CSM_H5S_DS_E_9_2
1
Digital Time Switch
H5S
Easier, More Convenient Time Switches, with
New 4-circuit Output and Yearly Models in
Addition to 2-circuit Weekly Models
Independent Day Keys provide easier operation.
Temporary holiday setting function makes it easy to turn OFF
output for holidays and non-operating days.
Settings can be made even with the Time Switch turned OFF.
Test mode enables easy program checking.
Complies with EMC Directives, UL/CSA, and other safety
standards.
Includes summer time (DST) adjustment.
Yearly models also offer automatic switching to DST.
Set value can be changed both upward and downward for
speedier setting.
Integrated temperature compensation circuit helps keep
accurate time over a wide temperature range. (See note 1.)
Includes time counter and total counter functions with alarm
indicator. (See note 2.)
Bank function allows program switching by an external input.
(See note 3.)
New 4-circuit output models with a compact, 72 × 72-mm DIN
size added to the series.
Note: 1. Available only on yearly models.
2. Available only on 2-circuit models.
3. Available only on weekly models.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Features
Easier and More Convenient to Use
Simple Setting
Convenient Functions
Time Counter/Total Counter Functions (See note.)
This function makes it possible to monitor the total time that a load
has been applied, or the total number of operating cycles. It allows
the Time Switch to be used for managing maintenance.
Time Adjustment Function (See note.)
The time can be set to 00 min 00 s by using an external input. The
times on multiple Time Switches can also be easily synchronized.
Note: Equipped on 2-circuit models.
Independent Day Keys make setting easy.
Up/down set value changing
for speedy setting.
Temporary holidays
(non-operating days)
are also easy to set.
Weekly models: Specify the day.
Yearly models: Specify the date.
With alarm indicator
Shows total lamp ON time
Synchronized!
Master SlaveSlave
H5S
2
More Applications on New Series Models
Automatic Program Switching by Seasons
The yearly operation can be set to automatically change the weekly
program depending on the season. (See note.)
Note: Up to four seasons can be set for 4-circuit models, and up to
two seasons for 2-circuit models.
Temperature Compensation Circuit Maintains
Accurate Time
A temperature compensation circuit is provided in the yearly models
to maintain accurate time keeping even when the ambient
temperature varies greatly. This ensures precise operation with
minimal time lags all year round, regardless of temperature changes.
Space-saving, Economical 4-circuit Models Added
to the Series
The new 4-circuit models are 72 × 72-mm DIN size. Their space-
saving size allows use in more applications.
Model Number Structure
Model Number Legend
Note: This model number legend includes combinations that are not available. Please check the “List of Models” for availability.
1. Control cycle
W: Weekly
Y: Yearly
2. Mounting method
None: Flush mounting
F: Surface mounting/track mounting
3. Panel language
B: English
A: Japanese
4. Number of outputs
2: 2 circuits
4: 4 circuits
5. Supply voltage
None: 100 to 240 VAC
D: 24 VDC
6. Time accuracy
None: Standard
X: With temperature compensation
Yearly Models
Spring Summer Autumn Winter
Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb
Season
(See note 2.)
Spring
17:30 ON
21:00 OFF
Summer
Program
example
19:00 ON
22:00 OFF
Winter
Autumn
18:00 ON
21:00 OFF
17:00 ON
21:00 OFF
4-circuit Models
Control all four
floors with a
single unit.
12345 6
H5S- @@@@@ - @
H5S
3
Ordering Information
List of Models
Accessories (Order Separately)
Specifications
Ratings
Note: 1. Do not use inverter output as a power supply. For details, refer to Precautions for Safe Use, item 24, on page 12.
2. The capacity is 15 A per circuit, but derating of the total current for two circuits is required as shown below depending on the ambient
temperature.
Control cycle Number of outputs Mounting method Supply voltage Models
Weekly 2 circuits Flush mounting 100 to 240 VAC H5S-WB2
24 VDC H5S-WB2D
Surface mounting/
track mounting
100 to 240 VAC H5S-WFB2
24 VDC H5S-WFB2D
Yearly 2 circuits Flush mounting 100 to 240 VAC H5S-YB2-X
24 VDC H5S-YB2D-X
Surface mounting/
track mounting
100 to 240 VAC H5S-YFB2-X
24 VDC H5S-YFB2D-X
4 circuits Flush mounting 100 to 240 VAC H5S-YB4-X
24 VDC H5S-YB4D-X
Surface mounting/
track mounting
100 to 240 VAC H5S-YFB4-X
24 VDC H5S-YFB4D-X
Name Model
Protective Cover Y92A-72C
Track Mounting Base Y92F-90
Large Terminal Cover (in pairs) Y92A-72H
Item Weekly 2-circuit Models
(H5S-W@2)
Yearly 2-circuit Models
(H5S-Y@2)
Yearly 4-circuit Models
(H5S-Y@4)
Rated supply voltage 100 to 240 VAC (50/60 Hz), 24 VDC (See note 1.)
Operating voltage range AC: 85% to 110% rated supply voltage
DC: 85% to 120% rated supply voltage
Power consumption Approx. 2.9 VA at 264 VAC 60 Hz
Approx. 0.8 W at 28.8 VDC
Approx. 3.2 VA at 264 VAC 60 Hz
Approx. 0.9 W at 28.8 VDC
Approx. 3.5 VA at 264 VAC 60 Hz
Approx. 1.0 W at 28.8 VDC
Control
outputs
Number of circuits SPST-NO × 2 circuits SPST-NO × 4 circuits
Circuits Power supply circuit and other (no-voltage) circuit
Capacity Resistive load
(cosφ = 1)
15 A at 250 VAC (See note 2.) 3 A at 250 VAC
Inductive load 10 A at 250 VAC (cosφ = 0.7) 2 A at 250 VAC (cosφ = 0.4)
Ambient operating temperature 10 to 55°C (with no icing or condensation)
Ambient operating humidity 25 to 85%
Storage temperature 25 to 65°C (with no icing or condensation)
Case color Light gray (Munsell 5Y7/1)
40
30
20
10
0
10 0 20 40 50 55 60 80
Ambient temperature (°C)
Total current (A)
H5S
4
Characteristics
Note: 1. The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to temperature change is
±0.01% ±0.05 s max.
2. The time given for memory protection is the calculated time of when power is not being supplied (including during storage) at an ambient
temperature of 25°C. The timer functions and set program are backed up by a lithium battery that is built into the Time Switch. These
will be lost if the life of the battery expires. If the lithium battery is replaced (if the PCB is replaced), the stored contents will also be lost.
Item Weekly 2-circuit Models
(H5S-W@2)
Yearly 2-circuit Models
(H5S-Y@2)
Yearly 4-circuit Models
(H5S-Y@4)
Accuracy of operating
time
±0.01%±0.05 s max. (See note 1.)
The ±0.01% value applies to the set time interval.
Setting error
Influence of voltage
Influence of temperature
Cyclic error ±15 s per month (at 25°C) ±15 s per month (at 10 to 45°C), ±20 s per month (at 45 to 55°C)
Memory protection Continuous use: 5 years min. (at 25°C) (See note 2.)
Insulation resistance 100 MΩ min. (between current-carrying terminals and exposed non-current carrying metal parts, between operation
circuit and control output circuit, between control output circuits, and between non-continuous contacts.)
Dielectric strength 2,950 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between operation circuit and control output circuit, and between control output
circuits)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Noise immunity ±1,500 V (between power terminals, for AC power models), ±500 V (between power terminals, for DC power models)
Square-wave noise by noise simulator (pulse width: 100 ns, for 1 μs, 1-ns rise time)
Vibration
resistance
Destruction 10 to 55 Hz with 0.375-mm single amplitude in 3 directions for 2 hours each
Malfunction 10 to 55 Hz with 0.25-mm single amplitude in 3 directions for 10 minutes each
Shock
resistance
Destruction 300 m/s2 3 times each in x, y, and z axes, 6 directions
Malfunction 100 m/s2 3 times each in x, y, and z axes, 6 directions
Life
expectancy
Mechanical 100,000 operations min.
Electrical 50,000 operations min. (15 A at 250 VAC, resistive load)
50,000 operations min. (10 A at 30 VDC, resistive load)
50,000 operations min. (10 A at 250 VAC, inductive load (cosφ = 0.7))
50,000 operations min. (1 HP at 250 VAC, motor load)
50,000 operations min. (100 W at 100 VAC, lamp load)
10,000 operations min. (300 W at 100 VAC, lamp load)
50,000 operations min. (3 A at
250 VAC, resistive load)
50,000 operations min. (3 A at
30 VDC, resistive load)
Approved standards CURUS: UL 508/CSA C22.2 No.14,
Conforms to EN 60730-2-7(Pollution degree 2/overvoltage category II),
Conforms to VDE 0106/part100.
