1
Power Entry Modules with Line Filter FKH
www.schurter.com/PG06
Connectors
IEC Appliance Inlet C14 with Filter, Fuseholder 1-pole, Line Switch 2-pole
Aluminum Nickel plated steel
Standard- or Medical-Filter
C14
70° C
Description
- Panel Mount:
Screw-on mounting from front side
- 4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5␠x␠20␠mm 1␠pole, Line-filter in standard version
- Quick connect terminals 6.3 x 0.8 mm
Approvals
- VDE Certificate Number: 40004665
- UL File Number: E72928
Characteristics
- Compact design with optimal shielding
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
If the power entry module is installed as normal, it is not possible to
touch any live parts with the test-finger according to IEC60529
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- With EMC-shield
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
- Medical version M80
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, Mating Connectors,
e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check, CAD-
Drawings, Accessories, Mounting instruction, Detailed request for
product
Technical Data
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
Leakage Current standard < 0.25 mA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Temp. -25 °C to 85 °C
Climatic Category 25/085/21 acc. to IEC 60068-1
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Quick connect terminals 6.3 x 0.8 mm
Panel Thickness s Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet C14 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C,
10 A, Protection Class I
Fuseholder 1-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
Rated Power Acceptance @
Ta 23 °C
5 x 20: 1.6 W (1 pole)
Power Acceptance @ Ta >
23°C
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Line Switch 2-pole, non-illuminated, acc. to IEC
61058-1
Technical Details
Line Filter Standard Version, IEC 60939, UL 1283,
CSA C22.2 no. 8
Technical Details
MTBF > 1'700'000 h acc. to MIL-HB-217 F
2
Power Entry Modules with Line Filter
FKH www.schurter.com/PG06
Connectors
Dimension
Case 45
40 49 40
R1
6.3x0.8
±0.5
±0.5
28
63
65
R4 61.3
50±0.5
50 67 28.7
±0.5
±0.5
5.5 14 29.5
3.5
ø 3.2
ø 6.3x90°
60.2
61
±0.15
M3
Case 50
40 49.5 40
6.3x0.8
±0.5
±0.5
28
63
65
R4 40.5
50±0.5
50 55 28.7
±0.5
±0.5
5.5 15 29.5
3.5
ø 3.2
ø 6.3x90°
60.2
61
±0.15
M3
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [M]
1Standard Version 2 x 10 68 2.2 1
2Standard Version 2 x 4 68 2.2 1
4Standard Version 2 x 1.5 68 2.2 1
6Standard Version 2 x 0.8 68 2.2 1
10 Standard Version 2 x 0.3 68 2.2 1
1Medical Version (M5) 2 x 10 68 - 1
2Medical Version (M5) 2 x 4 68 - 1
4Medical Version (M5) 2 x 1.5 68 - 1
6Medical Version (M5) 2 x 0.8 68 - 1
10 Medical Version (M5) 2 x 0.3 68 - 1
3
Power Entry Modules with Line Filter FKH
www.schurter.com/PG06
Connectors
Diagrams
Standard version
1) Line
2) only FKI
3) Load
Medical version
N
PE
L
Cx
L1
L2
N’
PE
L’
R
Cx
F2
F1
1)
2)
1) Line␍2) Load
Derating Curves
1-pole
Admissible power accep-
tance in Watt
020406080
100
0.2
0.0
I = << In
I = 0.7 In
I = 1.0 In
1.6
0.6
0.4
0.8
1.2
1.0
1.4
Ambient air temperature Ta °C
Attenuation Loss - - - - differential mode _____ common mode
Standard version
1 A 2 A 4 A 6 A
10 A
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [M]
1Standard Version 2 x 10 68 2.2 1
2Standard Version 2 x 4 68 2.2 1
4Standard Version 2 x 1.5 68 2.2 1
6Standard Version 2 x 0.8 68 2.2 1
10 Standard Version 2 x 0.3 68 2.2 1
1Medical Version (M5) 2 x 10 68 - 1
2Medical Version (M5) 2 x 4 68 - 1
4Medical Version (M5) 2 x 1.5 68 - 1
6Medical Version (M5) 2 x 0.8 68 - 1
10 Medical Version (M5) 2 x 0.3 68 - 1
4
Power Entry Modules with Line Filter
FKH www.schurter.com/PG06
Connectors
Medical version (M5)
1 A 2 A 4 A 6 A
10 A
Variants
Type Rated Current
[A]
Filter-Type Fuseholder Line Switch Housing Material: Housing Comment Order Number
FKH 1 Standard Version 1-pole 2-pole 45 Aluminum - 4304.4041
FKH 2 Standard Version 1-pole 2-pole 45 Aluminum - 4304.4042
FKH 4 Standard Version 1-pole 2-pole 45 Aluminum - 4304.4043
FKH 6 Standard Version 1-pole 2-pole 45 Aluminum - 4304.4044
FKH 10 Standard Version 1-pole 2-pole 45 Aluminum - 4304.4045
FKH 1 Medical Version (M5) 1-pole 2-pole 45 Aluminum - 4304.4046
FKH 2 Medical Version (M5) 1-pole 2-pole 45 Aluminum - 4304.4047
FKH 4 Medical Version (M5) 1-pole 2-pole 45 Aluminum - 4304.4048
FKH 6 Medical Version (M5) 1-pole 2-pole 45 Aluminum - 4304.4049
FKH 10 Medical Version (M5) 1-pole 2-pole 45 Aluminum - 4304.4050
FKH 1 Standard Version 1-pole 2-pole 50 Nickel plated steel - 4304.4001
FKH 2 Standard Version 1-pole 2-pole 50 Nickel plated steel - 4304.4002
FKH 4 Standard Version 1-pole 2-pole 50 Nickel plated steel - 4304.4003
FKH 6 Standard Version 1-pole 2-pole 50 Nickel plated steel - 4304.4004
FKH 10 Standard Version 1-pole 2-pole 50 Nickel plated steel - 4304.4005
Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
Packaging unit 10 Pcs
Accessories
Description
Assorted Covers
Rear Cover
5
Power Entry Modules with Line Filter FKH
www.schurter.com/PG06
Connectors
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder Terminal 4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal 4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal 5091
Appliance Outlet further types to FKH
Connector Overview complete
IEC Connector C15A, Rewireable, Straight 0102
IEC Connector C15A, Rewireable, Straight 0102-G
IEC Connector C15A, Rewireable, Angled 0112
IEC Connector C13, Rewireable, Angled 4012
IEC Connector C13, Rewireable, Straight 4022
Connector further types to FKH ...
The specifications, descriptions and illustrations indicated in this document are based on
current information. All content is subject to modifications and amendments.
11.03.2014