Mfg. Co., Ltd.) should be
used for crimping of terminals and wiring.
Although UL1007 (Twisted wire) and other equivalent twisted wires
can be used for electric cables, UL1061 with a small outer sheath
shape and equivalent twisted wires should be used for AWG22.
When accommodating crimped terminal wiring in the housing,
insert the wiring as far as possible to the back of the housing in a
single movement and check for an audible click. In addition, check
that wiring inserted in the housing is properly locked in place.
Installation Environment
Do not use the Power Supply in locations subject to shocks or
vibrations. In particular, install the Power Supply as far away as
possible from contactors or other devices that are a vibration
source.
Install the Power Supply well away from any sources of strong,
high-frequency noise and surge.
Ambient Operating and Storage Environments
Store the Power Supply at a temperature of 25 to 65°C (25 to
75°C for S8JX-P series) and a humidity of 25% to 90%.
The Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply outside the derating range (i.e., the
area shown by shading in the derating curve diagram on
page 44.)
Use the Power Supply at a humidity of 25% to 85%.
Do not use the Power Supply in locations subject to direct sunlight.
Do not use locations where liquids, foreign matter, or corrosive
gases may enter the interior of the Product.
Overload Protection
Internal parts may possibly deteriorate or be damaged if a short-
circuited, overload or peak load state continues during operation.
Internal parts may possibly deteriorate or be damaged if the Power
Supply is used for applications with frequent inrush current or
overloading at the load end. Do not use the Power Supply for such
applications.
Charging a Battery
When connecting a battery at the load, connect an overcurrent
limiting circuit and overvoltage protection circuit.
S8JX-P Series 300-W Models
S8JX-G Series 600-W Models
S8JX-P Series 600-W Models
15 W, 35 W
AWG12 to AWG20 (a cross section of
0.517 to 3.309 mm2)
UL-certified temperature of at least 75°C
50W, 100W,
150 W (except for 5 V)
AWG12 to AWG16 (a cross section of
1.309 to 3.309 mm2)
UL-certified temperature of at least 60°C or
60/75°C
150 W at 5 V
Input side
AWG12 to AWG16 (a cross-section of
1.309 to 3.309 mm2)
UL-certified temperature of at least 60°C or
60/75°C
Output side
AWG8 to AWG14 (a cross-section of 2.081
to 8.368 mm2)
UL-certified temperature of at least 60°C or
60/75°C
S8JX-G
series
300W 5V, 12V
600W 5V, 12V
S8JX-P
series
300 W, 600 W
Input side
AWG12 to AWG20 (a cross section of
0.517 to 3.309 mm2)
UL-certified temperature of at least 60
°
C or 60/75
°
C
Output side
AWG6 to AWG20 (a cross section of 0.517
to 13.30 mm2)
UL-certified temperature of at least 60
°
C or 60/75
°
C
S8JX-G series
300 W 24V, 48V,
600 W 24V, 48V
AWG12 to AWG20 (a cross section of
0.517 to 3.309 mm2)
UL-certified temperature of at least 60
°
C or 60/75
°
C
*3
*1*1
*3
*1*1
*1
*1
*3
Connector
used S12B-PHDSS
Manufactured
by JST Mfg.
Co., Ltd.
Housing PHDR-12VS
Terminal SPHD-001T-P0.5 or BPHD-001T-P0.5
1
S8JX
57
S8JX-G S8JX-P
Common Precautions
Output Voltage Adjuster (V.ADJ)
The output voltage adjuster (V.ADJ) may possibly be damaged if it
is turned with unnecessary force. Do not turn the adjuster with
excessive force.
After completing output voltage adjustment, be sure that the output
capacity or output current does not exceed the rated output
capacity or rated output current.
Ripple Noise Voltage
(S8JX-G Series 300 W 5 V and 600 W 5 V or 12 V
Models)
The specified standard for the ripple voltage noise was measured with
a measurement circuit that is based on JEITA standard RC-9131A.
DIN Rail-mounting
To mount the Power Supply to a DIN
Rail, pull down the rail stopper until
you hear it clicks open, hook portion
(A) of the Power Supply onto the DIN
Rail, press the Power Supply in
direction (B), and then push up the rail
stopper to lock the Power Supply in
place.
To dismount the Power Supply, pull
down portion (C) with a flat-blade
screwdriver and pull out the Power
Supply.
Series Operation
Two power supplies can be connected in series. The (±) voltage
output can be accomplished with two Power Supplies.
Note: 1. If the load is short-circuited, a reverse voltage will be
generated inside the Power Supply. If this occurs the Power
Supply may possibly deteriorate or be damaged. Always
connect a diode as shown in the figure. Select a diode
having the following ratings.
2. Although Products having different specifications can be
connected in series, the current flowing through the load
must not exceed the smaller rated output current.
Parallel Operation
Parallel operation is not possible.
Parallel operation is possible under 80% of the rated value.
To operate in parallel, set the switch to the "PARALLEL" side.
The length and thickness of each wire connected to the load must
be the same so that there is no difference in voltage drop value
between the load and the output terminals of each Power Supply.
It is desirable to set the same value on the voltage adjuster of each
Power Supply.
Type Schottky Barrier diode
Dielectric strength (VRRM) Twice the rated output voltage or above
Forward current (IF) Twice the rated output current or above
150mm
S8JX
Oscilloscope
Frequency band:
100 MHz
C1 C2 Load
C1:100µF
C2:0.47µF
Coaxial cable
+V
V
30 mm min.
Track stopper
(C)
(B)
(A)
+V
V
AC (L)
AC (N)
AC (L)
AC (N)
+V
V
+V
V
AC (L)
AC (N)
AC (L)
AC (N)
+V
V
Series Operation
Correct
Output Voltage (±)
Correct
15-/35-/50-/100-/150-W Models
S8JX-G Series 300-/600-W Models
+V
V
AC (L)
AC (N)
AC (L)
AC (N)
+V
V
Parallel Operation
Incorrect
+V
V
AC (L)
AC (N)
AC (L)
AC (N)
+V
V
Parallel Operation
Correct
S8JX
58
S8JX-G S8JX-P
Common Precautions
Connecting CB terminal (5 pin on CN) and CBG terminal (6 pin on
CN) enables the current balancing function and that allows the
parallel operation at 80% or less of the total output capacity.
Up to five Power Supplies can be connected.
Use 2-conductor shielded cable as a connection wire (*1).
Adjust the output voltage difference of each Power Supply to 100 mV
or less or 1% or less of the rated output voltage, whichever is smaller,
using the output voltage adjuster (V. ADJ).
During parallel operation, load current may be biased to one side,
resulting in damage to internal components.
Parallel operation is used to increase static capacity. The output
voltage may drop with sudden load fluctuations.
There may be steps in the rising waveform of the output voltage
during parallel operation.
Remove the standard supplied connector and prepare a connector
separately.
Backup operation
Backup operation is possible. (Requires an external diode.)
The same model should be used for power supplies A and B.
The output voltages of power supplies A and B output should be
set higher only by a value equivalent to the drop in diode D1 and D2
forward voltages (VF).
In addition, since power loss occurs resulting from power supply
output current (IOUT) × diode forward voltage (VF), the diode should
be cooled to ensure that its temperature is kept at the value
indicated in the catalog or lower.
Since power loss occurs due to load power and the diode, care
should be exercised to ensure that the rated power (Rated output
voltage × rated output current) for one power supply is not
exceeded.
For backup operation, do not connect the CB and CBG terminals
on S8JX-P-series 300-W or 600-W models.
In Case There Is No Output Voltage
The possible cause for no output voltage may be that the overcurrent
or overvoltage protection has operated. The internal protection may
operate if a large amount of surge voltage such as a lightening surge
occurs while turning ON the Power Supply.
In case there is no output voltage, please check the following points
before contacting us:
Checking overcurrent protected status:
Check whether the load is in overcurrent status or is short-
circuited. Remove wires to load when checking.
