3
Insulation 500 V AC between output groups
500 V AC between fast output and internal logic
Non-insulated between outputs
500 V AC between output and internal logic
500 V AC between fast input and internal logic
Non-insulated between inputs
500 V AC between input and internal logic
Non-insulated between supply and ground
500 V AC between supply and internal logic
Marking CE
Surge withstand 1 kV for transistor output in common mode conforming to EN/IEC 61000-4-5
1 kV for input in common mode conforming to EN/IEC 61000-4-5
1 kV for relay output in differential mode conforming to EN/IEC 61000-4-5
0.5 kV for power lines (DC) in differential mode conforming to EN/IEC 61000-4-5
1 kV for shielded cable in common mode conforming to EN/IEC 61000-4-5
1 kV for power lines (DC) in common mode conforming to EN/IEC 61000-4-5
Mounting support Plate or panel with fixing kit
Top hat type TH35-7.5 rail conforming to IEC 60715
Top hat type TH35-15 rail conforming to IEC 60715
Height 3.54 in (90 mm)
Depth 3.74 in (95 mm)
Width 7.48 in (190 mm)
Product weight 1.37 lb(US) (0.62 kg)
Environment
Standards CSA C22.2 No 142
UL 1604
UL 508
ANSI/ISA 12-12-01
CSA C22.2 No 213
EN/IEC 61131-2 : 2007
Marine specification (LR, ABS, DNV, GL)
Product certifications CSA
CULus
IACS E10
RCM
Resistance to electrostatic discharge 4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields 1 V/m (2 GHz...3 GHz) conforming to EN/IEC 61000-4-3
3 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
10 V/m (80 MHz...1 GHz) conforming to EN/IEC 61000-4-3
Resistance to fast transients 1 kV for transistor output conforming to EN/IEC 61000-4-4
1 kV for input conforming to EN/IEC 61000-4-4
1 kV for serial link conforming to EN/IEC 61000-4-4
2 kV for power lines conforming to EN/IEC 61000-4-4
Resistance to conducted disturbances, induced by
radio frequency fields
10 V (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) conforming to
Marine specification (LR, ABS, DNV, GL)
3 V (0.1...80 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Electromagnetic emission Radiated emissions, test level: 47 dBμV/m QP with class A (radio frequency: 230
MHz...1 GHz) conforming to EN/IEC 55011
Radiated emissions, test level: 40 dBμV/m QP with class A (radio frequency: 30...230
MHz) conforming to EN/IEC 55011
Conducted emissions, test level: 63 dBμV/m QP, condition of test: power lines (radio
frequency: 1.5...30 MHz) conforming to EN/IEC 55011
Conducted emissions, test level: 79...63 dBμV/m QP, condition of test: power lines
(radio frequency: 150 kHz...1.5 MHz) conforming to EN/IEC 55011
Conducted emissions, test level: 120...69 dBµV/m QP, condition of test: power lines
(radio frequency: 10...150 kHz) conforming to EN/IEC 55011
Immunity to microbreaks 10 ms
Ambient air temperature for operation -10...55 °C for horizontal installation
-10...50 °C for vertical installation
Ambient air temperature for storage -13...158 °F (-25...70 °C)
Relative humidity 10...95 % without condensation in storage
10...95 % without condensation in operation