Technical Specifications
82100-1260 Iss. 2A
THURLBY THANDAR INSTRUMENTS
HA1600A
Harmonics, Flicker and Power Analyser
high speed and high accuracy power measurements
MAINS ANALYSER
Measurement Circuit: Single Phase with standard mains connector.
Current Rating: 16A rms continuous, or national connector rating if
lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Current Ranges: ±24mA pk to ±400A pk in fifteen 2:1 ranges.
Frequency Range: 43 - 67 Hz.
Shunt Resistance: 3mW.
Sampling Rate: 300 points per cycle.
Basic Accuracy: Better than 0.2% ±1mA, up to 16A.
Measured Parameters: Vrms, Vpk, Arms, Apk, Crest factors, THD, W, VA,
Power factor, Frequency, Inrush current.
Display Modes:
Tabular display of all parameters including latest and highest inrush cur-
rent. Waveform graph display of voltage and current with normal, max
hold, accumulate and multiple cycle display.
Monitor Outputs: Re-constructed Voltage and Current Signals.
HARMONICS ANALYSER
Measurements: 1st harmonic to 40th harmonic.
Measurement processing for both 2006 and 2000 editions of EN61000-3-2.
Continuous calculation, analysis and assessment of unfiltered, filtered, av-
erage, minimum and maximum current harmonic levels and limits. Continu-
ous measurement and assessment of supply waveform and harmonics.
Current Rating: 16A rms continuous, or national connector rating if
lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Current Ranges: ±24mA pk to ±400A pk in fifteen 2:1 ranges.
Frequency Range: 43 - 67 Hz.
Shunt Resistance: 3mW.
Transform Windows: Continuous 4, 10, 12 or 16 cycle Discrete Fourier
Transforms.
Basic Accuracy: Better than 5% of limit or 0.2% of selected range (which-
ever is the greater) ± 1mA.
Display Modes:
Display of load supply assessment for voltage, harmonics, crest limits and
frequency against requirements of EN61000-3-2.
Histogram or tabular display of supply voltage harmonics.
Histogram display of current harmonics with limits, Min. hold, Max. hold
and percentage of limit display options.
Tabular display of current harmonics showing present values, limits, aver-
age values, average as percent of limit, maximum values, maximum as
percent of limit and pass or fail assessment for each harmonic.
Test Control:
Untimed, manually timed or automatically timed tests; user-defined test
time.
Limits automatically determined from EN61000-3-2 for appropriate class;
Class C and Class D limits can be automatically calculated from power
measurements or from ratings declared by the user. Minimum and maxi-
mum power thresholds for limits can be changed by the user.
Facility for declaring supply voltages other than 230V and deriving appro-
priate limits. Facility for insetting test limits.
Report Printing:
Direct printer connection for hard-copy report with user-entered narrative,
supply voltage assessment and current harmonic analysis and assess-
ment.
VOLTAGE FLUCTUATIONS & FLICKER METER
Measurements: Voltage fluctuations dmax, dc, d(t) and flicker Pst and Plt
to EN61000-3-3 and EN61000-4-15.
Current Rating: 16A rms continuous, or national connector rating if
lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Fluctuation Range: 25% max. (relative to nominal voltage)
Flickermeter Range: Voltage change up to 20% (sinewave change) or 10%
(low repetition rate rectangular change) relative to AGC
level. Equivalent to 6400 pu on 8.8 Hz sinewave.
Designed and built in Europe by:
Thurlby Thandar Instruments Ltd.
Glebe Road, Huntingdon. Cambs. PE29 7DR United Kingdom
Tel: +44 (0)1480 412451 Fax: +44 (0)1480 450409
Email: info@aimtti.com Web: www.aimtti.com
optional low-distortion 1kW AC power source (AC1000A)
compliance quality harmonics analysis to EN61000-3-2
compliance quality flicker measurement to EN61000-3-3
Flickermeter AGC: Up to ± 5%.
Flickermeter Accuracy: Better than 5% for Pst range 0·7 to 10·0.
