instabus EIB
Technical Product Information
September 2001
Shutter Switch GE 521 5WG1 521-4AB02
1 x 230 V AC / 6A, 42 x 28 mm
Technical Specifications
Power supply
Technical Manual GE 521, 4 pages Siemens AG
via bus cable
Outputs
• number: 1 output channel (volt free contacts)
• rated voltage: AC 230 V, 47 ... 63 Hz
• rated current: 6 A resistive load
• switching current at AC 230 V
- 0,01 ... 6 A resistive load
- tubular motors with auxiliary phase capacitor ≤ 14
µF, max. power 500 VA at 20000 load switching
cycles
(UP-DOWN-STOP) respectively
max. 750 VA at 12000 load switching cycles
- total maximum load at cosϕ = 0,4; 750 VA
• switching current at DC 24 V:
6 A resistive load,
4 A inductive load (L/R = 7 ms)
• switching characteristic: set in parameter list accord-
ing to application program
• switching refresh intervals: min. 150 ms
Control elements
1 learning button:
for switching between normal operating mode and ad-
dressing mode
Display elements
1 red LED:
for monitoring bus voltage and displaying mode, se-
lected with the learning button
Connections
• load circuit, physical:
strip insulation for 9 ... 10 mm
permissible conductor types/cross sections:
- 0,5 ... 2,5 mm² single core or flexible conductor,
8 mm ultrasonically compacted
- 0,5 ... 2,5 mm² flexible conductor with terminal pin,
crimped on gas tight
- 0,5 ... 1,5 mm² flexible conductor with connector
sleeve
- 1,0 and 1,5 mm² plain flexible conductor
• load circuit, electrical:
- plain flexible conductor, min. 1 mm²:
current carrying capacity max. 6 A
- all other conductors, min. 1,5 mm²:
current carrying capacity max. 10 A
- The load circuits must be protected with a 10 A
miniature circuit breaker A or B characteristic.
V WARNING
When looping through the L-conductor (connection
blocks 3 and 4), take care that the maximum connec-
tion current of 10 A (as governed by the maximum
permissible printed conductor load) is not exceeded!
• bus line, screwless bus connection block:
∅ 0,6 ... 0,8 mm single core
Physical specifications
• housing: plastic
• dimensions (W x H x L): 42 x 28 x 274,5 mm
• weight: approx. 190 g
• fire load: approx. 3900 kJ ± 10 %
• installation: screw-mount into devices
Electrical safety
• fouling class (according to IEC 664-1): 2
• protection (according to EN 60529): IP 20
• overvoltage class (according to IEC 664-1): III
• bus: safety extra low voltage SELV DC 24 V
• relay with µ-contact
• the device complies with EN 50090-2-2 and EN
60669-2-1
Reliability
rate of failure: 522 fit at 40 °C
Electromagnetic compatibility
complies with
EN 50081-1, EN 50082-2 and EN 50090-2-2
Environmental specifications
• climatic conditions: EN 50090-2-2
• ambient temperature operating: - 5 ... + 45 °C
• ambient temperature non-op.: - 25 ... + 70 ° C
• relative humidity (non-condensing): 5 % to 93 %
Certification
EIB certificate
CE norm
complies with the EMC regulations (residential and
functional buildings), and low voltage regulations
Automation and Drives Group
Update: http://www.siemens.de/installationstechnik Siemens AG 2001 Electrical Installation Technology
Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg