Tyco Electronics Corporation
300 Constitutional Drive
Menlo Park, CA 94025 USA
No: C-6114
Rev: A
Date: December 17, 1999
Page: 21 of 23
If this document is printed it becomes uncontrolled. Check for the latest revision
4.5.16 Random Vibration (see 3.6.14). Terminated, mated connector assemblies shall be
tested in accordance with MIL-STD-1344, Method 2005, Test Condition V, Letter E.
Connectors shall be panel mounted by normal means, with at least 8 inches (200 mm)
of wire unsupported behind each connector. Specimens shall be subjected to vibration
for 8 hours in each major axis for a total of 24 hours. Shield grounding accessories
shall have a minimum of 4 ground circuit wires independently monitored for
discontinuities.
4.5.17 Mechanical Shock (see 3.6.15). Terminated, mated connectors shall be tested in
accordance with MIL-STD-1344, Method 2004, Test Condition A. The connectors
shall be panel mounted by normal means, with at least 8 inches (200 mm) of wire
unsupported behind each connector. Shield grounding accessories shall have a
minimum of 4 ground circuit wires independently monitored for discontinuities.
4.5.18 Thermal Cycling (see 3.6.16). Mated connector assemblies shall be tested in
accordance MIL-STD-202, Method 107, Test Condition B.
4.5.19 Temperature Life (see 3.6.17). Terminated, mated connector assemblies shall be tested
in accordance with MIL-STD-1344, Method 1005, for 1000 hours at 125oC, using an
air-circulating oven. Contacts shall not be wired in series or connected to an electrical
load. Leads shall be brought out through a suitable port so that electrical measurements
can be taken. After 1000 hours and while connectors are still at the maximum rated
temperature and mated, the insulation resistance shall be measured in accordance with
4.5.3.
4.5.20 Humidity (see 3.6.18). Terminated, mated connector assemblies shall be tested in
accordance with MIL-STD-1344, Method 1002, Type II. Polarization voltage is not
required. Step 7 (a) shall be performed during the last cycle. After the end of the last
cycle the connector assemblies shall be removed form the humidity chamber and placed
in ambient conditions. Insulation resistance measurements shall be made within 1 to 2
hours and again after 24 hours.
4.5.21 Seal Leakage (see 3.6.19). Terminated, mated connectors shall be tested in accordance
with the seal leakage procedure specified in ARINC Specification 600 Attachment 19.
4.5.22 Polarization Lockout (see 3.6.20) Connector assemblies shall be prepared with one
side of the shells having compatible keying pins and the other side having keying pins
which completely interfere with each other. The mating hardware on the side of the
connector with compatible keying pins shall be engaged. The force required to
override the keying pins shall be recorded. The applied force shall be limited to 100 lb.
The test shall then be repeated with the interfering keying pins at right angles to each
other forming a 50% interference.