Frequency Range: 50 Hz (operates over 43 – 67 Hz).
Report Printing: Tabular listing of voltage variations, Pst classifier and Pst
in each Plt interval.
GENERAL
Display: 320 x 240 pixel backlit LCD.
Clock: Realtime clock for time/date stamping of Report data.
Interfaces: Parallel Printer, RS-232, USB.
Instrument Supply: 230V or 115V ±14%, 48 to 65Hz.
Operating Range: +5°C to 40°C, 20-80% RH.
Storage Range: –10°C to +60°C.
Dimensions: 357 x 132 x 235mm (WxHxD)
Weight: 4.4 kg
Safety: Complies with EN61010-1
EMC Compliance: Complies with EN61326-1
FREE FIRMWARE UPDATES
Changes to measurement methods required by occasional updates to the
EN61000-3-2 & EN61000-3-3 standards will generally require just an instrument
firmware update. So far, it has beeb possible to upgrade all HA1600A and
HA1600 models ever built to meet the latest requirements.
To upgrade firmware and to check what revisions of the standard are now sup-
ported, follow links from the Support page of the TTi web site.
HA-PC LINK PLUS SOFTWARE
HA-PC LINK PLUS is PC (Windows) software supplied with the HA1600A.
It can communicate with the instrument through either an RS232 or a USB con-
nection.
It is intended to assist users in taking routine compliance measurements and ar-
chiving the results.
The PC is used for configuration, display and data archiving only; all real time
data handling and measurement processing continues to be performed by the
Digital Signal Processor in the instrument. The performance of the PC does not
affect the accuracy of the measurement results, and so there is no need for the
either the PC or its software to be covered by a calibration certificate.
AC1000A LOW DISTORTION POWER SOURCE
Input Voltage: Factory built to 220V to 240V, 110V to115V or 100V.
Factory configure to 50Hz or 60Hz.
Installation Category II.
Supply Tolerances: Voltage ± 10%. Frequency ± 1%
Output Voltage: Tracks the amplitude of the fundamental of the input
voltage. A variable voltage input may be used to adjust
the output voltage to within the limits specified by
EN61000–3–2.
Output Distortion: Will meet the requirements of EN61000–3–2 for all
normal levels of input voltage distortion.
Output Current: Maximum continuous output current is 4·4A (10A peak).
Output Power: Maximum output power is input voltage x 4·4 VA
Input Connection: IEC connector; front panel switch.
Output Connection: U.K., Schuko, or other national outlet sockets. Load
power switch can be set to DIRECT or CORRECTED for
‘A–B’ comparisons.
Protection: Thermal trip automatically diverts load to a DIRECT con-
nection in the event of thermal overload.
Operating Range: +5°C to +35°C at full rated output; 20% to 80% RH
(non-condensing).
Storage Range: –40°C to +70°C
Environmental: Indoor use at altitudes to 2000m, Pollution Degree 2.
Safety: Complies with EN61010–1
EMC: Complies with EN31326-1
Size and Weight: 357 x 132 x 235mm mm (W x H x D); 5.5kg.
Thurlby Thandar Instruments Ltd. operates a policy of continuous development and
reserves the right to alter specifications without prior notice.
HA1600A Power and Harmonics Analyser Harmonics analysis to EN61000-3-2
High speed compliance quality measurements Fluctuations & flicker measurement to EN61000-3-3
High performance power
analyser
The HA1600A is a high speed, high accu-
racy ac power analyser for single phase
loads of up to 16 amps RMS.
Dual power cables allow the supply to the
load to be independent of the supply to the
instrument. The output to the load is via a
front panel mounted ‘standard’ mains con-
nector. A wide range of power connectors is
available including most national types.
The HA1600A can measure Watts, VA,
Volts rms, Volts peak, Amps rms, Amps
peak, Crest factors, THD, Power factor, Fre-
quency and Inrush current.
The large display can show multiple param-
eters simultaneously as well as graphical
representations of voltage and current
waveforms.