Conforms to Electrical Appliance and Material Safety Law (for Japan)
EMC (EMI) EN 60730-2-7
EMI Radiated: EN 60730-2-7 (CISPR 22 Class B)
EMI Conducted (Continuous): EN 60730-2-7 (CISPR 22 Class B)
EMI Conducted (Non-continuous): EN 60730-2-7 (CISPR 14-1)
Harmonic Current: EN 60730-2-7 (IEC 61000-3-2 Class A)
Voltage fluctuation/flicker: EN 60730-2-7 (IEC 61000-3-3)
(EMS) EN 60730-2-7
ESD Immunity: EN 60730-2-7 (IEC 61000-4-2): 6 kV contact discharge
8 kV air discharge
Radiated Electromagnetic Field Immunity: EN 60730-2-7 (IEC 61000-4-3): 10-V/m AM modulation
(80 MHz to 1 GHz, 1.4 GHz to 2 GHz)
10-V/m pulse modulation (900 MHz)
Conducted Disturbance Immunity: EN 60730-2-7 (IEC 61000-4-6): 10 V (0.15 to 80 MHz)
Burst Immunity: EN 60730-2-7 (IEC 61000-4-4): 2 kV power line
1 kV control line
Surge Immunity: EN 60730-2-7 (IEC 61000-4-5): 1 kV line to line (power line, output line)
2 kV line to ground (power line, output
line)
0.5 kV line to line (input line)
1 kV line to ground (input line)
Voltage Dip/Interrupting Immunity: EN 60730-2-7 (IEC 61000-4-11): 0.5-s cycle, 100% (rated voltage)
Weight Approx. 200 g
H5S
5
Operation
Note: 1. Depending the operation, the following steps can be used for weekly programs.
Timer operation: 2 steps
Pulse-output operation: 1 step
Cyclic operation: 4 steps
2. When the season switching setting is not being used.
3. When the season switching setting is being used.
Operation Functions
Item Weekly 2-circuit Models
(H5S-W@2)
Yearly 2-circuit Models
(H5S-Y@2)
Yearly 4-circuit Models
(H5S-Y@4)
Operation method Digital quartz
Operation period 1 week (7 days) 1 year (with integrated calendar to 2099)
Display Day, hrs (switchable between 24-hr indication and a.m./p.m. 12-hr indication), minutes, seconds
(0.00 to 23:59, 0.00 to 11:59 a.m., 0.00 to 11:59 p.m.)
Digital indication by LCD (character height: 10 mm)
Digital display of operation schedule during operation
Timing chart display of operation schedule during operation
Min. setting unit 1 min
Number of
steps that
can be set
Weekly program
(See note 1.)
40 steps/circuit 48 steps/circuit (See note 2.)
24 steps/circuit (per season) (See
note 3.)
48 steps/circuit (See note 2.)
12 steps/circuit (per season) (See
note 3.)
Yearly program --- 4 yearly programs/circuit
Number of
settable yearly
temporary
holiday settings
--- 16
Item Weekly 2-circuit Models (H5S-W@2) Yearly 2-circuit Models (H5S-Y@2) Yearly 4-circuit Models (H5S-Y@4)
Weekly timer
operation
Controls the output according to the set time of ON and OFF.
Min. setting unit: 1 min
Multiple-day operation also possible.
Weekly pulse-
output
operation
Output turns ON for a fixed period (pulse width) at the set ON time.
Pulse width: 1 to 59 s (in 1-s increments), or 1 to 60 min (in 1-min increments)
The pulse width can be set for each step.
Weekly cyclic
operation
Repeatedly turns ON and OFF during the period from the cyclic start time to the stop time.
Independent ON- and OFF-time settings are possible.
Min. setting unit: 1 min
(The ON time width and OFF time width can each be set to between 1 minute
and 11 hours 59 minutes.)
The timer operation repeatedly turns the signal ON and OFF for the time widths specified
by the ON time and OFF time during the period from the day of the week and time that are
set for the cyclic start time to the day of the week and time that are set for the stop time.
Yearly timer
operation
--- Adds a yearly timer operation to the weekly timer program.
For details, refer to About Yearly Programs on page 18.
Yearly pulse-
output
operation
--- Adds a yearly pulse-output operation to the weekly pulse-output program.
For details, refer to About Yearly Programs on page 18.
Temporary
holiday setting
Sets temporary holidays (non-operating days) without having to revise the existing program.
For details, refer to Setting Temporary Holidays (Weekly) and Setting Temporary Holidays (Yearly) on page 20.
Day override
operation
Executes the operation for one day
temporarily on another day in the 7-day
period starting from the current day.
For details, refer to Day Override
Operation on page 21.
---
Program check Consecutively displays the days and times when the output is set to turn ON and OFF over the course of one week in the
sequence in which the Time Switch is to operate.
For details, refer to Program Check Function on page 21.
ONOFF
Timer operation
Pulse output operation
ON
Pulse width
Cyclic operation
StopStart ON
OFF
()
H5S
6
Checking the
settings
Consecutively displays the times when the output is set to turn ON and OFF for one day in the sequence in which the Time
Switch is to operate.
For details, refer to Checking the Settings on page 21.
Forced ON/OFF
operation
Allows the output to be forcibly turned ON/OFF by the Output ON/OFF Switch regardless of the control output setting.
Override and
automatic
return
operation
Allows the control output to be maintained in the ON (or OFF) state until the next OFF (or ON) time. This operation is controlled
by using the Output ON/OFF Switch and Write Key. When completed, the Time Switch automatically resumes the previously
set operation.
For details, refer to Override and Automatic Return Operation on page 22.
Summertime
(DST)
adjustment
Switches the current time from “current time” to “current time + 1 h” for daylight savings time. Yearly models also offer automatic
switching to daylight savings time.
For details, refer to Manual Summer Time (DST) Adjustment on page 21.
Time counter/
total counter
display
Displays the total elapsed time and total count of external input. It also displays a
warning when a set value is entered.
For details, refer to Time Counter/Total Counter Display (F2, F3, F4) on page 23.
---
Time
adjustment
input
Allows the time to be set to 00 min 00 s at the same time as an external input is
applied.
For details, refer to Time Adjustment Input Function (F2) on page 24.
---
Manual
operation on
recovery from
power failure
Allows the output state to be specified following recovery from a power failure.
For details, refer to Manual Operation on Recovery from Power Failure (F2) on page
24.
---
Bank switching Allows two groups (banks) of programs to
be registered and switched by external
input.
For details, refer to Bank Switching (F2)
on page 24.
---
Season
switching
--- Allows weekly programs to be automatically switched in response to seasons
throughout the year.
For details, refer to Season Switching/Period of Season (F8/F9) on page 24.
Power OFF
settings
Allows the display to remain lit even when the power is turned OFF, and settings to be made for all functions except Override
and Automatic Return Operation.
The display illumination will turn OFF when there has been no operation for 2 min. The display will light again when any key
other than a slide switch is pressed for at least 1 s.
No output will be generated.
Item Weekly 2-circuit Models (H5S-W@2) Yearly 2-circuit Models (H5S-Y@2) Yearly 4-circuit Models (H5S-Y@4)
H5S
7
Connections
Terminal Arrangement
H5S-@A@/-@B@ Flush Mounting Models
Two-circuit Models Four-circuit Models
H5S-@FA@/-@FB@ Surface Mounting Models
Two-circuit Models Four-circuit Models
Note: 1. The Time Switch output uses a no-voltage contact. An external power supply is required for applications in which a load is driven.
2. The output contact ratings are different for 2-circuit and 4-circuit models.
Input Connection (Two-circuit Models Only)
Use a switch or relay as the input contact.
Use a contact that is capable of operating with 5 V, 0.1 A (with a minimum signal input width of 100 ms).
One of the following functions can be assigned to the input.
Time Counter/Total Counter Display
Time Adjustment
Manual Operation on Recovery from Power Failure
Bank Switching
Note: Input must be selected using the “F2: Input selection” step of initial setting mode. For details, refer to Using Advanced Functions on page 23.
Output 2
Output 1Power
source
Input
+
(Rear View)
G
A
H JI
DCB
Output 2 Output 3
Output 4
Output 1Power
source
+
(Rear View)
BE
D
AC
FJ
H
GI
Output 2Input
Output 1 Power
source
+
(Front View)
FGHI
CB DE
Output 2Output 3
Output 4
Output 1 Power
source
+
(Front View)
BE
D
AC
FJ
H
GI
Flush mounting models
(H5S-@A2@/-@B2@)
Surface mounting models
(H5S-@FA2@/-@FB2@)G
J
F
I
H5S
8
Nomenclature
Front Panel (with Cover Open)
Weekly Two-circuit Models
Yearly Two-circuit Models
Yearly Four-circuit Models
Key Operations
Note: To enable operation according to the settings that you made,
first make the settings and then set the Output ON/OFF Switch
(12) to AUTO and the Mode Switch (1) to RUN.
