https://www.phoenixcontact.com/us/products/2688459
04/21/2021Page4/11
Bus coupler-AXL F BK ETH-2688459
Technical data
Axioline potentials
Designation AxiolineF local bus supply (UBus)
Supply voltage 5 VDC (via bus base module)
Power supply unit max. 2 A (up to HW 04)
max. 2.5 A (as of HW 05)
Electrical isolation
Test section Ethernet interface 1 / Ethernet interface 2 1500 VAC 50 Hz 1 min.
Ethernet interface 1 / 24 V communications voltage (UL) feed-in 1500 VAC
50 Hz 1 min.
Ethernet interface 2 / 24 V communications voltage (UL) feed-in 1500 VAC
50 Hz 1 min.
Ethernet interface 1 / functional ground 1500 VAC 50 Hz 1 min.
Ethernet interface 2 / functional ground 1500 VAC 50 Hz 1 min.
24 V communications voltage (UL) feed-in / functional ground 500 VAC 50
Hz 1 min.
Standards and Regulations
Immunity to ESD
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B, 6 kV contact
discharge, 8 kV air discharge
Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN61000-4-3/IEC61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Immunity to surge
Noise immunity test in accordance with EN 61000-6-2 Transient
overvoltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B, DC supply
lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield:
±1 kV
Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN61000-4-6/IEC61000-4-6 Criterion A, Test voltage 10 V
Interference emission Noise emission test according to EN 61000-6-3 Class B
Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Protection class III (IEC61140, EN61140, VDE0140-1)
Overvoltage category II (IEC60664-1, EN60664-1)
Drawings