AC-DC 180 Watts xppower.com ECP180 Series * Low 1"Profile with 2"x 4"Footprint * 120 W Convection / 180 W Forced-cooled * High Efficiency - up to 95% * Medical & ITE Approvals * Class I & Class II Applications * <0.5 W No Load Input Power * 3 Year Warranty Specification Input General * 85-264 VAC, derate from 120 W at 100 VAC to 110 W at 90 VAC and 100 W at 85 VAC when convection cooled Input Frequency * 47-63 Hz Input Current * 1.8 A typical at 115 VAC, 0.9 A typical at 230 VAC Inrush Current * 120 A max at 230 VAC, cold start at 25 C Power Factor * >0.95 at full load Earth Leakage Current * <230 A at 264 VAC, 60 Hz No Load Input Power * <0.5 W Input Protection * Internal T3.15A/250VAC fitted in line and neutral Input Voltage Output Output Voltage Initial Set Accuracy Minimum Load Start Up Delay Start Up Rise Time Hold Up Time * * * * * * Line Regulation Load Regulation Transient Response * * * Ripple & Noise * Overvoltage Protection * Overload Protection Short Circuit Protection Thermal Protection Temperature Coefficient Fan Supply * * * * See tables 1% at 50 % load No minimum load requirement 1 s max 55 ms typical 10 ms minimum at full load and 115 VAC 16 ms typical at 120 W 0.5% max 0.5% max 4% maximum deviation, recovering to less than 1% within 500 s for 25% step load 1% max pk-pk, 20 MHz bandwidth, (see note 2) 110% - 140% of nominal voltage on main output. Recycle mains to reset. 110-160% Trip and restart (hiccup) Measured internally. Auto resetting. 0.02%/C * 12 V at 500 mA Efficiency Isolation Protection Level Power Density Switching Frequency MTBF * See table * 4000 VAC Input to Output 1500 VAC Input to Ground 1500 VAC Output to Ground * Primary to Secondary: 2 MOPP Primary to Earth: 1 MOPP Secondary to Earth: 1 MOPP * 15/22 W/in3 convection/forced-cooled * PFC: 70-130 KHz, PWM: 50-90 KHz * >300 kHrs to MIL-HDBK-217F at 25 C, GB Environmental Operating Temperature * -20 C to +70 C derate from 100% load at 50 C to 50% load at 70 C Cooling * Convection cooled: 120 W Forced cooled: 180 W with 10 CFM Operating Humidity * 5% to 90% RH, non condensing Operating Altitude * 5000 m Storage Temperature * -40 C to +85 C Shock * IEC68-2-27, 30 g, 11 ms half sine, 3 times in each of 6 axes Vibration * IEC68-2-6, 10-500 Hz, 2 g 10 mins / sweep. 60 mins for each of 3 axes EMC & Safety Emissions Harmonic Currents Voltage Flicker ESD Immunity Radiated Immunity EFT/Burst Surge Conducted Immunity Dips & Interruptions Safety Approvals * EN55032/11, Level B conducted & Level A radiated * EN61000-3-2 Class A * EN61000-3-3 * EN61000-4-2, 8 kV air, 4 kV contact, Perf Criteria A * EN61000-4-3, 3 V/m, Perf Criteria A * EN61000-4-4, level 3, Perf Criteria A * EN61000-4-5, installation class 3, Perf Criteria A * EN61000-4-6, 3 V, Perf Criteria A * EN55024, 100% 10 ms, 30%, 500 ms, 100%, 5000 ms Perf Criteria A, A, B for high line, A, B, B for low line at full load, EN60601-1-2, 30% 500 ms, 60% 100 ms, 100% 10 ms, 100% 5000 ms, Perf Criteria A, A, A, B for high line, A, B, A, B for low line at full load * UL60950-1, IEC60950-1, EN60950-1, ANSI/AAMI ES 60601-1, IEC60601-1, EN60601-1 Output Current Convection-cooled Forced-cooled(1) Ripple and Noise pk-pk(2) Fan Output(4,5) Efficiency(3) Model Number(4) 12.0 V 10.00 A 15.00 A 120 mV 12 V/0.5 A 92% ECP180PS12 Output Voltage 15.0 V 8.00 A 12.00 A 150 mV 12 V/0.5 A 92% ECP180PS15 24.0 V 5.00 A 7.50 A 240 mV 12 V/0.5 A 93% ECP180PS24 28.0 V 4.30 A 6.43 A 280 mV 12 V/0.5 A 93% ECP180PS28 36.0 V 3.33 A 5.00 A 360 mV 12 V/0.5 A 94% ECP180PS36 48.0 V 2.50 A 3.75 A 480 mV 12 V/0.5 A 94% ECP180PS48 Notes 4. Typical voltage, actual regulated voltage will be in range of 10.5 V to 11.3V 5. Regulation of the fan output requires a minimum load of 10 W on the main output. 1. Requires 10 CFM. 2. Measured with 20 MHz bandwidth and 10 F electrolytic capacitor in parallel with 0.1 F ceramic capacitor 3. Minimum average efficiencies measured at 25%, 50%, 75% & 100% of 180 W load and 230 VAC input. Mechanical Details CN1 - Input Connector Pin 1 Neutral Pin 2 Not Fitted Pin 3 Line 0.84 (21.3) 0.06 (1.6) Mates with JST housing VHR-3N and JST Series SVH-21T-P1.1 crimp terminals 0.10 (2.5) 4.00 (101.6) Mounting holes marked with must be connected to safety earth 3.75 (95.3) CN2 - Output Connector Pin 1 -Vout Pin 2 -Vout Pin 3 -Vout Pin 4 +Vout Pin 5 +Vout Pin 6 +Vout 6 1.74 (44.5) CN2 2.00 (50.8) 1 1 CN1 Mates with JST housing VHR-6N and JST Series SVH-21T-P1.1 crimp terminals 3 2 1 CN3 - Fan Connector Pin 1 Fan - Pin 2 Fan + Mates with Molex housing 22-01-1022 and 2759 crimp terminals CN3 Mounting screw holes 4 places 0.13 (3.2) 0.13 (3.2) 0.13 (o3.4) Mounting holes marked with must be connected to safety earth for class I applications and connected together for class II applications for optimum EMC performance Notes 1. All dimensions shown in inches (mm). Tolerance: 0.02 (0.5) 2. Weight: 0.51 lbs (230 g) approx. Derating Curve Output Power (%) 100 80 60 40 20 0 -20 -10 0 10 20 30 40 50 60 70 80 Ambient Temperature (C) 03 June 19 AC-DC ECP180 Models and Ratings