13. Day Keys
10. Time Adjustment
Key
12. Output
ON/OFF
Switches
1. Mode
Switch
2. Holiday/
Down Key
3. Write Key
4. m/Pulse Key
5. h Key
6. Reset Key
7. +1h/Clear
Key
8. Copy/Cycle Key
9. Test
Key
11. Output
Setting
Switches
13. Day Keys
10. Time Adjustment
Key
12. Output
ON/OFF
Switches
1. Mode
Switch
2. Holiday/
Down Key
3. Write Key
4. m/Pulse Key
5. h Key
6. Reset Key
7. +1h/Clear
Key
8. Cycle Key
9. Test/
Year
Key
11. Output
Setting
Switches
13. Day Keys
10. Time Adjustment
Key
12. Output
ON/OFF
Switches
1. Mode
Switch
2. Holiday/
Select Program/
Down Key
3. Write Key
4. m/Pulse Key
5. h Key
6. Reset Key
7. +1h/Clear
Key
8. Cycle Key
9. Test/
Year
Key
11. Output
Setting
Switches
No. Functions
1Two-circuit Models
P1: Circuit (output) 1 Setting mode
P2: Circuit (output) 2 Setting mode
RUN: RUN mode
Four-circuit Models
PRGM: Setting mode (allows use of the Select Program Key
to set the circuit (output) number)
RUN: RUN mode
2Two-circuit Models
In RUN mode, this key shifts the Time Switch to the Holiday
Setting mode
In Setting mode or Time Adjustment mode, this key
decrements the value for the operation just completed.
Four-circuit Models
In RUN mode, this key shifts the Time Switch to the Holiday
Setting mode.
When selecting the output, this key is used to set the circuit
(output) number.
In Setting mode or Time Adjustment mode, this key
decrements the value for the operation just completed.
3Sets parameters.
4Used to set the current time, ON/OFF time, or pulse width.
5
6Used to reset all parameters, including the current time.
7In RUN mode, this key sets or cancels summer time (+1 h)
In Setting mode, this key clears the parameter.
8In RUN mode (weekly models only), this key shifts the Time
Switch to the Day Override operation setting mode.
In Setting mode, this key shifts the Time Switch to cyclic
operation setting.
9In RUN mode, this key shifts the Time Switch to the Program
Check mode.
In Setting mode (yearly models only), this key is used to set
the yearly program.
10 This key shifts the Time Switch to the time adjustment mode.
11 TIMER: Executes a timer or cyclic operation.
PULSE: Executes a pulse-output operation.
12 ON: Turns ON the output regardless of the setting.
AUTO: Executes automatic operation as specified by these
settings.
OFF: Turns OFF the output regardless of the setting.
13 Used to set the current day, operating day, etc.
Used to specify the date (yearly models only)
In RUN mode, these keys are used to shift the Time Switch
to the Checking the Settings mode.
H5S
9
Display
Display Description
No. Function
1Lights when power is supplied to the Time
Switch.
2When 12-hour display is selected, either AM
or PM lights. (24-hour display is the default.)
3Lights when summer time (+1 h) is activated.
4Displays the current time and other values.
5Displays the unit for the pulse width.
6Lights when the total time or count value
exceeds the alarm setting.
7Displays the number of remaining steps for
programming in setting mode.
8Displays the number of the circuit (output)
that has been set.
9Displays the time for the next operation, the
date (yearly models only), and other values.
10 Displays the next operation and other
information in chart form.
11 Displays the bank name (weekly models) or
season name (yearly models).
12 Lights when setting the ON/OFF time or
when setting a day override operation.
13 Lit during the temporary holiday operation or
when setting a temporary holiday.
14 Lit during the day override operation or when
setting a day override operation.
15 Lit during setting a yearly program.
16 Flashes during the Time Adjustment mode.
17 Displays the current day or the day set for an
operation.
18 Displays the number of the circuit (output) for
which output is ON.
Weekly Two-circuit Models
5. Pulse width unit indicator
4. Main display
9. Sub-display
10. Timing chart display
17. Day indicator
11. Bank indicator
12. From/To indicator
14. Copy indicator
1. Power indicator
2. AM/PM indicator
3. Summer time indicator
2. AM/PM indicator
13. Holiday indicator
7. Display of number
of remaining steps
8. Set circuit number
indicator
6. Total value alarm
indicator
18. Output circuit number
indicator
16. Time adjustment mode
indicator
Yearly Two-circuit Models
4. Main display
9. Sub-display
10. Timing chart display
17. Day indicator
11. Season indicators
12. From/To indicator
13. Holiday indicator
1. Power indicator
2. AM/PM indicator
3. Summer time indicator
2. AM/PM indicator
15. Year indicator
7. Display of number
of remaining steps
8. Set circuit number
indicator
6. Total value alarm
indicator
16. Time adjustment mode
indicator
5. Pulse width unit
indicator
18. Output circuit number
indicator
Yearly Four-circuit Models
4. Main display
9. Sub-display
10. Timing chart display
17. Day indicators
11. Season indicator
12. From/To indicator
13. Holiday indicator
1. Power indicator
2. AM/PM indicator
3. Summer time indicator
2. AM/PM indicator
15. Year indicator
7. Display of number
of remaining steps
8. Set circuit number
indicator
16. Time adjustment mode
indicator
5. Pulse width unit
indicator
18. Output circuit number
indicator
H5S
10
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Digital Time Switch
Mounting bracket (included)
Four M3 x 8 screws (included) for mounting
the terminal covers
Two terminal covers (included)
Two M4 x 12 screws (included)
for the mounting bracket
Protective Cover
Y92A-72C (Order separately)
9.5 (53.2)
49
6
(75 × 75)
(12.5)
67.6 × 67.6
72
72
68+
0.8
0
68+
0.8
0
9.5 49
Mounting panel
H5S
TIME SWITCH
Flush Mounting Model
H5S-@A@/-@B@
Note: 1. The terminal screws are M3.5.
2. This illustration shows a 2-circuit model. The 4-circuit model
has the same dimensions.
Panel Cutout
Note: Panel thickness: 1 to 5 mm
Protective Cover
Y92A-72C (Order separately)
Y92F-90 DIN Track
Mounting Base
(Order separately)
Four M3 x 8 screws (included)
for mounting terminal covers
Two terminal covers (included)
(9.5)
55
49 (20.2)
16
(75 × 75)
(61.5)
58.5
Mounting holes
for four M4 screws 63.2
72
56
96 89 72
Mounting panel
89±0.2
56±0.15
4-dia. *
Panel thickness t
Hole diameter
0.8 to 1.2
3.6
1.6 to 4
3.7
*Diameter of pilot holes for
included M4 tapping screws (guideline)
17.7
37
Four M3 x 8 screws for
mounting the Y92A-72H
Large Terminal Cover
(included with the Y92A-72H)
Y92A-72H Large Terminal Cover
(Order separately)
66.7
126.7
Use a tool such as long nose pliers to prepare the openings for pulling wires.
When using the product
in an exposed mounting
condition, always use the
Y92A-72H Large
Terminal Cover (order
separately) to comply
with Electrical Appliance
and Material Safety Law
(for Japan).
71.1 *1
79.8 *2
Y92F-90 DIN Track Mounting Base
(Order separately)
DIN Track
Mounting panel
H5S
TIME SWITCH
Surface Mounting Model
H5S-@FA@/-@FB@
Note: 1. The terminal screws are M3.5.
2. This illustration shows a 2-circuit model. The 4-circuit model
has the same dimensions.
Mounting holes
(Surface mounted)
(With the large terminal cover (order separately) attached) (DIN track mounted)
Note: 1. Using a PFP-50N or PFP-100N
Mounting Track.
2. Using a PFP-100N2 Mounting Track.
H5S
11
Accessories (Order Separately)
Track Mounting Accessories (Order Separately)
Protective Cover
Y92A-72C
DIN Track Mounting
Base
Y92F-90
Note: The DIN Track Mounting Base can be
used only with the surface mounting
models (H5S-@FA@/-@FB@).
Large Terminal Covers
Y92A-72H (two per set)
Note: The Large Terminal Cover can be
used only with the surface mounting
models (H5S-@FA@/-@FB@).
1
35
±0.3
7.3
±0.15
27
±0.15
4.5
15 25 25
10 15 (5) *
10
25 25
* The numbers in parentheses ( ) are dimensions for the PFP-50N
1,000 (500) *
Mounting Track
PFP-100N
PFP-50N
15 25 25
1,000
4.5
25 25 15
10 1
242735
±0.3
16
1.5
29.2
10
PFP-100N2
4.8
1.3
35.5 35.3
1.8
1
1.8
10
6.2
M4 spring washer
50
11.5
M4 × 8
pan-head
screw
10
End Plate
PFP-M 5
16
12
44.3
34.8
16.5
Spacer
PFP-S
H5S
12
Safety Precautions
!CAUTION
Precautions for Safe Use
Please comply strictly with the following instructions which are
intended to ensure safe operation of the product.
1. Have the Time Switch installed only by qualified electrical
workers.
2. Store the Time Switch within the specified ratings. If the Time
Switch has been stored at temperatures of 10°C or lower, let it
stand for three hours or longer at room temperature before
turning ON the power supply.
3. Mounting the Time Switch side-by-side may reduce the life
expectancies of internal components.
4. Use the Time Switch within the specified ratings for operating
temperature and humidity.
5. Do not operate the Time Switch in any of the following locations.
Locations subject to sudden or extreme changes in
temperature.
Locations where high humidity may result in condensation.
6. The Time Switch is not waterproof or oil resistant. Do not use it in
locations subject to water or oil.
7. Do not use the Time Switch in locations subject to excessive dust,
corrosive gas, or direct sunlight.
8. Install the Time Switch well away from any sources of excessive
static electricity, such as pipes transporting molding materials,
powders, or liquids.
9. Maintain voltage fluctuations in the power supply within the
specified range.
10.Internal elements may be destroyed if a voltage outside the rated
voltage is applied.
11.Be sure to wire the terminals correctly and use the correct
polarity.
12.Separate equipment that produces input signals, input signal
wiring, and the Time Switch from noise-generating sources and
high-voltage lines containing noise.
13.Do not connect more than two crimp terminals to each Time
Switch terminal.
14.Up to two wires of the same size and type can be inserted into a
single terminals.
15.Use the specified wires for wiring.
Applicable wire: AWG 22 to AWG 14 (equal to a cross-sectional
area of 0.326 to 2.081 mm2)
Solid wire or twisted wire
Material: Copper
16.Install a switch or circuit breaker that allows the operator to
immediately turn OFF the power, and label it to clearly indicate its
function.
17.Take adequate protective measures (such as a breaker, or fuse)
for the power supply of the Time Switch.
18.When using heaters, be sure to use a thermal switch for the load
circuit.
19.Always maintain the load current within specifications.
20.Use a switch, relay, or other contacts so that the rated power
supply voltage will be reached within 0.1 s. If the power supply
voltage is not reached quickly enough, the power source may fail
to reset or the outputs may fail to operate correctly.
21.Use a switch, relay, or other contact to turn the power supply OFF
instantaneously. Outputs may malfunction and memory errors
may occur if the power supply voltage is decreased gradually.
22.The Time Switch utilizes a transformerless power supply. Do not
touch the input terminal while power is being supplied; touching
live terminals may result in electric shock.
23.Use the Time Switch within the specified ratings for vibration and
shock.
24.Use a commercial power supply when using AC power supply
voltage input.
Although some inverters specify their output frequency as 50/
60 Hz, smoke or burning may occur from a rise in internal
temperature. Do not use inverter output as the power supply.
25.Do not leave the Time Switch for long periods at a high
temperature with output current in the ON state. Doing so may
result in the premature deterioration of internal components (e.g.,
electrolytic capacitors).
26.Do not use organic solvents (such as paint thinner or benzine),
strong alkaline, or strong acids to clean the case because they
will damage the external finish.
27.None of the Time Switch components are user-replaceable,
including the battery.
28.Use a tool such as long nose pliers to prepare the openings for
pulling wires out of the optional Y92A-72H Large Terminal Cover.
Attempts to form an opening by hand may result in injury.
Precautions for Correct Use
1. When the power is turned ON, an inrush current will flow for a
short time (AC: Approx. 2.5 A (0.3 ms), DC: Approx. 1.1 A (3 ms)).
Depending on the power supply capacity, operation may not start.
Be sure to use a power supply with a sufficient capacity.
2. Inrush current generated by turning ON or OFF the power supply
may deteriorate contacts on the power supply circuit. Use to turn
ON or OFF devices with a rated current of 10 A min.
3. The timer functions and set program are backed up by a battery. If
the life of the battery expires, the display will become irregular or
may fail to function. The battery cannot be replaced by the user.
Contact your OMRON representative.
Minor injury by electric shock may occasionally occur. Do
not touch any of the terminals while power is being
supplied. Be sure to mount the terminal cover after wiring.
When using a surface-mounting model in an exposed
condition, always install the Y92A-72H terminal cover
(separately purchased) to comply with Electrical
Appliance and Material Safety Law (for Japan).
Minor injury due to explosion may occasionally occur. Do
not use the product where subject to flammable or
explosive gas.
Minor electric shock, fire or malfunction may occasionally
occur. Never attempt to disassemble, modify, or repair the
product or touch any of the internal parts.
Fire may occasionally occur. Tighten the terminal screws
to the rated torque (from 0.98 to 1.17 N·m).
Unexpected operation may occasionally occur.
Before changing times or other settings while power is
being supplied, either turn OFF the power on the load
side or set the output ON/OFF switch to OFF and confirm
the safety of the system.
Minor electric shock, fire, or malfunction may occasionally
occur. Do not allow metal fragments, lead wire scraps, or
shavings from installation work to fall inside the Time
Switch.
If the output relay is used beyond its life expectancy, its
contacts may become fused or there may be a risk of
burning. Use the product within its rated load and
electrical life expectancy. The life expectancy of the
output relay varies considerably according to its capacity
and operating conditions.
Serious injury may occasionally occur due to fire or
explosion of a battery, or leakage from a battery. Never
attempt to short the positive and negative terminals,
recharge, disassemble, deform by applying excessive
pressure, or expose the battery to fire.
H5S
13
EN/IEC Standards
The insulation system between the power supply circuit and input-
output terminals provides basic insulation.
Therefore connect the output terminals only to circuits without
exposed conductive parts. If a connection to a Safety Extra Low
Voltage (SELV) circuit is desired, supplementary insulation must be
provided.
Use crimp type cable lug terminals with insulating sleeves for
wiring.
Be sure to mount a surface-mounting model (H5S-@FA@/-@FB@)
in an enclosure.
The relationship between load current and ambient air temperature
is shown by the range below for 2-circuit models.
If wires with a temperature rating of 105 °C or higher are used, refer
to the derating curve in Specifications on page 3.
Control system: Electronic
Types of automatic operation: Weekly models - Type 1 BSTU
Yearly models - Type 2 BSTU
Protective class: Class 0
Rated impulse withstand voltage: 2,500 V AC
Ball-pressure test temperature (enclosure material): 125°C
Basic Use
Prior to Using
Before setting the parameters necessary for each operation, the operation of each circuit (output) must be determined. Begin by setting initial
setting mode as required.
40
30
20
10
0
10 0 20 40 55 60 80
Ambient temperature (°C)
Total current (A)
Open the front cover.
Determine and
set the operation
of each circuit (output).
Set initial setting mode.
The Initial Setting mode must be
set to use the following functions.
Common to all models:
Next Operation Display Switching
Weekly models:
Time Counter/Total Counter Display
Time Adjustment Input
Manual Operation on Recovery
from Power Failure
Bank Switching
Yearly models:
Time Counter/Total Counter
Display
(See note.)
Time Adjustment Input (See note.)
Manual Operation on Recovery
from Power Failure (See note.)
Season Switching
Date Format Selection
Summer Time (DST) Adjustment
Note: 2-circuit models only
Set as necessary:
Note: Pull the front cover
open with your
fingertips.
Note: Use the tip of a ball-
point pen, or other
sharp instrument, to
make the settings.
For details, refer to Using Advanced Functions on
page 23.
HOLID
A
ON
AUTO
OFF
OUT
SATFRITHUWEDTUEMONSUN
P2
P1
RUN
OUT1
OUT2
DMY
W
R
m/PLS
h
Timer operation Pulse operatio
n
OUT
R
PULSE
TIMER
HOLID
A
SATFRITHUWEDTUEMONSUN
OUT1
OUT2
TEST
YEAR CYCLE CLEARTIME ADJ
DMY
WR
I
h
ON
AUTO
OFF
m/PLS
Note:
These settings
are not required
to use the basic
Time Switch
functions.
To enable operation
according to the
settings that you
made, first make the
settings and then set
the Output ON/OFF
Switch to AUTO and
the Mode Switch to
RUN.
H5S
14
Time Adjustment (Weekly Models) Time Adjustment (Yearly Models)
Weekly, 2 Circuits
Example: Set the current time to Saturday 17:28.
1. Set the Mode
Switch to RUN. Shaded portion indicates
blinking of the indicator.
2. Press for 2 s or more.
The symbol flashes.
3. Press .
(The bar ( ) mark at the Saturday
position will turn ON.)
Set the time with and . *
4. Press to enter the setting,
and the Time Switch will start from 0
second.
* Holding down the and Keys rapidly advances the value.
Pressing decrements the value of the key that was last
pressed.
Note:
When first turned ON or after a reset,
the time adjustment display appears
on the screen. Adjust the time by
following steps 3 and 4.
If is pressed again before
pressing , the setting is
cancelled. (The setting is not revised.)
P1
P2
RUN
TIME ADJ
SUN
MON
TUE
WED
THU
FRI
SAT
SAT
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
SUN
MON
TUE
WED
THU
FRI
SAT
hm
TIME ADJ
WRITE
SUN
MON
TUE
WED
THU
FRI
SAT
Yearly, 2 Circuits Yearly, 4 Circuits
Example: Set the current time to 17:28 on August 15, 2006.
1. Set the Mode
Switch to RUN.
Shaded portion indicates
blinking of the indicator.
2. Press for 2 s or more.
The symbol flashes.
3. Specify the date by pressing ,
and . *
4. Press .
Set the time with and . *
5. Press to enter the settings,
and the Time Switch will start from 0
second.
* Holding down the and Keys rapidly advances the value.
Pressing decrements the value of the key that was last
pressed.
Note:
When first turned ON or after a reset,
the time adjustment display appears
on the screen. Adjust the time by
following steps 3 through 5.
If is pressed again before
pressing , the setting is
cancelled. (The setting is not revised.)
2 circuits
P1
P2
RUN
4 circuits
PRGM
RUN
TIME ADJ
Y M
D
WRITE
hm
WRITE
hm
TIME ADJ
WRITE
H5S
15
Ordinary Timer Operation Multiple-day Operation 1
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Example: ON at 8:30 and OFF at 17:15 on Monday through Friday.
1. Set the Mode Switch to P1 or P2. *1
(The Time Switch enters program
setting mode.)
For 4-circuit models, refer to
page 18.
2. Press the Day Keys to turn ON the
bars ( ) at the positions of Monday
through Friday.
Set the ON time with and . *2
3. Press .
Set the OFF time with and . *2
4. Press to enter the settings.
*1 If one or more programs have already been set, the display
starts showing the set programs.
To add another program, press repeatedly until “--:--
is displayed.
*2 Holding down the and Keys rapidly advances the value.
Pressing decrements the value of the key that was last
pressed.
Note:
If multiple settings are required, repeat steps 2 through 4.
Both the ON and OFF times must be set.
All of the weekly programs for the selected circuit (output) can be
checked by pressing in program setting mode.
When the Mode Switch is set to P1 or P2 (to PRGM for 4-circuit
models), the Time Switch stops automatic operation. To forcibly
turn ON or OFF the output, use the Output ON/OFF Switches.
The set data will be cleared if the Output Setting Switch is moved
between the TIMER and PULSE positions after the data has been
set.
SUN MON TUE WED THU FRI SAT
8:30 17:15 8:30 17:15 8:30 17:15 8:30 17:15 8:30 17:15
Shaded portion
indicates blinking of
the indicator.
SUN
MON
TUE
WED
THU
FRI
SAT
Number of
remaining steps
P1
P2
RUN
PULSE
TIMER
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
WRITE
hm
WRITE
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Example: ON continuously from 8:30 on Monday to 17:15 on Friday.
1. Set the Mode Switch to P1 or P2.*1
(The Time Switch enters program
setting mode.)
For 4-circuit models, refer to
page 18.
2. Press the Day Keys to turn ON the
bar ( ) at the Monday position.Set
the ON time with and . *2
3. Press .
Press to flash the bar ( ) at
all day positions and press to
turn ON the bar ( ) at the Friday
position.
Set the OFF time with and . *2
4. Press to enter the settings.
*1 If one or more programs have already been set, the display
starts showing the set programs.
To add another program, press repeatedly until “--:--
is displayed.
*2 Holding down the and Keys rapidly advances the value.
Pressing decrements the value of the key that was last
pressed.
8:30 17:15
SUN MON TUE WED THU FRI SAT
Shaded portion
indicates blinking of
the indicator.
SUN
MON
TUE
WED
THU
FRI
SAT
Number of
remaining steps
P1
P2
RUN
PULSE
TIMER
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
MON
FRI
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
WRITE
hm
H5S
16
Multiple-day Operation 2 Pulse-output Operation
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Example: ON at 22:00 from Monday through Friday and OFF at 8:00
each following morning.
1. Set the Mode Switch to P1 or P2. *1
(The Time Switch enters program
setting mode.)
For 4-circuit models, refer to
page 18.
2. Press the Day Keys to turn ON the
bar ( ) at the positions of Monday
through Friday.
Set the ON time with and . *2
3. Press .
Press to turn OFF the bar
( ) at the Monday position and
press to turn ON the bar ( )
at the Friday position.
Set the OFF time with and . *2
4. Press to enter the settings.
*1 If one or more programs have already been set, the display starts
showing the set programs.
To add another program, press repeatedly until “--:--
is displayed.
*2 Holding down the and Keys rapidly advances the value.
Pressing decrements the value of the key that was last
pressed.
22 8 22 8 22 8 22 8 22 8
SUN MON TUE WED THU FRI SAT
Shaded portion
indicates blinking of
the indicator.
SUN
MON
TUE
WED
THU
FRI
SAT
Number of
remaining steps
P1
P2
RUN PULSE
TIMER
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
MON
SAT
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
WRITE
hm
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Example: ON for 30 seconds at 8:25 am from Monday through
Saturday.
1. Set the Mode Switch to P1 or P2.*1
(The Time Switch enters program
setting mode.)
For 4-circuit models, refer to
page 18.
2. Press the Day Keys to turn ON the
bars ( ) at the positions of Monday
through Saturday.Set the ON time
with and . *2
3. Press .
Set the pulse width with . *2
The displayed pulse width changes
by pressing this key in the following
order.
1s2s…59s1m…59m60m1s
4. Press to enter the settings.
*1If one or more programs have already been set, the display starts
showing the set programs.
To add another program, press repeatedly until “--:--
is displayed.
*2Holding down the and Keys rapidly advances the value.
Pressing decrements the value of the key that was last
pressed.
Note:
If multiple settings are required, repeat steps 2 through 4.
Both the ON time and pulse width must be set.
All of the weekly programs for the selected circuit (output) can be
checked by pressing in program setting mode.
When the Mode Switch is set to P1 or P2 (to PRGM for the 4-
circuit model), the Time Switch stops automatic operation. To
forcibly turn ON or OFF the output, use the Output ON/OFF
switches.
The set data will be cleared if the Output setting switch is moved
between the TIMER and PULSE positions after the data has been
set.
AM8:25
30 s
SUN MON TUE WED THU FRI SAT
Shaded portion
indicates blinking of
the indicator.
SUN
MON
TUE
WED
THU
FRI
SAT
Number of
remaining steps
P1
P2
RUN
PULSE
TIMER
hm
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
PLS
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
WRITE
hm
WRITE
H5S
17
Cyclic Operation
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Example: ON for 5 minutes and OFF for 1 hour 55 minutes
repeatedly from 8:00 to 19:00 on Sunday.
1. Set the Mode Switch to P1 or P2. *1
(The Time Switch enters program
setting mode.)
For 4-circuit models, refer to
page 18.
2. Press .
(The Time Switch enters cyclic
program setting mode.)
3. Press the Day Keys to turn ON the bar
( ) at the Sunday position.
Set the start time to 8:00 with and
. *2
4. Press .
Set the stop time to 19:00 with
and . *2
5. Press .
Set the ON time period with and
. *2
6. Press .
Set the OFF time period with and
. *2
7. Press to enter the settings.
*1 If one or more programs have already been set, the display starts
showing the set programs.
To add another program, press repeatedly until “--:--
is displayed.
*2 Holding down the and Keys rapidly advances the value.
Pressing decrements the value of the key that was last
pressed.
The ON time width and OFF time width can each be set to
between 1 minute and 11 hours 59 minutes.
Note:
If multiple settings are required, repeat steps 2 through 7.
