Protection level UP (L-PEN) ≤ 1.4 kV
Residual voltage (L-PEN) ≤ 1.4 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1.1 kV (at 5 kA)
≤ 1 kV (at 3 kA)
Clamping voltage SVR (L-PEN) ≤ 0.9 kV
Clamping voltage ringwave (L-PEN) ≤ 1.2 kV (category C3 20 kV/10 kA)
≤ 1.1 kV (category C2 10 kV/5 kA)
≤ 1 kV (category B3/C1 6 kV/3 kA)
Response time (L-N) ≤ 25 ns
Max. required backup fuse with branch wiring 125 A (gL/gG)
Max. required backup fuse with V-type through
wiring
40 A (gL/gG)
Short-circuit resistance IP with max. backup fuse
(effective)
25 kA
Connection, protective circuit
Connection method Screw connection
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 16 mm
Conductor cross section stranded min. 2.5 mm²
Conductor cross section stranded max. 16 mm²
Conductor cross section solid min. 2.5 mm²
Conductor cross section solid max. 25 mm²
Conductor cross section AWG/kcmil min. 12
Conductor cross section AWG/kcmil max 4
Remote indicator contact
Connection name Remote fault indicator contact
Switching function PDT contact
Connection method Pluggable screw connection
Screw thread M2
Tightening torque 0.25 Nm