Specifications are subject to change without notice 1
• Universal AC input full range
• Installation on DIN rail 7.5 or 15mm
• Short circuit protection
• Overload protection
• Class 2 output
• High efficiency
• LED indicator for DC power ON
• Power Ok output
• CE, TUV approved and cULus Listed
Product Description
The Switching power
supplies SPD series are
specially designed to be
used in all automation
application where the
installation is on a DIN rail
and compact dimensions
and performance are a must.
Switching Power Supply
Type SPD 60W
DIN rail mounting
Optional Features
Approvals
Description code
Spring connectors B
Line regulation ± 0.5%
Load regulation ± 0.5%
Minimum load 0
Turn on time 1.0s max
(full resistive load)
Transient recovery time 300µs
Ripple and noise 50mVpp
Ouput Voltage accuracy ±2%
Temperature coefficient ± 0.02%/°C
Hold up Time Vi = 115Vac 20ms
Hold up time Vi = 230Vac 30ms
Voltage fall time (I0nom) 150ms max
Voltage rise time at 150ms max
full resistive load
Output data
Rated input voltage 100 - 240
Voltage range
AC 85 - 264 Vac
DC 90 - 375 Vdc
Frequency range 47- 63 Hz
Inrush current
Vi= 115Vac 30A
Vi= 230Vac 60A
Input data
Model
Mounting ( D = Din rail )
Output voltage
Output power
Input Type
Optional features
Input type: 1= single phase
Ordering Key SP D 24 60 1 B
Model
SPD05
SPD12
SPD24
SPD48
Output
Voltage (VDC)
5
12
24
48
Output
Current (A)
10
5
2.5
1.25
Output
Power (W)
50
60
60
60
Min. VDC
5
12
24
48
Max. VDC
5.5
14
28
55
DC on LED
(VDC Min.)
4
9.6
19.2
37
Typical
Efficiency
79%
86%
89%
89%
Voltage Trim Range
Output performances
2Specifications are subject to change without notice
Switching Power Supply
Type SPD 60W
DIN rail mounting
Overload 110 – 150%
Input Fuse T2A/250Vac internal*
Output Short Circuit Fold forward
Power ready output (only SPD 24)
On threshold 20V ± 1V
Off threshold 19.2V ± 1V
Over voltage protection VDC
Min. Max.
SPD5 6 6.8
SPD12 15 16.5
SPD24 30 33
SPD48 60 66
Controls and Protections
Ambient temperature -10°C to 71°C
Derating (>60°C to +71°C) 2.5%/°C
Ambient humidity 20 ~ 90%RH
Storage -25°C to +85°C
Protection degree IP20
Cooling Free air convection
MTBF (MIL-HDBK-217F) 500.000h
Case material Plastic: PC, UL94-V0
Dimensions L x W x D 90 x 40.5 x 115
Weight 360g
General data (@ nominal line, full load, 25°C )
Insulation voltage I / O 3.000Vac min
Insulation resistance 100Mohm min
UL / cUL UL508 listed, UL1950,
UL1310 Class 2
(5V without class 2)
Recognised
TUV EN60950
CE EN61000-6-3 - EN55022
Class B
EN61000-3-2 - EN61000-3-3
EN61000-6-2 - EN550241
EN61000-4-2 - EN61000-4-3
EN61000-4-4 - EN61000-4-5
EN61000-4-6 - EN61000-4-8
EN61000-4-11
Norms and Standards
* fuse not replaceable by user
Block diagrams
L
N
Y
Vo +
Vo -
Vout
ADJ.
DCON
(Green LED)
RDY
(Open Collector)
Fuse
Line
Filter
Inrush Current
Limiter and
Rectifier
Switching
Device Rectifier
PWM
Controller
Current
Detection
Opto -
isolation
Reference &
Error Amp.
Output Level
Detection
Pin No. Designation Description
1 RDY DC OK, output for relay (only on SPD 24)
3+ Positive output terminal
4+ Positive output terminal
5- Negative output terminal
6- Negative output terminal
7 GND Ground terminal to minimise High frequency emissions
8L Phase input ( no polarity with DC input )
9N Neutral input ( no polarity with DC input )
Vout ADJ. Trimmer for fine output voltage adjustment
DC ON DC output ready LED
Pin assignement and front controls
Specifications are subject to change without notice 3
Switching Power Supply
Type SPD 60W
DIN rail mounting
Output Rdy Wiring diagram
SPD
Rdy
- Vout
relay
Relay connection diagram
SPD
Rdy
- Vout
5V signal
5V
2k2 0.5W
RL> 700ohm
5v1 0.3W
Derating Diagram
Power out (%)
Temperature (°C)
100
90
80
70
60
50
40
30
20
10
0
-10 0 5 10 55 60 65 70 75 80
Mechanical Drawings
115 (4.53)
40.5 (1.59)
90.0 (3.60)
6 8
5 1
DCON
- - + + N.C.
Ventilation and cooling Normal convection
All sides 25mm free space
for cooling is recommended
Connector size range Solid: 0.2 – 2mm2
(AWG24-14)
(use copper conductors only)
Installation
24
24