Checking overvoltage or internal protection:
Turn the power supply OFF once, and leave it OFF for at least
7 minutes for S8JX-G series and 3 minutes for S8JX-P series.
Then turn it ON again to see if this clears the condition.
There is a possibility that functions such as over-current protection,
over-voltage protection or overheating protection are functioning. In
addition, other possible causes include stoppage of the built-in fan
and the remote control function (OFF). Please check the following 5
points and, if there is still no output voltage, contact your OMRON
sales representative.
Method of Checking Over-current Protection
Check (after removing load line) whether or not the load is in over-
current status (including short circuits).
Method of Checking Over-voltage Protection
Switch off the input power supply, and switch back on after at least
3 minutes have elapsed.
Check whether or not the +S and -S terminals are open.
Method of Check Overheating Protection
Switch off the input power supply and switch back on after allowing
sufficient time for cooling.
Checking for Built-in Fan Stoppage
Check whether or not the built-in fan has stopped. The fan is a
replaceable component.
Checking the Remote Control Function
Check whether or not the +RC and -RC terminals are in open
status. Carry out the regulated connections.
S8JX-P Series 300-/600-W Models
Type: Schottky Barrier diode
Withstand voltage (VRRM): Equivalent to or higher than the rated
power supply output voltage
Forward current (IF): Double the rated power supply output
current or higher
S8JX
CN
CB CBG
+V
V
AC(L)
AC(N)
S8JX CN
CB CBG
+V
V
AC(L)
AC(N)
*1
+V
A
B
D
1
D
2
-V
+V
-V
Load
S8JX-G Series
S8JX-P Series 50-/100-/150-W Models
S8JX-P Series 300-/600-W Models
S8JX
59
S8JX-G S8JX-P
Common Precautions
Switching the AC Input Voltage between 100 and 200 VAC
The input voltage can be switched between 100 V and 200 V by using
the input voltage switch. Make the setting shown in the following
figure for the voltage that will be used. (The input voltage is factory-
set to 200 V.)
The input voltage can be switched between 100 and 200 V by shorting
or opening the input voltage selection terminals. Set the required
voltage as shown below. (The voltage is factory-set to 200 V.)
Note: A 300-W model is shown above.
Fan Replacement
The service life of the fan is approximately 50,000 hours (at 25°C).
The service life varies, however, depending on the ambient
temperature or other surrounding environmental conditions such as
dust. As a preventive maintenance measure, replace the fan within
approx. two years if it is used at an ambient temperature of 40°C.
Purchase the S82Y-JX FAN Replacement Fan (sold separately) to
replace the fan.
Replace the fan as shown in the following illustration.
Please contact your OMRON sales representative regarding fan
replacement. Fans will be replaced at cost. In addition, a replacement
fan unit (Model S82Y-JXP
@@
FAN) is available. Please use the curve
below as a guideline for the timing of fan replacement.
Fan replacements made by the customer fall outside the scope of
safety standards.
Replacement should be implemented as shown below.
S8JX-G Series 150-W, 5-V Models
S8JX-G Series 300-/600-W Models
The input voltage switch is at the back
on the bottom of the Power Supply. "230V": 200 to 240 VAC
"115V": 100 to 120 VAC
SHORT BAR
N
L
VOLTAGE SELECT
SHORT 100-120V
OPEN 200-230V
SHORT BAR
N
L
VOLTAGE SELECT
SHORT 100-120V
OPEN 200-230V
200-V input100-V input
Short with the short bar. Remove the short bar
and leave the terminals open.
S8JX-G Series 300-W 5V, 12V/600-W Model
S8JX-P Series 300-/600-W Models
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Fan Set:
Fan (above), instruction sheet
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THA
T THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. T041-E1-08 0316 (1111)
© OMRON Corporation 2009-2016 All Rights Reserved.
OMRON Corporation Industrial Automation Company
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact: www.ia.omron.com
Kyoto, JAPAN
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
CSM_19_2_0318