Dual 16 bit Analog to Digital converters con-
tinuously sample both voltage and current
and give a wide dynamic range. A fast Digi-
tal Signal Processor gives the performance
needed for continuous real-time analysis of
the data. Advanced algorithms yield accu-
rate results, using extended precision or
floating point arithmetic wherever neces-
sary.
HA1600A
u
Measures power, voltage, current, phase angle etc.
u
Tabular and histogram display of harmonics
u
Voltage and current waveform displays
u
Continuous analysis with real-time graphical update
u
Compliance quality measurements to EN61000-3-2/-3
u
Wide range of national power connectors available
u
Parallel printer and RS232 and USB interfaces
u
PC control and documentation software supplied
AC1000A
u
Provides an EN61000–3–2 compliant source
u
1000W power capability at 230V
u
Up to 4·4A rms load current and up to 10A peak currents
u
Comprehensive overload protection
u
Connection via standard national power connector
Compliance-quality
harmonics analyser
All electrical equipment sold within the EEC
must comply with legislation relating to the
harmonics content of the current waveform.
The HA1600A has been designed to make
these measurements both quick and simple.
It measures harmonics from the 1st to the
40th and updates the display in real time.
It is suitable for pre-compliance measure-
ments using a normal mains supply and is
capable of full compliance measurements
to EN61000-3-2 in conjunction with a suit-
able power source such as the AC1000A.
Support is provided for both the 2006 and
2000 editions of EN61000-3-2. Capabilities
include continuous monitoring of the supply
voltage, continuous automatic calculation of
harmonic limits, and timed test sequences
with analysis of fluctuating harmonics.
Optional low distortion
1kW power source
The AC1000A is a low cost pure power
source designed specifically for use with a
harmonics analyser such as the HA1600A.
The AC supply available at a standard wall
socket is usually distorted. This comes
about because of nonlinear loads (non–re-
sistive loads) on the AC supply such as
transformers, fluorescent lights,
switched–mode power supplies etc. The ef-
fect of this is to flatten off the top of the sine
wave causing significant distortion.
In a typical factory environment this distor-
tion is so significant that it is easily visible
using the HA1600A waveform display.
EN61000–3–2 requires that the source sup-
ply provides a pure voltage waveform to the
equipment under test. The harmonic cur-
rents can differ significantly when a pure
source is used, so for true compliance
measurements it is important that any test-
ing is performed with a device such as the
AC1000A.
Because of the large increase in the peak
currents that can result from having a pure
sinewave maims voltage supply, the
AC1000A is also very useful for stress test-
ing a wide variety of power supplies types
within electronic equipment.
Compact and portable, the AC1000A is
rated at 1000 V·A for 230 V operation at up
to 35°C ambient.
Maximum continuous rms current is 4.4A
with a peak current capability of 10A.
Overview
The HA1600A is a fast, easy to use mains
and harmonics analyser with a large and
high resolution graphical display, capable
of continuous real-time analysis.
The HA1600A is intended primarily as a
dedicated harmonics and flicker analyser
for compliance quality measurements,
but it can also be used as a general pur-
pose mains analyser.
The unit is available with range of power
connectors to suit different national stan-
dards.
A printer interface is included for record
keepinga/archiving, along with RS-232
and USB interfaces for PC connectivity.
The HA1600A is suitable for both the
product development environment, and
for production line test verification.
HA-PC Link Plus is Windows based
sofware supplied with the HA1600A.
It is intended to assist users in taking
routine compliance measurements and
archiving the results.
It can communicate with the instrument
through either an RS232 or a USB con-
nection.
The AC1000A is an innovative, low cost,
pure power source designed specifically
for use with a harmonics analyser such as
the TTi HA1600A.
It permitts compliance quality measure-
ments to EN61000–3–2 in situations
where the quality of the AC supply is poor
or variable, without the expense of a full
AC power source.
Compliance-quality
fluctuations & flicker meter
The HA1600A can operate as a compliance
quality flicker and fluctuations meter in con-
formance with EN61000-3-3 and
EN61000-4-15.
A current measurement method can be
used, as an alternative to voltage measure-
ment, thus eliminating the need for a refer-
ence impedance.
Flicker severity is measured in terms of Pst
and Plt using analysis periods as defined
within the standard.
Simultaneously full analysis of voltage vari-
ations is performed, including the calcula-
tion of the maximum value dmax, the
difference between steady states dc, and
the change characteristic d(t).
The HA1600A incorporates both RS232,
and USB interfaces for use with a PC, and a
Centronics parallel interface for direct con-
nection to a printer.
The firmware of the instrument is stored in
flash memory and can be updated via
RS232 or USB as the requirements of the
standards evolve.
Digital interfaces and PC software
HA-PC Link Plus software is supplied with
the instrument to assist users in taking rou-
tine compliance measurements and archiv-
ing the results.
Data updating is continuous, permitting
real-time viewing on the PC.
Harmonics can be displayed on the PC as
tabular reports or as graphical histo-
grams.
Voltage and current waveforms.
The mains voltage purity has been restored
using an AC1000A. Compare this with the
uncorrected mains voltage shown in the
instrument illustration.
Sections of the HA-PC Link Plus screen
HA1600A Power and Harmonics Analyser Harmonics analysis to EN61000-3-2
High speed compliance quality measurements Fluctuations & flicker measurement to EN61000-3-3
High performance power
analyser
The HA1600A is a high speed, high accu-
racy ac power analyser for single phase
loads of up to 16 amps RMS.
Dual power cables allow the supply to the
load to be independent of the supply to the
instrument. The output to the load is via a
front panel mounted ‘standard’ mains con-
nector. A wide range of power connectors is
available including most national types.
The HA1600A can measure Watts, VA,
Volts rms, Volts peak, Amps rms, Amps
peak, Crest factors, THD, Power factor, Fre-
quency and Inrush current.
The large display can show multiple param-
eters simultaneously as well as graphical
representations of voltage and current
waveforms.
Dual 16 bit Analog to Digital converters con-
tinuously sample both voltage and current
and give a wide dynamic range. A fast Digi-
tal Signal Processor gives the performance
needed for continuous real-time analysis of
the data. Advanced algorithms yield accu-
rate results, using extended precision or
floating point arithmetic wherever neces-
sary.
HA1600A
u
Measures power, voltage, current, phase angle etc.
u
Tabular and histogram display of harmonics
u
Voltage and current waveform displays
u
Continuous analysis with real-time graphical update
u
Compliance quality measurements to EN61000-3-2/-3
u
Wide range of national power connectors available
u
Parallel printer and RS232 and USB interfaces
u
PC control and documentation software supplied
AC1000A
u
Provides an EN61000–3–2 compliant source
u
1000W power capability at 230V
u
Up to 4·4A rms load current and up to 10A peak currents
u
Comprehensive overload protection
u
Connection via standard national power connector
Compliance-quality
harmonics analyser
All electrical equipment sold within the EEC
must comply with legislation relating to the
harmonics content of the current waveform.
The HA1600A has been designed to make
these measurements both quick and simple.
It measures harmonics from the 1st to the
40th and updates the display in real time.
It is suitable for pre-compliance measure-
ments using a normal mains supply and is
capable of full compliance measurements
to EN61000-3-2 in conjunction with a suit-
able power source such as the AC1000A.
Support is provided for both the 2006 and
2000 editions of EN61000-3-2. Capabilities
include continuous monitoring of the supply
voltage, continuous automatic calculation of
harmonic limits, and timed test sequences
with analysis of fluctuating harmonics.
Optional low distortion
1kW power source
The AC1000A is a low cost pure power
source designed specifically for use with a
harmonics analyser such as the HA1600A.
The AC supply available at a standard wall
socket is usually distorted. This comes
about because of nonlinear loads (non–re-
sistive loads) on the AC supply such as
transformers, fluorescent lights,
switched–mode power supplies etc. The ef-
fect of this is to flatten off the top of the sine
wave causing significant distortion.
