1
10-2014, Rev. 1014
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company.
Catalog and product specification according
to IEC 61810-1 and to be used only together
with the ‘Definitions’ section.
Catalog and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Catalog product data, ‘Definitions’ section,
application notes and all specifications are
subject to change.
SCHRACK
General Purpose
Panel/Plug-in Relays
Multimode Relay MT
n 2/3 pole 10A, 2 form C (CO) or 3 form C (CO) contacts
n DC and AC coils
n Mechanical indicator as standard
n Electrical indicator
n New test system with front operated finger protected
push-to-test button and integral locking test tab
n White write on panel
Typical applications
Mechanical engineering, plant control.
Approvals
VDE Cert. No. 40009096, UL E214025
Technical data of approved types on request.
Contact Data
Contact arrangement 2 form C (CO) or 3 form C (CO)
Rated voltage 240VAC
Max. switching voltage 400VAC
Rated current 10A 10A
Limiting making current, max. 20ms 20A 20A
Limiting breaking current 10A 10A
Switching power 2500VA 2500VA
Contact material AgNi90/10 AgNi90/10
- gold plated
Contact style single single
contact contact
Min. recommended contact load 12V 20mV
at 10mA at 1mA
Initial voltage drop 30mV at 100mA/6VAC/1kHz
Frequency of operation, with/without load 1200/6000h-1
Operate time max., DC coil 15ms
Release time max., DC coil 10ms
Bounce time max., DC coil, form A/form B 4/10ms
Contact ratings
Type Contact Load Cycles
IEC 61810
MT22 DC coil C (CO) 10A, 250VAC, cos
φ
=1, 35°C 100x10
3
MT22 AC coil C (CO) 10A, 250VAC, cos
φ
=1, 35°C 20x10
3
MT32 DC coil C (CO) 10A, 250VAC, cos
φ
=1, 35°C 100x10
3
MT32 AC coil C (CO) 10A, 250VAC, cos
φ
=1, 35°C 20x10
3
UL 508
MT3 A (NO)/B (NC) B300, 40°C 6.000
MT2 C (CO) 10A, 250VAC, resistive, 40° 30x10
3
MT2 A (NO)/B (NC) B300 40°C 6.000
MT3 C (CO) 10A, 250VAC, resistive, 40°C 100x10
3
Contact Data (continued)
Mechanical endurance
DC coil 20x106 operations
AC coil 20x106 operations
Coil Data
Coil voltage range 6 to 220VDC
6 to 230VAC
Operative range, IEC 61810 2
Coil insulation system according UL class 130 (B)
Coil versions, DC coil
Coil code Rated Operate Release Coil Rated coil
STD PD3) voltage voltage voltage resistance power
VDC VDC VDC Ω±10%1)2) W
006 0A6 6 4.5 0.6 32 1.1
012 0B2 12 9.0 1.2 110 1.3
024 0C4 24 18.0 2.4 475 1.2
048 0E8 48 36.0 4.8 2000 1.2
060 0G0 60 45.0 6.0 2850 1.3
110 1B0 110 82.5 11.5 100001) 1.2
220 2C0 220 165.0 22.0 400002) 1.2
1) Coil resistance ±12%, 2) Coil resistance ±15%.
3) Protection diode PD; standard polarity: 2-pole relays: +2 / -7, 3-pole relays: +2 / -10.
All figures are given for coil without pre-energization, at ambient temperature +23°C.
Coil versions, AC coil, 50/60Hz
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
50/60Hz 50/60Hz 50/60Hz
VAC VAC VAC Ω±10%1) VA
006 6 4.8/5.1 1.8 5.3 2.29/1.98
012 12 9.6/10.2 3.6 24 2.19/1.86
024 24 19.2/20.4 7.2 86 2.26/1.95
048 48 38.4/40.8 14.4 345 2.28/1.97
060 60 48.0/51.0 18.0 544 2.27/1.96
115 115 92.0/97.8 34.5 2000 2.37/2.00
230 230 184.0/195.5 69.0 83001) 2.32/1.96
1) Coil resistance ±12%.
All figures are given for coil without pre-energization, at ambient temperature +23°C.