https://www.phoenixcontact.com/us/products/2904960 Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Ex i measuring transducer power supply and input signal conditioner, HART. Transfers supplied or active 4 - 20 mA electrically isolated signals from the Ex area to two loads in the safe area. 4-way electrical isolation, PLd, push-in technology. The figure shows a version with a screw connection Product Features Key commercial data Packing unit 1 pc Custom tariff number 85437090 Country of origin Germany Technical data Note Utilization restriction EMC: class A product, see manufacturer's declaration in the download area Dimensions Width 12.5 mm Height 99 mm Depth 114.5 mm Ambient conditions Ambient temperature (operation) -20 C ... 60 C (Any mounting position) Ambient temperature (storage/transport) -40 C ... 80 C Maximum altitude 2000 m Permissible humidity (operation) 10 % ... 95 % (non-condensing) Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations. 05/18/2015 Page 1 / 6 https://www.phoenixcontact.com/us/products/2904960 Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960 Technical data Ambient conditions Degree of protection IP20 Input data Signal input Repeater power supply operation Current input signal 4 mA ... 20 mA Transmitter supply voltage > 16 V (20 mA) > 15.1 V (23 mA) Signal input Signal conditioner operation Current input signal 4 mA ... 20 mA Voltage drop approx. 3.9 V Output data Signal output Repeater power supply operation Current output signal 4 mA ... 20 mA (active) Load/output load current output < 450 (20 mA) < 380 (23 mA) Output ripple < 20 mVrms Output behavior in the event of an error 0 mA (Cable break in the input) 23 mA (Cable short-circuit in the input) Signal output Signal conditioner operation Current output signal 4 mA ... 20 mA (active) Load/output load current output < 450 (20 mA) < 380 (23 mA) Output ripple < 20 mVrms Output behavior in the event of an error 0 mA (Cable break in the input) 0 mA (Cable short-circuit in the input) Power supply Designation Repeater power supply operation Supply voltage range 19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%)) Max. current consumption < 75 mA (24 V DC / 20 mA) Power consumption < 1.45 W (24 V DC/ 20 mA) Connection data Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 1.5 mm Conductor cross section flexible min. 0.2 mm Conductor cross section flexible max. 1.5 mm Conductor cross section AWG min. 24 05/18/2015 Page 2 / 6 https://www.phoenixcontact.com/us/products/2904960 Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960 Technical data Connection data Conductor cross section AWG max. 16 Stripping length 8 mm Connection method Push-in connection General Maximum transmission error < 0.1 % (of final value) Transmission error, typical < 0.05 % (of final value) Maximum temperature coefficient < 0.01 %/K Step response (10-90%) < 600 s (for 4 mA ... 20 mA step) Status display Green LED (PWR supply voltage) Inflammability class according to UL 94 V0 Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC Housing material PA 66-FR Color yellow Designation Input/output/power supply Electrical isolation 300 Vrms (Rated insulation voltage (surge voltage category II; pollution degree 2, safe isolation as per EN 61010-1)) 2.5 kV (50 Hz, 1 min., test voltage) Designation Input/output Electrical isolation 375 V (Peak value in accordance with EN 60079-11) Designation Input/power supply Electrical isolation 375 V (Peak value in accordance with EN 60079-11) Designation Output 1/output 2 Electrical isolation 1.5 kV AC (50 Hz, 1 min., test voltage) Conformance CE-compliant, additionally EN 61326 ATEX II (1) G [Ex ia Ga] IIC/IIB II (1) D [Ex ia Da] IIIC II 3 (1)G Ex nA [ia Ga] IIC/IIB T4 Gc IECEx [Ex ia Ga] IIC/IIB [Ex ia Da] Ex nA [ia Ga] IIC/IIB T4 Gc UL, USA / Canada UL 61010 Class I Div 2; IS for Class I, II, III Div 1 Data communication (bypass) HART function Yes Protocols supported HART Safety data 05/18/2015 Page 3 / 6 https://www.phoenixcontact.com/us/products/2904960 Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960 Technical data Safety data Operation Repeater power supply operation Max. output voltage Uo 25.2 V Max. output current Io 93 mA Max. output power Po 587 mW Group IIC Max. external inductivity Lo 2 mH Max. external capacity Co 107 nF Group IIB Max. external inductivity Lo 4 mH Max. external capacity Co 820 nF Safety-related maximum voltage Um 253 V AC (125 V DC) Operation Signal conditioner operation Input voltage Ui 30 V Input current Ii 150 mA Max. internal inductance Li negligible Max. internal capacitance Ci negligible Classifications eCl@ss eCl@ss 4.0 27210120 eCl@ss 4.1 27210120 eCl@ss 5.0 27210120 eCl@ss 5.1 27210120 eCl@ss 6.0 27210120 eCl@ss 7.0 27210120 eCl@ss 8.0 27210120 ETIM ETIM 2.0 EC001485 ETIM 3.0 EC001485 ETIM 4.0 EC001485 ETIM 5.0 EC002653 UNSPSC UNSPSC 6.01 30211506 UNSPSC 7.0901 39121008 05/18/2015 Page 4 / 6 https://www.phoenixcontact.com/us/products/2904960 Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960 Classifications UNSPSC UNSPSC 11 39121008 UNSPSC 12.01 39121008 UNSPSC 13.2 39121008 Approvals Approvals Approvals UL Listed / cUL Listed / GL / cULus Listed Ex Approvals IECEx / ATEX / UL Listed / cUL Listed / cULus Listed Approvals submitted Approval details UL Listed cUL Listed GL cULus Listed Drawings 05/18/2015 Page 5 / 6 https://www.phoenixcontact.com/us/products/2904960 Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960 Block diagram OUT IN Sensor / Field PLC / DCS AI passive 4.2 - 4.2 4.1 + 3.2 3.2 OUT 1 4.1 3.1 or 3.1 + 2.2 passive OUT 2 2.1 5.2 - 5.2 5.1 + GND 5.1 +24V 1.2 2.2 2.1 + 1.1 Power GND +24V Zone 0,1,2 Zone 20,21,22 Zone 2 Div. 1,2 Div. 2 Phoenix Contact 2015 (c) - all rights reserved http://www.phoenixcontact.com 05/18/2015 Page 6 / 6