In a typical factory environment this distor-
tion is so significant that it is easily visible
using the HA1600A waveform display.
EN61000–3–2 requires that the source sup-
ply provides a pure voltage waveform to the
equipment under test. The harmonic cur-
rents can differ significantly when a pure
source is used, so for true compliance
measurements it is important that any test-
ing is performed with a device such as the
AC1000A.
Because of the large increase in the peak
currents that can result from having a pure
sinewave maims voltage supply, the
AC1000A is also very useful for stress test-
ing a wide variety of power supplies types
within electronic equipment.
Compact and portable, the AC1000A is
rated at 1000 V·A for 230 V operation at up
to 35°C ambient.
Maximum continuous rms current is 4.4A
with a peak current capability of 10A.
Overview
The HA1600A is a fast, easy to use mains
and harmonics analyser with a large and
high resolution graphical display, capable
of continuous real-time analysis.
The HA1600A is intended primarily as a
dedicated harmonics and flicker analyser
for compliance quality measurements,
but it can also be used as a general pur-
pose mains analyser.
The unit is available with range of power
connectors to suit different national stan-
dards.
A printer interface is included for record
keepinga/archiving, along with RS-232
and USB interfaces for PC connectivity.
The HA1600A is suitable for both the
product development environment, and
for production line test verification.
HA-PC Link Plus is Windows based
sofware supplied with the HA1600A.
It is intended to assist users in taking
routine compliance measurements and
archiving the results.
It can communicate with the instrument
through either an RS232 or a USB con-
nection.
The AC1000A is an innovative, low cost,
pure power source designed specifically
for use with a harmonics analyser such as
the TTi HA1600A.
It permitts compliance quality measure-
ments to EN61000–3–2 in situations
where the quality of the AC supply is poor
or variable, without the expense of a full
AC power source.
Compliance-quality
fluctuations & flicker meter
The HA1600A can operate as a compliance
quality flicker and fluctuations meter in con-
formance with EN61000-3-3 and
EN61000-4-15.
A current measurement method can be
used, as an alternative to voltage measure-
ment, thus eliminating the need for a refer-
ence impedance.
Flicker severity is measured in terms of Pst
and Plt using analysis periods as defined
within the standard.
Simultaneously full analysis of voltage vari-
ations is performed, including the calcula-
tion of the maximum value dmax, the
difference between steady states dc, and
the change characteristic d(t).
The HA1600A incorporates both RS232,
and USB interfaces for use with a PC, and a
Centronics parallel interface for direct con-
nection to a printer.
The firmware of the instrument is stored in
flash memory and can be updated via
RS232 or USB as the requirements of the
standards evolve.
Digital interfaces and PC software
HA-PC Link Plus software is supplied with
the instrument to assist users in taking rou-
tine compliance measurements and archiv-
ing the results.
Data updating is continuous, permitting
real-time viewing on the PC.
Harmonics can be displayed on the PC as
tabular reports or as graphical histo-
grams.
Voltage and current waveforms.
The mains voltage purity has been restored
using an AC1000A. Compare this with the
uncorrected mains voltage shown in the
instrument illustration.
Sections of the HA-PC Link Plus screen
Technical Specifications
82100-1260 Iss. 2A
THURLBY THANDAR INSTRUMENTS
HA1600A
Harmonics, Flicker and Power Analyser
high speed and high accuracy power measurements
MAINS ANALYSER
Measurement Circuit: Single Phase with standard mains connector.
Current Rating: 16A rms continuous, or national connector rating if
lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Current Ranges: ±24mA pk to ±400A pk in fifteen 2:1 ranges.
Frequency Range: 43 - 67 Hz.
Shunt Resistance: 3mW.
Sampling Rate: 300 points per cycle.
Basic Accuracy: Better than 0.2% ±1mA, up to 16A.
Measured Parameters: Vrms, Vpk, Arms, Apk, Crest factors, THD, W, VA,
Power factor, Frequency, Inrush current.