All the start/stop times, and ON/OFF time periods must be set.
All of the weekly programs for the selected circuit (output) can be
checked by pressing in program setting mode.
When the Mode Switch is set to P1 or P2 (to PRGM for 4-circuit
models), the Time Switch stops automatic operation. To forcibly
turn ON or OFF the output, use the Output ON/OFF Switches.
Set cyclic operation so as not to overlap other operations in
individual circuits.
The set data will be cleared if the Output Setting Switch is moved
between the TIMER and PULSE positions after the data has been
set.
SUN
8:00
Start
1 h 55 min
5 min
19:00
Stop
Shaded portion
indicates blinking of
the indicator.
SUN
MON
TUE
WED
THU
FRI
SAT
Number of
remaining steps
P1
P2
RUN
PULSE
TIMER
CYCLE
SUN
MON
TUE
WED
THU
FRI
SAT
h
m
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
h
m
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
h
m
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
h
m
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
WRITE
hm
WRITE
H5S
18
Clearing the Settings
Partial clearing
Clearing all the settings in an entire circuit
Programming for 4-circuit models
The following shows how to program (select the output circuit
number) for 4-circuit models.
About Yearly Programs
Yearly programs in addition to ordinary weekly programs can be set
for 2- and 4-circuit yearly models.
Note: 1. This example combines the following programs.
For details on yearly programming, refer to page 19.
Weekly program
Friday, Saturday, and Sunday: 9:00 (ON time),
18:00 (OFF time)
Yearly program
March 25: 18:00 (ON time), 22:15 (OFF time)
2. For details on automatically switching the weekly program
depending on the season, refer to page 24.
To set multiple-day operation for a yearly program, two yearly
programs must to be set as shown in the following example.
Note: Do not enter a weekly program.
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
1. Set the Mode Switch to P1 or P2 and
select the setting to be cleared. Shaded portion indicates
blinking of the indicator.
2. Press briefly.
3. Press to clear the setting. *
1. Set the Mode Switch to the position
for the circuit whose settings are to
be cleared. Shaded portion indicates
blinking of the indicator.
2. Press and hold for 3 s or
more.
3. Press to clear all the settings of the circuit. *
* The clearing operation can be cancelled by pressing
while clr is displayed.
Yearly, 4 Circuits
1. Set the Mode Switch to PRGM.
(The Time Switch enters program
setting mode.)
Shaded portion indicates
blinking of the indicator.
2. Select an output circuit with
. Pressing the key
changes the set circuit number
displayed in the lower right corner of
the LCD.
The rest of the procedure is the same
as for 2-circuit models.
Note: The circuit number cannot be changed during the course of
setting.
CLEAR
WRITE
CLEAR
WRITE
CLEAR
PRGM
RUN
SELECT PRGM
1234
SUN
MON
TUE
WED
THU
FRI
SAT
Yearly, 2 Circuits Yearly, 4 Circuits
Example: Extend ordinary weekly operation from 18:00 to 22:15 on
March 25 only.
Example: ON continuously from 18:00 on March 25, 2006, to 12:00
on April 9, 2006.
3/22(THU) 3/23(FRI) 3/24(SAT) 3/25(SUN) 3/26(MON)
18 18
18
Weekly
Program
22:15
Yearly
Program
Output
performance
of H5S
9189 9
18 22:1591899
2006/3/24 3/25 3/26 4/7 4/8 4/9
18 12
March 25, 2006 (Start date)
April 8, 2006 (End date)
18:00 (ON time)
12:00 (OFF time)
March 26, 2006 (Start date)
April 8, 2006 (End date)
8:00 (ON time)
22:00 (OFF time)
Program AProgram B
3/25/2006 3/26 4/7 4/8 4/9
18 12 18 12 18 12 18 12
Program A
822 822822
Program B
18 12
Output
performance
of H5S
H5S
19
Yearly Timer Operation Yearly Pulse-output Operation
Yearly, 2 Circuits Yearly, 4 Circuits
Example: ON at 18:00 and OFF at 22:15 on March 25 every year.
Shaded portion indicates
blinking of the indicator.
1. Set the Mode Switch to P1 or P2.
For 4-circuit models, refer to
page 18.
2. Press for 1 s or more. (The
Time Switch enters yearly program
setting mode. *1)
3. Specify the start date using ,
and . *2
The year can be set from the current
year to the next two years as shown
in the example. If the year is set to
--”, the operation performs every
year.
<Example>
If the current year is 2006, the
displayed year changes as follows.
-- 06 07 08 -- 06
4. Press .
Specify the end date using ,
and . *2
If the starting year has been set to
--”, the ending year cannot be set.
5. Press .
Set the ON time with and . *2
6. Press .
Set the OFF time with and . *2
7. Press to enter the settings.
*1 If one or more programs have already been set, the display starts showing the
set programs.
To add another program, press repeatedly until “--:--“ is displayed.
*2 Holding down the date- or time-setting keys rapidly advances the value.
Pressing decrements the value of the key that was last pressed.
Note:
Yearly programs are added to weekly programs.
All the start/end dates and ON/OFF times must be set. the maximum
number of yearly timer operations that can be set is four for each output
circuit.
If multiple settings are required, repeat steps 3 through 7.
All of the yearly programs for the selected circuit (output) can be checked by
pressing in yearly program setting mode.
The set data will be cleared if the Output Setting Switch is moved between
the TIMER and PULSE positions after the data has been set.
Set the program in the following order.
March 25, 2006 (Start date)
March 25, 2006 (End date)
18:00 (ON time)
22:15 (OFF time)
Day
period
Time
period
SUN
MON
TUE
WED
THU
FRI
SAT
P1
P2
RUN
PULSE
TIMER
YEAR
Y
m
D
WRITE
Y
m
D
Number of
remaining steps
WRITE
hm
WRITE
hm
WRITE
WRITE
WRITE
Yearly, 2 Circuits Yearly, 4 Circuits
Example: To produce output for 2 minutes at 18:00 from March 25 to
April 9.
Shaded portion indicates
blinking of the indicator.
1. Set the Mode Switch to P1 or P2.
For 4-circuit models, refer to
page 18.
2. Press for 1 s or more. (The
Time Switch enters yearly program
setting mode. *1)
3. Specify the start date using ,
and . *2
The year can be set from the current
year to the next two years as shown in
the example. If the year is set to --,
the operation performs every year.
<Example>
If the current year is 2006, the
displayed year changes as follows.
-- 06 07 08 -- 06
4. Press .
Specify the end date using ,
and . *2
If the starting year has been set to
--”, the ending year cannot be set.
5. Press .
Set the ON time with and . *2
6. Press .
Set the pulse width with .
The displayed pulse width changes
by pressing this key in the following
order.
1 s 2 s··· 59 s1 m···
59 m60 m1 s
7. Press to enter the settings.
*1 If one or more programs have already been set, the display starts showing the
set programs.
To add another program, press repeatedly until “--:--“ is displayed.
*2 Holding down the date- or time-setting keys rapidly advances the value.
Pressing decrements the value of the key that was last pressed.
Note:
Yearly programs are added to weekly programs.
All the start/end dates, ON time, and pulse width must be set. The maximum
number of yearly pulse output operations that can be set is four for each
output circuit.
If multiple settings are required, repeat steps 3 through 7.
All of the yearly programs for the selected circuit (output) can be checked by
pressing in yearly program setting mode.
The set data will be cleared if the Output Setting Switch is moved between
the TIMER and PULSE positions after the data has been set.
Set the program in the following order.
March 25, 2006 (Start date)
April 9, 2006 (End date)
18:00 (ON time)
2 minutes (Pulse width)
Day
period
Time
period
SUN
MON
TUE
WED
THU
FRI
SAT
P1
P2
RUN PULSE
TIMER
YEAR
Y
m
D
WRITE
Y
m
D
WRITE
hm
Number of
remaining steps
WRITE
PLS
WRITE
WRITE
WRITE
H5S
20
Convenient Functions
Setting Temporary Holidays (Weekly)
Temporary holidays (non-operating days) can be easily set.
Because the setting is automatically cleared after the set holiday has
passed, temporary holidays are easily set without changing other
settings, including those of the Output ON/OFF Switches.
Setting Temporary Holidays (Yearly)
Temporary* holidays (non-operating days) can be set simply by
specifying dates. The holidays will be OFF in both the weekly and
yearly programs. Because the setting is automatically cleared after
the set holiday has passed, temporary holidays are easily set without
changing other settings, including those of the Output ON/OFF
Switches.
* Annual holidays can also be set.
Weekly, 2 Circuits
Example: Friday and Saturday in the current week are set as
holidays (non-operating days).
