SPECIFICATION
MDR-100-12 MDR-100-24 MDR-100-48
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME Note.5
HOLDUP TIME (Typ.)
VOLTAGERANGE Note.6
FREQUENCY RANGE
EFFICIENCY (Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT (Typ.)
SAFETY STANDARDS
HARMONICCURRENT
EMSIMMUNITY
WORKINGHUMIDITY
WORKINGTEMP.
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
12V 24V 48V
7.5A 4A 2A
0~7.5A 0~4A 0~2A
90W 96W 96W
120mVp-p 150mVp-p
24~30V
200mVp-p
48~56V
1.0% 1.0% 1.0%
12~15V
1.0% 1.0% 1.0%
1.0% 1.0% 1.0%
3000ms,50ms/230VAC3000ms,50ms/115VAC atfullload
50ms/230VAC20ms/115VAC atfullload
85~264VAC120~370VDC
47~63Hz
85% 86% 88%
1.3A/115VAC0.8A/230VAC
COLDSTART 30A/115VAC60A/230VAC
105~150% ratedoutputpower
Protectiontype: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
15.6~18V 31.2~36V 57.6~64.8V
-10~+60 (Refertooutputloadderatingcurve)
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50
Component: eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-610~500Hz,2G10min./1cycle,periodfor60min.
346Khrsmin.MIL-HDBK-217F(25 )
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Deating maybe needed under low input voltages, please check the derating curve for more detail.
FileName:MDR-100-SPEC2010-12-07
UL508, TUVEN60950-1approved,designrefertoNECCLASS2(for24V,48Vonly)
Complianceto EN61000-3-2,-3
96WSingleOutputIndustrialDINRailPowerSupply MDR-100 ser i e s
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note4)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
EMICONDUCTION&RADIATION
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage / Over temperature
ZCS/ZVS technology to reduce power dissipation
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
DC OK relay contact
No load power consumption<1W
NEC Class 2, limited power source
LED indicator for power on
100% full load burn-in test
3 years warranty
(for 24V,48V only)
Features :
55*90*100mm(W*H*D)
0.42Kg;30pcs/13.6Kg/0.82CUFT
LEAKAGECURRENT <1mA /240VAC
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:>100MOhms/500VDC/25 /70%RH
FUNCTION DCOKSIGNAL Relaycontactrating(max.):30V/1A resistive
CompliancetoEN55011,EN55022(CISPR22),EN61204-3ClassB
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3,heavyindustrylevel,criteria A
OVERTEMPERATURE 90 10 (RTH2)detectonheatsinkofpowertransistor
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
POWERFACTOR (Typ.) PF 0.95/230VACPF 0.98/115VAC atfullload
http://store.iiic.cc/
MechanicalSpecification
FileName:MDR-100-SPEC2010-12-07
BlockDiagram
DCOKRelayContact
-10 0 10 20 30 40 50 60 70 (VERTICAL)
20
40
60
80
100
AMBIENTTEMPERATURE( )
LOAD(%)
CIRCUIT
DETECTION
O.L.P.
O.T.P.
EMIFILTER
&
RECTIFIERS
PFC
CIRCUIT
POWER
SWITCHING FILTER
&
RECTIFIERS +V
DCOK
-V
I/P
PWMPFC
CONTROLCONTROL
O.V.P.
O.C.P.
OutputDeratingVSInputVoltage
INPUTVOLTAGE(VAC)60Hz
85 10095 120115 160140 200180 240220 264
LOAD(%)
Ta=25
90
100
80
70
60
50
40
DeratingCurve
+
InstallDINrail TS35/7.5or TS35/15
35
+V +V
90
55
-V -V
N L
DCOK
DCOK
+V ADJ
5 5 5 5 5
7.5
7.5
100
CaseNo.973A Unit:mm
FG
ContactClose PSUturnson/DCOK.
PSUturnsoff/DCFail.
30V/1A resistiveload.
ContactOpen
ContactRatings(max.)
96WSingleOutputIndustrialDINRailPowerSupply MDR-100 ser i e s
http://store.iiic.cc/