Display Modes:
Tabular display of all parameters including latest and highest inrush cur-
rent. Waveform graph display of voltage and current with normal, max
hold, accumulate and multiple cycle display.
Monitor Outputs: Re-constructed Voltage and Current Signals.
HARMONICS ANALYSER
Measurements: 1st harmonic to 40th harmonic.
Measurement processing for both 2006 and 2000 editions of EN61000-3-2.
Continuous calculation, analysis and assessment of unfiltered, filtered, av-
erage, minimum and maximum current harmonic levels and limits. Continu-
ous measurement and assessment of supply waveform and harmonics.
Current Rating: 16A rms continuous, or national connector rating if
lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Current Ranges: ±24mA pk to ±400A pk in fifteen 2:1 ranges.
Frequency Range: 43 - 67 Hz.
Shunt Resistance: 3mW.
Transform Windows: Continuous 4, 10, 12 or 16 cycle Discrete Fourier
Transforms.
Basic Accuracy: Better than 5% of limit or 0.2% of selected range (which-
ever is the greater) ± 1mA.
Display Modes:
Display of load supply assessment for voltage, harmonics, crest limits and
frequency against requirements of EN61000-3-2.
Histogram or tabular display of supply voltage harmonics.
Histogram display of current harmonics with limits, Min. hold, Max. hold
and percentage of limit display options.
Tabular display of current harmonics showing present values, limits, aver-
age values, average as percent of limit, maximum values, maximum as
percent of limit and pass or fail assessment for each harmonic.
Test Control:
Untimed, manually timed or automatically timed tests; user-defined test
time.
Limits automatically determined from EN61000-3-2 for appropriate class;
Class C and Class D limits can be automatically calculated from power
measurements or from ratings declared by the user. Minimum and maxi-
mum power thresholds for limits can be changed by the user.
Facility for declaring supply voltages other than 230V and deriving appro-
priate limits. Facility for insetting test limits.
Report Printing:
Direct printer connection for hard-copy report with user-entered narrative,
supply voltage assessment and current harmonic analysis and assess-
ment.
VOLTAGE FLUCTUATIONS & FLICKER METER
Measurements: Voltage fluctuations dmax, dc, d(t) and flicker Pst and Plt
to EN61000-3-3 and EN61000-4-15.
Current Rating: 16A rms continuous, or national connector rating if
lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Fluctuation Range: 25% max. (relative to nominal voltage)
Flickermeter Range: Voltage change up to 20% (sinewave change) or 10%
(low repetition rate rectangular change) relative to AGC
level. Equivalent to 6400 pu on 8.8 Hz sinewave.
Designed and built in Europe by:
Thurlby Thandar Instruments Ltd.
Glebe Road, Huntingdon. Cambs. PE29 7DR United Kingdom
Tel: +44 (0)1480 412451 Fax: +44 (0)1480 450409
Email: info@aimtti.com Web: www.aimtti.com
optional low-distortion 1kW AC power source (AC1000A)
compliance quality harmonics analysis to EN61000-3-2
compliance quality flicker measurement to EN61000-3-3
Flickermeter AGC: Up to ± 5%.
Flickermeter Accuracy: Better than 5% for Pst range 0·7 to 10·0.
Frequency Range: 50 Hz (operates over 43 – 67 Hz).
Report Printing: Tabular listing of voltage variations, Pst classifier and Pst
in each Plt interval.
GENERAL
Display: 320 x 240 pixel backlit LCD.
Clock: Realtime clock for time/date stamping of Report data.
Interfaces: Parallel Printer, RS-232, USB.
Instrument Supply: 230V or 115V ±14%, 48 to 65Hz.
Operating Range: +5°C to 40°C, 20-80% RH.
Storage Range: –10°C to +60°C.
