Maximum leakage current each Line to Ground:
@ 120 VAC 60 Hz: 1.62 mA
@ 250 VAC 50 Hz: 2.82 mA
Hipot rating (one minute):
Line to Ground: 1500 VAC
Line to Line: 1450 VDC
Rated Voltage (max):
Phase to Phase: 440 VAC
Phase to Ground: 250 VAC
Operating Frequency: 50/60 Hz
Rated Current: 16 to 100A*
Operating Ambient Temperature Range
(at rated current Ir): -10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io= Ir(85-Ta)/45
• For 3-phase, four wire, WYE applications
• Cost-effective, universal 3-phase filters
• Good attenuation over the complete frequency
range of 10kHz to 30MHz
• Two different mounting styles available
Ordering Information
36 AYA 6 A
Suffix
A – Flange Mounted
(for threaded bolt style only)
Omit for bulkhead mount
or for Terminal Blocks
(flange mount only)
Input / Output Style
6 – Threaded bolt
10 – Terminal block
(flange mount only)
AYA Series
Current Rating
16, 25, 36, 50, 63 or 100A
Specifications
UL Recognized*
25AYA6A
Available Part Numbers
Flange Mount Bulkhead Mount
16AYA6A 16AYA6
16AYA10 25AYA6
25AYA6A 36AYA6
36AYA6A 50AYA6
36AYA10
50AYA6A
63AYA6A
63AYA10
100AYA6A
3-phase WYE RFI Power Line Filters
AYA Series
104
AYA Series
Dimensions are in inches and millimeters unless otherwise specified. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Specifications subject to change.
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
For email, phone or live chat, please go to
te.com/help
corcom.com
*UL Approvals for all models except:
16AYA10, 36AYA10, 63AYA10, 63AYA6, 63AYA6A and 100AYA6A