https://www.phoenixcontact.com/us/products/2904960
05/18/2015Page1/6
Repeater power supply-MACX PL-EX-RPSSI-2I-SP-2904960
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Ex i measuring transducer power supply and input signal conditioner, HART. Transfers supplied or active 4 - 20
mA electrically isolated signals from the Ex area to two loads in the safe area. 4-way electrical isolation, PLd,
push-in technology.
The figure shows a version with a
screw connection
Product Features
Key commercial data
Packing unit 1 pc
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 12.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
https://www.phoenixcontact.com/us/products/2904960
05/18/2015Page2/6
Repeater power supply-MACX PL-EX-RPSSI-2I-SP-2904960
Technical data
Ambient conditions
Degree of protection IP20
Input data
Signal input Repeater power supply operation
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (20mA)
> 15.1 V (23mA)
Signal input Signal conditioner operation
Current input signal 4 mA ... 20 mA
Voltage drop approx. 3.9 V
Output data
Signal output Repeater power supply operation
Current output signal 4 mA ... 20 mA (active)
Load/output load current output < 450 Ω (20mA)
< 380 Ω (23mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Signal output Signal conditioner operation
Current output signal 4 mA ... 20 mA (active)
Load/output load current output < 450 Ω (20mA)
< 380 Ω (23mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Power supply
Designation Repeater power supply operation
Supply voltage range 19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
Max. current consumption < 75 mA (24VDC / 20mA)
Power consumption < 1.45 W (24 V DC/ 20 mA)
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
https://www.phoenixcontact.com/us/products/2904960
05/18/2015Page3/6
Repeater power supply-MACX PL-EX-RPSSI-2I-SP-2904960
Technical data
Connection data
Conductor cross section AWG max. 16
Stripping length 8 mm
Connection method Push-in connection
General
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 600 µs (for 4 mA ... 20 mA step)
Status display Green LED (PWR supply voltage)
Inflammability class according to UL 94 V0
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Housing material PA 66-FR
Color yellow
Designation Input/output/power supply
Electrical isolation 300 Vrms (Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output 1/output 2
Electrical isolation 1.5 kV AC (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326
ATEX  II (1) G [Ex ia Ga] IIC/IIB
 II (1) D [Ex ia Da] IIIC
 II 3 (1)G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx [Ex ia Ga] IIC/IIB
[Ex ia Da]
Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA / Canada UL 61010
Class I Div 2; IS for Class I, II, III Div 1
Data communication (bypass)
HART function Yes
Protocols supported HART
Safety data
https://www.phoenixcontact.com/us/products/2904960
05/18/2015Page4/6
Repeater power supply-MACX PL-EX-RPSSI-2I-SP-2904960
Technical data
Safety data
Operation Repeater power supply operation
Max. output voltage Uo25.2 V
Max. output current Io93 mA
Max. output power Po587 mW
Group IIC
Max. external inductivity Lo2 mH
Max. external capacity Co107 nF
Group IIB
Max. external inductivity Lo4 mH
Max. external capacity Co820 nF
Safety-related maximum voltage Um253 V AC (125 V DC)
Operation Signal conditioner operation
Input voltage Ui≤ 30 V
Input current Ii≤ 150 mA
Max. internal inductance Linegligible
Max. internal capacitance Cinegligible
Classifications
eCl@ss
eCl@ss 4.0 27210120
eCl@ss 4.1 27210120
eCl@ss 5.0 27210120
eCl@ss 5.1 27210120
eCl@ss 6.0 27210120
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
ETIM
ETIM 2.0 EC001485
ETIM 3.0 EC001485
ETIM 4.0 EC001485
ETIM 5.0 EC002653
UNSPSC
UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
https://www.phoenixcontact.com/us/products/2904960
05/18/2015Page5/6
Repeater power supply-MACX PL-EX-RPSSI-2I-SP-2904960
Classifications
UNSPSC
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Approvals
Approvals
Approvals
UL Listed / cUL Listed / GL / cULus Listed
Ex Approvals
IECEx / ATEX / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
GL
cULus Listed
Drawings
https://www.phoenixcontact.com/us/products/2904960
05/18/2015Page6/6
Repeater power supply-MACX PL-EX-RPSSI-2I-SP-2904960
Block diagram
Zone 2
Div. 2
Sensor / Field
or
4.2
5.2
4.1
5.1
Zone 0,1,2
Zone 20,21,22
Div. 1,2
4.2
5.2
4.1
5.1
3.2
3.1
2.2
2.1
1.2
1.1
GND
OUT 1
OUT 2
+24V
GND +24V
Power
+
+
-
-
IN OUT
PLC / DCS
3.2
3.1 +
-
2.2
2.1 +
-
passive
passive
AI
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com