Dimensions: 357 x 132 x 235mm (WxHxD)
Weight: 4.4 kg
Safety: Complies with EN61010-1
EMC Compliance: Complies with EN61326-1
FREE FIRMWARE UPDATES
Changes to measurement methods required by occasional updates to the
EN61000-3-2 & EN61000-3-3 standards will generally require just an instrument
firmware update. So far, it has beeb possible to upgrade all HA1600A and
HA1600 models ever built to meet the latest requirements.
To upgrade firmware and to check what revisions of the standard are now sup-
ported, follow links from the Support page of the TTi web site.
HA-PC LINK PLUS SOFTWARE
HA-PC LINK PLUS is PC (Windows) software supplied with the HA1600A.
It can communicate with the instrument through either an RS232 or a USB con-
nection.
It is intended to assist users in taking routine compliance measurements and ar-
chiving the results.
The PC is used for configuration, display and data archiving only; all real time
data handling and measurement processing continues to be performed by the
Digital Signal Processor in the instrument. The performance of the PC does not
affect the accuracy of the measurement results, and so there is no need for the
either the PC or its software to be covered by a calibration certificate.
AC1000A LOW DISTORTION POWER SOURCE
Input Voltage: Factory built to 220V to 240V, 110V to115V or 100V.
Factory configure to 50Hz or 60Hz.
Installation Category II.
Supply Tolerances: Voltage ± 10%. Frequency ± 1%
Output Voltage: Tracks the amplitude of the fundamental of the input
voltage. A variable voltage input may be used to adjust
the output voltage to within the limits specified by
EN61000–3–2.
Output Distortion: Will meet the requirements of EN61000–3–2 for all
normal levels of input voltage distortion.
Output Current: Maximum continuous output current is 4·4A (10A peak).
Output Power: Maximum output power is input voltage x 4·4 VA
Input Connection: IEC connector; front panel switch.
Output Connection: U.K., Schuko, or other national outlet sockets. Load
power switch can be set to DIRECT or CORRECTED for
‘A–B’ comparisons.
Protection: Thermal trip automatically diverts load to a DIRECT con-
nection in the event of thermal overload.
Operating Range: +5°C to +35°C at full rated output; 20% to 80% RH
(non-condensing).
Storage Range: –40°C to +70°C
Environmental: Indoor use at altitudes to 2000m, Pollution Degree 2.
Safety: Complies with EN61010–1
EMC: Complies with EN31326-1
Size and Weight: 357 x 132 x 235mm mm (W x H x D); 5.5kg.
Thurlby Thandar Instruments Ltd. operates a policy of continuous development and
reserves the right to alter specifications without prior notice.
Thurlby Thandar Instruments Ltd.
Glebe Road, Huntingdon, Cambridgeshire PE29 7DR England (United Kingdom)
Tel: +44 (0)1480 412451 Fax: +44 (0)1480 450409
Email: info@aimtti.com Web: www.aimtti.com
Designed and built in Europe by:
Company name and product brands
Thurlby Thandar Instruments Ltd. (TTi) is one of Europe’s leading
manufacturers of test and measurement instruments.
Products have been sold under two brand names:
TTi and Aim.
In the future, however, the full product range will be branded Aim-TTi.
This changeover will be gradual and many products will continue to carry
the TTi or Aim brands for some time to come.
Web Addresses (URLs)
The preferred URL for obtaining information concerning Aim-TTi products
is:
www.aimtti.com (international customers)
Customers in the UK should use the URL:
www.aimtti.co.uk
Customers in the USA should use the URL:
www.aimtti.us
Note that previous URLs such as www.tti-test.com will continue to operate
for the time being.
Product Summary
Laboratory Power Supplies
Bench and system power supplies from 30 watts up to
1200 watts using linear, mixed-mode and PowerFlex
regulation technologies.
Waveform Generators
Analog and digital (DDS) function generators, true
arbitrary generators, arbitrary/function generators and
pulse generators.
Precision Measurement Instruments
Benchtop DMMs, frequency counters, component
measurement instruments (LCR), electronic dc loads,
current probes.
RF and EMC Test Equipment
Spectrum analyzers, signal generators, frequency counters,
power meters, emc measurement instruments.