The Time Switch then operates according to the ordinary
(previous) settings from the following week onward.
Shaded portion indicates
blinking of the indicator.
1. Press for 2 s or more in
RUN mode.
(The Time Switch enters holiday
setting mode.)
2. Turn OFF the bars ( ) at the
positions of the days to be set as
holidays.
Bar ON: Operating day
Bar OFF: Holiday
3. Press to enter the setting.
After “hday” is displayed for
approximately 1 s, the Time Switch
returns to RUN mode.
Note:
Any day in the 7-day period starting from the current day can be
set as a holiday.
The setting is automatically cleared after the set holiday has
passed.
All ON operations are cancelled on the holiday.
The set holidays are valid for all the output circuits.
You must be in RUN mode to enter to holiday setting mode.
If the current day of the week is changed, the holiday settings will
be cleared.
Press for 2 s in holiday setting mode to return to RUN
mode. If you do nothing for 30 s, the Time Switch will
automatically return to RUN mode.
HOLIDAY
SUN
MON
TUE
WED
THU
FRI
SAT
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
HOLIDAY
Yearly, 2 Circuits Yearly, 4 Circuits
Example: The days from April 29 to May 7 in 2006 are set as
holidays (non-operating days). The Time Switch then
operates according to the ordinary (previous) settings
from the following year onward.
Shaded portion indicates
blinking of the indicator.
1. Press for 2 s or more in
RUN mode. *1
(The Time Switch enters holiday
setting mode.)
2. Specify the start date of holidays
using , and . *2
The year is displayed in the following
order by pressing . (The year can
be set from the current year to the
next two years.)
<Example> If the current year is 2006,
the displayed year changes
as follows.
060708--06
If the year is set to --, the holiday
setting is executed every year.
3. Press .
In the same manner, specify the end
date of holidays using , and
. *2
If the starting year has been set to
--“, the ending year cannot be set.
4. Press to enter the settings.
5. Press for 2 s or more to return to RUN mode.
*1 If one or more programs have already been set, the display starts showing
the set programs.
To add another program, press repeatedly until “--.--“ is
displayed.
*2 Holding down the date-setting keys rapidly advances the value.
Pressing decrements the value of the key that was last pressed.
Note:
Any date between the current date and December 31 in the year
after the following year can be specified as a holiday.
The setting is automatically cleared after the set holiday has
passed (unless the year is set to --).
Repeat steps 2 to 4 to make other settings.
Both the start and end dates of holidays must be set. The
maximum number of holidays that can be set is 16.
You must be in RUN mode to enter to holiday setting mode.
If the current date is changed, the holiday settings will be cleared.
When you specify the year, be sure to set the end date so that it is
after the start date.
Press for 2 s in holiday setting mode to return to RUN
mode. If you do nothing for 30 s, the Time Switch will
automatically return to RUN mode.
All ON operations are cancelled on the holiday.
The set holidays are valid for all the output circuits.
HOLIDAY
Y M D
Y
WRITE
Y M
D
WRITE
HOLIDAY
WRITE
HOLIDAY
H5S
21
Program Check Function
The days and times when output is set to turn ON and OFF over the
course of one week can be displayed in the sequence in which the
Time Switch is to operate.
However, for timer operation, only the OFF time will be displayed for
the programming that is currently being executed. The ON time will
not be displayed.
For a program that is not being executed, all of the programming for
circuit 1 will be displayed and then the programming for circuit 2 and
later will be displayed.
Note: A yearly program cannot be tested.
Checking the Settings
The program can be checked for one week from the current day.
Change to the setting mode to check the year program past one
week.
Day Override Operation
Operation for one day can be temporarily (for only one week)
executed on another day.
Manual Summer Time (DST)
Adjustment
Each time is pressed for 2 s or more in RUN mode, the current
time switches between the current time and the current time +1 hour.
Note: With Yearly models, the current time can also be automatically
switched to DST. For details, refer to functions F6 and F7 on
page 25.
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press for 2 s or more in RUN
mode.
(“test” flashes and the day and time
of the next change in output state are
displayed.)
2. Press .
The display shows the time of the
next change in output state.
Each time is pressed, the
display shows the days and times for
one week.
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press one of the Day Keys for 2 s or
more in RUN mode to check settings
for the day.
(“chec” flashes and the time of the
first ON time is displayed.)
2. Press .
The display shows the time of the
next change in output state.
TEST
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
WRITE
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
Weekly, 2 Circuits
Example: The operation set for Sunday is executed this Saturday.
The Time Switch performs the ordinary operation
(according to the previous settings) from next Saturday
onward.
Shaded portion indicates
blinking of the indicator.
1. Press for 2 s or more in RUN
mode.
(The Time Switch enters day override
operation setting mode.)
2. Turn ON the bar ( ) at the position
of the day for which the set operation
is to be executed on another day.
(“copy” will flash.)
3. Press to select the day on
which the operation is to be
executed.
4. Turn ON the bar ( ) at the position
of the day. More than one day can be
selected.
5. Press to enter the setting.
Note:
Any day in the 7-day period starting from the current day can be
set as a day on which another day's operation is to be executed.
The setting is automatically cleared after the day has passed.
All ON operations are executed on another day.
The day override operation settings are valid for all the output
circuits.
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
COPY
SUN
MON
TUE
WED
THU
FRI
SAT
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
SUN
MON
TUE
WED
THU
FRI
SAT
SUN
MON
TUE
WED
THU
FRI
SAT
WRITE
+1h
SUN
MON
TUE
WED
THU
FRI
SAT SUN
MON
TUE
WED
THU
FRI
SAT
H5S
22
Switching between 12-hour and 24-
hour display
Each time is pressed for 2 s or more in RUN mode, the current
time switches between 12-hour (AM/PM) and 24-hour display.
Display Switching
Each time is pressed for 2 s or more in RUN mode, the displayed
content switches as shown below.
Note: Displays only when Input selection (see function F2 on
page 23) is set to totl.
Note: Displays only when Input selection (see function F2 on
page 23) is set to totl.
Override and Automatic Return
Operation
Helps to cope with sudden schedule changes without having to
revise the existing program. This function allows ON/OFF states that
were forcibly set using the Output ON/OFF Switch to be maintained
until the next ON/OFF time.
Turn output OFF while maintaining AUTO
operation
1. Change the setting of the Output ON/OFF Switch from AUTO to
OFF.
2. Return the Output ON/OFF Switch from OFF to AUTO
while pressing . (Output remains in the OFF
state.)
3. The regular operation will be performed from the next
ON time.
Turn output ON while maintaining AUTO
operation
1. Change the setting of the Output ON/OFF Switch from AUTO to
ON.
2. Return the Output ON/OFF Switch from ON to AUTO
with pressed. (Output remains in the ON
state.)
3. The regular operation will be performed from the next
OFF time.
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Weekly, 2 Circuits
Yearly, 2 Circuits
Yearly, 4 Circuits
h
SUN
MON
TUE
WED
THU
FRI
SAT SUN
MON
TUE
WED
THU
FRI
SAT
m
Current time
Next operation
(Factory setting)
hour cnt
Total time Total count
(See note.) (See note.)
hour cnt
Current time
Current month and day
(Factory setting)
Total time Total count
(See note.) (See note.)
Current time
Next operation
Current time
Current month and day
(Factory setting)
Current time
Next operation
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
ON
AUTO
OFF
WRITE
ON
AUTO
OFF
WRITE
H5S
23
Using Advanced Functions
About Advanced Functions
Set the advanced functions as required to perform more advanced
operation. Outlines of the advanced functions are provided on the
following pages.
Refer to the Instruction Manual enclosed with the H5S for details.
Initial Setting Mode
Time Counter/Total Counter Display
(F2, F3, F4)
This function displays the total elapsed time and total input count for
an external input.
The alarm indicator can also be displayed if an alarm value has been
set.
Note: For display details, refer to Display Switching on page 22.
.
Input selection (F2)
Set Input selection (F2) in initial setting mode to Time Counter/Total
Counter.
Alarm for time counter (F3)
Alarm for total counter (F4)
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
<2-circuit models>
P1
P2
RUN
P1
P2
RUN
<4-circuit models>
PRGM
RUN
Program setting mode
Initial setting mode
F1:Next operation display
F2:Input selection
*2-circuit models only
F3:Total time alarm
*Only when "totl"
is selected in F2.
F4:Total count alarm
F5:Date format
selection *Yearly models only
F6:Summer time
(DST) adjustment *Yearly models only
F7:Summer time
schedule selection *Yearly models only
Only when "auto"
is selected in F6.
F8:Season switching
*Yearly models only
F9:Period of season
*Yearly models only
Only when "on"
is selected in F8.
