BS88, IEC269
Industrial HRC Fuse Links 660V Range
Offset Bolted Tags
H07-660
Offset Bolted Tag
Catalog
Number
Nom.
Watts
Loss
Rated
Voltage
Dimensions (mm)
Amp
Ratings
Pre-
Arcing
Total
at
415V
Total
at
550V
Total
at
660V
ABC D E F G H J
H07-660 2 0.8 1.6 2.4 3.2 1.5
82.3 71.5 52.0 22.0 22.4 11.5 8.7 7.7 5.4
H07-660 4 5 10 15 20 2.7
H07-660 6 20 40 60 80 3.3 660V
H07-660 10 44 130 180 220 2.8 a.c.
H07-660 16 250 765 1,000 1,200 2.8 250V
H07-660 20 430 900 1,300 2,500 2.7 d.c.
H07-660 25 850 1,800 2,500 4,900 3.1
H07-660 32 2,100 4,400 6,100 12,000 3.3
Bussmann Division
Cooper (U.K.) Ltd
Burton-on-the-Wolds
Leicestershire, LE12 5TH
United Kingdom
Tel: (44) (0)1509 88 27 37
Fax: (44) (0)1509 88 27 86
Dimensional Data
I t (Ampere Seconds)
22
Bussmann®
Time-Current Characteristic Curve
2A
4A
6A
10A
16A
20A
25A
32A
Head Office
St. Louis, MO, U.S.A. Tel: (314) 527-3877 Fax: (800) 544-2570 International Fax: (314) 527-1445
BiFBussmann Information Fax (00 1) 314 527 1450 HO7 11.96
Doc. No. 4150
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end
user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and
to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any
technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
Carton Quantities:
Ordering Code:
All H07 range packed in 20's
Rating followed by H07-660