DM-II Plus Power Quality Recorder
Specifications, cont.
Current measurement (Using AM-FLEX 33)
Range Accuracy Resolution Protection against overloads
15 to 3000 A ±(1.5% of range) 0.1 A 600 V
Minimal Current measurable is equal to 1.5% of Clamp Full Scale
Power measurement (cos : 0.5c[positive] – 0.5i[negative])
Value Ranges Accuracy Resolution
Active power 0 – 999.9W ±(1.5% + 2 digit) 0.1W
1kW – 999.9kW ±(1.5% + 2 digit) 0.1kW
1MW – 999.9MW ±(1.5% + 2 digit) 0.1MW
Reactive power 0 – 999.9VAR ±(1.5% + 2 digit) 0.1VAR
1kVAR – 999.9kVAR ±(1.5% + 2 digit) 0.1kVAR
1MVAR – 999.9MVAR ±(1.5% + 2 digit) 0.1MVAR
Apparent power 0 – 999.9VA ±(1.5% + 2 digit) 0.1VA
1kVA – 999.9kVA ±(1.5% + 2 digit) 0.1kVA
1MVA – 999.9MVA ±(1.5% + 2 digit) 0.1MVA
Active energy 0 – 999.9Wh ±(1.5% + 2 digit) 0.1Wh
1kWh – 999.9kWh ±(1.5% + 2 digit) 0.1kWh
1MWh – 999.9MWh ±(1.5% + 2 digit) 0.1MWh
Reactive energy 0 – 999.9VARh ±(1.5% + 2 digit) 0.1VARh
1kVARh – 999.9kVARh ±(1.5% + 2 digit) 0.1kVARh
1MVARh – 999.9MVARh ±(1.5% + 2 digit) 0.1MVARh
Cos measurement
Cos Resolution Accuracy (expressed in degrees)
0 to 0.20 0.01 0.6
0.21 to 0.50 0.01 0.7
0.51 to 0.80 0.01 1
Measurement of Harmonics
Voltage
Range Accuracy Resolution
DC – 25h ±(5.0% + 2 digit) 0.1V
26h – 33h ±(10.0% + 2 digit) 0.1V
34h – 49h ±(15.0% + 2 digit) 0.1V
The voltage harmonics will be null under the following threshold:
- DC: if <1V or <2% of 1st harmonic
- 1st harmonic: if <2V
- 2nd to 49th: if <1V or <2% 1st harmonic
Current
Range Accuracy Resolution
DC – 25h ±(5.0% + 2 digit) 0.1A
26h – 33h ±(10.0% + 2 digit) 0.1A
34h – 49h ±(15.0% + 2 digit) 0.1A
The current harmonics will be null under the following threshold:
- DC: if <2% of 1st harmonic or < 0,2% of clamp full scale
- 1st harmonic: if < 0.2% of clamp full scale
- 2nd to 49th: if<2% 1st harmonic or < 0.2% of clamp full scale
Setting the FLEX option the DC component will be ignored.
Frequency Measurement
Instrument set to 50Hz
Range Resolution Accuracy
47 to 53 0.1Hz ±(1.0% + 1 digit)
Instrument set to 60Hz
Range Resolution Accuracy
57 to 63.6 0.1Hz ±(1.0% + 1 digit)