TIME ADJ
Press briefly
.
TIME ADJ
or
Press
for 3 s or more.
*Only when "totl"
is selected in F2.
Press briefly
.
TIME ADJ
Press briefly
.
TIME ADJ
Press briefly
.
TIME ADJ
Press briefly
.
TIME ADJ
Press briefly
.
TIME ADJ
Press briefly
.
TIME ADJ
Press briefly
.
TIME ADJ
Press briefly
.
TIME ADJ
Yearly, 2 Circuits Yearly, 2 Circuits
<Resetting the total time and count>
1. Press for 3 s or more while
the total time or count is displayed.
2. Press to reset the total time
and total count
* The resetting is cancelled by pressing
again while “clr” is flashing.
Shaded portion indicates
blinking of the indicator.
1. Press or to change the
display to totl.
2. Press to enter the setting.
Shaded portion indicates
blinking of the indicator.
1. The display will automatically change
to the alarm setting screen 2 s after
switching to F3.
Press the or .
Key: Increments in units of 1,000 h*
Key: Increments in units of 10 h*
Note: The default setting
is 0.0 h (no alarm
display).
2. Press to enter the setting.
* Pressing decrements the value of the
key that was last pressed.
Shaded portion indicates
blinking of the indicator.
1. The display will automatically change
to the alarm setting screen 2 s after
switching to F4.
Press the or .
Key: Increments in units of 10,000*
Key: Increments in units of 100*
Note: The default setting
is 0 (no alarm
display).
2. Press to enter the setting.
* Pressing decrements the value of the
key that was last pressed.
Alarm
indicator
Time counter display
(Example shows display
when the total elapsed time
is 30,000 hours.)
Total counter display
(Example shows display
when the total input
count is 500,000.)
Thecolorindicatesflashing.
CLEAR
WRITE
CLEAR
hm
WRITE
hm
h
m
WRITE
hm
h
m
WRITE
H5S
24
Time Adjustment Input Function (F2)
The time can be set to 00 min 00 s at the same time as external input
is applied. (The hours is rounded up for 30 minutes or higher and
rounded down for 29 minutes or lower.)
When using two or more Time Switches, their times can be
synchronized.
Input selection (F2)
Set Input selection (F2) in initial setting mode to Time Adjustment
Input.
Manual Operation on Recovery from
Power Failure (F2)
After power is restored to the H5S, it is possible to set the Time
Switch to stop turning ON output until external input is applied.
Input selection (F2)
Set Input selection (F2) in initial setting mode to Manual Operation
on Recovery from Power Failure.
Bank Switching (F2)
Two groups (banks) of programs can be registered with the Time
Switch. Banks can be switched by external input.
Input selection (F2)
Set Input selection (F2) in initial setting mode to Bank Switching.
Switching banks in RUN mode
Banks are switched as shown in the following table depending on the
external input state.
Programming a bank
Press in program setting mode to switch banks.
Different programs can be set for each bank.
Season Switching/Period of Season
(F8/F9)
Weekly programs can be set to automatically switch throughout the
year in response to seasons.
* Up to four seasons can be set for 4-circuit models, and up to two
seasons for 2-circuit models.
Season switching (F8)
Turn ON Season switching (F8) in initial setting mode.
Weekly, 2 Circuits Yearly, 2 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press or to change the
display to sync.
2. Press to enter the setting.
Weekly, 2 Circuits Yearly, 2 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press or to change the
display to boot.
2. Press to enter the setting.
hm
WRITE
ON OFF
Flashing
ON
indicator
(in the upper left corner of the screen)
Power
supply
External
input
Output
hm
WRITE
Weekly, 2 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press or to change the
display to bank.
2. Press to enter the setting.
Open-circuited Short-circuited
Bank A B
Yearly, 2 Circuits Yearly, 4 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press or to change the
display to on.
2. Press to enter the setting.
Note: The “C” and “D”
indications are not
displayed in 2-circuit
models.
Bank A
Switching
Weekly programs
13:00 ON
16:00 OFF
Bank B
Weekly programs
8:00 ON
10:00 OFF
hm
WRITE
TIME ADJ
Mar. Apr. May Jun. Jul. Aug. Sept. Oct. Nov. Dec. Jan. Feb.
Spring Summer Autumn Winter
Seasons(*)
Setting
Spring
17:30 ON
21:00 OFF
Summer
19:00 ON
22:00 OFF
Autumn
18:00 ON
21:00 OFF
Winter
17:00 ON
21:00 OFF
hm
WRITE
H5S
25
Period of Season (F9)
Switching seasons
One group of programs is automatically switched to another,
according to the seasons set in initial setting mode.*
* The season switching functions apply only to weekly programs, not
yearly programs.
Programming a season
Press in program setting mode to switch seasons.
Different weekly programs can be set for each season.
Next Operation Display (F1)
The order of the output channels for which the next operation (the
next ON or OFF time) is set can be selected for the sub-display.
This function is useful when an operation in a particular circuit is to
be monitored.
Parameters
- - - - - - - - - - Displays the next operation for circuit 1 only.
only 2 - - - - - - - - - -Displays the next operation for circuit 2 only.
only 3 - - - - - - - - - -Displays the next operation for circuit 3 only.
only 4 - - - - - - - - - -Displays the next operation for circuit 4 only.
all 1234 - - - - - - - - Displays the next operation for all circuits.
Note: 1. Circuits 3 and 4 are not displayed for 2-circuit models.
2. indicate the default.
Setting method
Date Format Selection (F5)
The displayed date format is selectable between “month. day” and
“day. month”.
Parameters
: “month. day”
dd.nn: “day. month”
Note: indicate the default.
Setting method
Summer Time (DST) Adjustment (F6)
Manual or automatic summer time adjustment can be selected.
Parameters
: Manual adjustment
auto: Automatic adjustment (Select summer time schedule in F7.)
Note: indicate the default.
Setting method
Shaded portion indicates
blinking of the indicator.
1. Press or to select the desired
season.
2. Press to enter the setting.
The display then changes to the start
period of season input screen. Press
or to designate the starting
date.
3. Press to enter the setting.
The display then changes to the end
period of season input screen. Press
or to designate the ending
date.
4. Press to enter the setting.
Note:
The following is set as the default period of season.
A: 1.1 to 12.31 (1/1 to 12/31)
B to D: --.-- to --.-- (no setting)
*The “C” and “D” indications are not displayed in 2-circuit models.
If overlapping periods are set, the priority becomes A<B<C<D.
For example, setting A (1/1 to 12/31) and B (4/1 to 9/30) will result in the
following: 1/1 to 3/31: A, 4/1 to 9/30: B, 10/1 to 12/31: A.
All outputs are OFF in the weekly program for all dates that do not come in
any period.
Weekly, 2 Circuits Yearly, 2 Circuits Yearly, 4 Circuits
Shaded portion indicates
blinking of the indicator.
1. Select one of the parameters using
or .
2. Press to enter the setting.
hm
WRITE
M D
WRITE
M D
WRITE
TIME ADJ
only 1
The inverted characters
hm
WRITE
Yearly, 2 Circuits Yearly, 4 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press or to select one of the
parameters.
2. Press to enter the setting.
Yearly, 2 Circuits Yearly, 4 Circuits
Shaded portion indicates
blinking of the indicator.
1. Press or to select one of the
parameters.
2. Press to enter the setting.
mm.dd
The inverted characters
hm
WRITE
off
The inverted characters
hm
WRITE
H5S
26
Summer Time Schedule Selection (F7)
The time and date when the Time Switch automatically switches to
and from summer time can be selected with reference to the
following regions.
Parameters
Note: indicate the default.
Setting method
About the Self Diagnosis Function
The following indications will be displayed when an error is
generated.
Yearly, 2 Circuits Yearly, 4 Circuits
Regions Summer time start
date and time
Summer time end
date and time
(North
America)
At 2:00 on the second
Sunday in March
At 2:00 on the first
Sunday in November
eu (Europe) At 2:00 on the last
Sunday in March
At 3:00 on the last
Sunday in October
aust (Australia) At 2:00 on the last
Sunday in October
At 3:00 on the last
Sunday in March
Shaded portion indicates
blinking of the indicator.
1. Press or to select one of the
parameters.
2. Press to enter the setting.
us
The inverted characters
hm
WRITE
Indication Description Output Remedy
e1 CPU error OFF Press
“RESET”
e2 Memory error OFF Press
“RESET”
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2012.8
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2012 All Right Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
Y92F-90 Y92A-72C H5S-WB2 H5S-WFB2 H5S-YFB4-X H5S-YFB4D-X H5S-YFB2D-X