RT 2000
Isolation characteristics
Vb Rated isolation voltage rms 1) 300 V
with IEC 61010-1 standards and following conditions:
- Reinforced isolation
- Over voltage category CAT III
- Pollution degree PD2
- Heterogeneous eld
Vd Rms voltage for AC isolation test 2), 50 Hz, 1 min 3.5 kV
Vw Impulse withstand voltage 1.2/50 µs 6.5 kV
Min
dCp Creepage distance 6 mm
dCI Clearance distance 6 mm
CTI Comparative Tracking Index (group I) 3) 600 V
Notes: 1) Between primary conductor and ground. If isolated cable is used for the
primary circuit, the voltage category could be improved according to the
primary cable insulation category
(please refer to the cable manufacturer’s indications)
2) Between primary (completely lling the hole) and secondary
3) Plastic parts.
Safety and warning notes
In order to guarantee safe operation of the transducer and to be able to make
proper use of all features and functions, please read these instructions thoroughly!
Safe operation can only be guaranteed if the transducer is used for the purpose
it has been designed for and within the limits of the technical specications.
Ensure you get up-to-date technical information that can be found in the latest
associated datasheet under www.lem.com.
Caution! Risk of danger
Ignoring the warnings can lead to serious injury and/or cause damage!
The electric measuring transducer may only be installed and put into
operation by qualied personnel that have received an appropriate training.
The corresponding national regulations shall be observed during
installation and operation of the transducer and any electrical conductor.
The transducer shall be used in electric/electronic equipment with respect
to applicable standards and safety requirements and in accordance with all
the related systems and components manufacturers’ operating instructions.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module may carry
hazardous live voltage (e.g. primary conductor). The user shall ensure
to take all measures necessary to protect against electrical shock. The
transducer is a build-in device containing conducting parts that shall not be
accessible after installation. A protective enclosure or additional insulation
barrier may be necessary. Installation and maintenance shall be done with
the main power supply disconnected except if there are no hazardous live
parts in or in close proximity to the system and if the applicable national
regulations are fully observed.
Safe and trouble-free operation of this transducer can only be guaranteed if transport,
storage and installation are carried out correctly and operation and maintenance are
carried out with care.