1
Thermal (T- and TA-Line) T12-211
https://www.schurter.com /PG17_20
Circuit Breakers
Circuit Breaker for Equipment thermal, Threaded neck type, Reset type, Quick connect terminals
Approvals and Compliances
Description
- Threaded neck type
- Thermal circuit breaker
- 1-pole
- Reset type
- Quick connect terminals 6.3 x 0.8 mm
Unique Selling Proposition
- Compact design
- Positively trip-free release
- Available with cover
- Different mounting possibilities
Applications
- Power supplies
- Uninterruptible power supply
- Power tools
- Household appliances
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
Rated Voltage AC 240 V; 50/60 Hz
Rated Voltage DC 28 V
Rated current range AC 0.05 - 15/16 A , see approbations
Conditional short circuit ca-
pacity
IEC: Inc, PC1, AC 240 V: 1 kA
Short circuit capacity Icn at In < 7 A/240 VAC : 8 x In
at In 7 A/240 VAC : 200 A
AC/DC 28 V : 400 A
Degree of Protection from front side IP 40 acc. to IEC 60529
Dielectric Strength 50 Hz: > 1.5 kV
Impulse 1.2/50 μs: > 2.5 kV
Insulation Resistance 500 VDC > 100 MΩ
Endurance typical 2 x Ir: 5000 switching cycles
Endurance minimum Reset type
AC : 2 x Ir , cos φ 0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
50 switching cycles
Overload IEC: min. 40 trips
@ 6 x Ir, cos φ 0.6
UL / CSA: min. 50 trips
@ 1.5 x Ir, cos φ 0.75
Ambient temperature -5 °C to 60 °C
Vibration Resistance ± 1.5 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Shock Resistance 100 G / 6 ms
acc. to IEC 60068-2-27, test Ea
Tripping Type Thermal
Actuation Type Reset type
Weight ca. 10 g
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: T12
Approval Logo Certificates Certification Body Description
VDE Approvals VDE VDE Certificate Number:
UL Approvals UL UL File Number:
CQC Approvals CQC CCC File Number:
2
Thermal (T- and TA-Line)
T12-211 https://www.schurter.com /PG17_20
Circuit Breakers
Application standards
Application standards where the product can be used
Organization Design Standard Description
Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Compliances
The product complies with following Guide Lines
Identification Details Initiator Description
CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS SCHURTER AG EU Directive RoHS 2011/65/EU
China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Dimension [mm]
T12-211
12
3/8-27UNS-2A
10
24.6
14.7
18
Ø 5.7
11.5
48.5
+0.5
0.2
2
31–0.2
8.8
SW
14
14.5
3
Thermal (T- and TA-Line) T12-211
https://www.schurter.com /PG17_20
Circuit Breakers
T12-211SN
8.8
48.5
12
3/8-27UNS-2A
10
14.7
18
Ø 5.7
+0.5
0.2
2
57. 5
57.5
2.5
20.2
24.6
31–0.2
3
14.5
SW
14
A 6.3
5
46
Ø 9.6
8.9
16 16
4
Thermal (T- and TA-Line)
T12-211 https://www.schurter.com /PG17_20
Circuit Breakers
Diagrams
Tap 4,8 x 0,8 mm
2
1
Tap 4,8 x 0,8 mm
23
1
Tap 4,8 x 0,8 mm
54
6
2
1
Tap 4,8 x 0,8 mm
5
23
14
6
Approval Main circuit Auxiliary circuit
Rated current Rated voltage AC Rated voltage DC Rated current Rated voltage AC Rated voltage DC
UL 1077
CSA C22.2 No. 235
0.05...15 A 240 V 28 V 2 A
3 A
120 V
-
-
28 V
CSA C22.2 No. 235 0.3...16 A 240 V 28 V 1 A 240 V -
IEC 60934 0.05...16 A 240 V 28 V 1 A 240 V 28 V
GB 17701 0.05...16 A 240 V 28 V 1 A 240 V 28 V
5
Thermal (T- and TA-Line) T12-211
https://www.schurter.com /PG17_20
Circuit Breakers
Typical internal resistance
Rated Current [A] Internal Resistance []
0.05 225.000
0.50 3.300
1.00 0.880
2.00 0.267
3.00 0.128
4.00 0.073
5.00 0.040
6.00 0.031
7.00 0.018
8.00 0.018
9.00 0.010
10.00 0.0087
11.00 0.0087
12.00 0.0087
13.00 0.0087
14.00 0.0070
15.00 0.0070
16.00 0.0055
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C] Correction factor
-5 0.87
0 0.90
10 0.95
23 1.00
30 1.05
40 1.12
50 1.20
60 1.30
Example: Rated current = 5 A; Environmental temperature = 50 °C; --> Correction factor =
1.2; Resulting current = 6.0 A
6
Thermal (T- and TA-Line)
T12-211 https://www.schurter.com /PG17_20
Circuit Breakers
Time-Current-Curves
Time in Seconds
10'000
60
2´000
1´000
500
200
100
50
20
10
5
2
1
0, 5
0, 3
0, 2
0, 1
[ sec ][ min ]
10
5
1
30
20
1,05 10854321,32
< 7,0 A
> 7,0 A
Multiple of Rated Current In
Reference Temperature +23°
Config. Code
T12|-|1|2|3|A|B|C|-|1.23|
The characters are placeholders for the correspondingly keys of selections from the key tables.
T12|-| 1 |2|3|A|B|C|-|1.23| = Mounting
Mounting Configuration
key
Threaded neck type with hexagonal- and knurled nut 2
T12|-|1| 2 |3|A|B|C|-|1.23| = Actuation Type
Actuation Type Configuration
key
Reset type 1
T12|-|1|2| 3 |A|B|C|-|1.23| = Terminal
Terminal Configuration
key
Quick connect terminal 6.3x0.8mm 1
T12|-|1|2|3| A |B|C|-|1.23| = Auxiliary contact
Auxiliary contact Configuration
key
Auxiliary contact S
T12|-|1|2|3|A| B |C|-|1.23| = Shunt terminal
Shunt terminal Configuration
key
Shunt terminal N
T12|-|1|2|3|A|B| C |-|1.23| = Setting indication
Setting indication Configuration
key
Setting indication R
T12|-|1|2|3|A|B|C|-| 1.23 | = Rated current
Rated current Configuration
key
0.05 A 0.05
0.1 A 0.1
0.15 A 0.15
0.2 A 0.2
0.3 A 0.3
0.4 A 0.4
0.5 A 0.5
0.6 A 0.6
0.7 A 0.7
0.8 A 0.8
0.9 A 0.9
1.0 1
1.1 A 1.1
1.2 A 1.2
1.3 A 1.3
1.4 A 1.4
Other rated currents on request
7
Thermal (T- and TA-Line) T12-211
https://www.schurter.com /PG17_20
Circuit Breakers
Rated current Configuration
key
1.5 A 1.5
1.6 A 1.6
1.7 A 1.7
1.8 A 1.8
1.9 A 1.9
2.0 A 2
2.1 A 2.1
2.3 A 2.3
2.5 A 2.5
2.8 A 2.8
3.0 A 3
3.3 A 3.3
3.5 A 3.5
4.0 A 4
4.5 A 4.5
5.0 A 5
Other rated currents on request
Rated current Configuration
key
5.5 A 5.5
6.0 6
6.5 A 6.5
7.0 A 7
7.5 A 7.5
8.0 A 8
8.5 A 8.5
9.0 A 9
9.5 A 9.5
10.0 A 10
11.0 A 11
12.0 A 12
13.0 A 13
14.0 A 14
15.0 A 15
16.0 A 16
Other rated currents on request
Variants
Rated current Construction variants Config. Code Order Number
Auxiliary contact Shunt terminal Setting indication
0.8 A l T12-211S-0.8 4410.0044
1.0 lllT12-211SNR-1 4410.0655
2.5 A l T12-211S-2.5 4410.0046
6.5 A l T12-211S-6.5 4410.0264
10.0 A T12-211-10 4410.0106
12.0 A T12-211-12 4410.0019
Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-
Check-SCHURTER
Packaging Unit 20 Pcs
Accessories
Description
T-Line Accessories
Accessories to T-Line
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
30.11.2017
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Schurter:
4410.0011 4410.0016 4410.0358 4410.0367 4410.0436 4410.0543 4410.0558 4410.0602 4410.0662 4410.0118
4410.0239 4410.0398 4410.0103 4410.0359 4410.0669 4410.0794 4410.0030