SDR-240 series 240W Single Output Industrial DIN RAIL with PFC Function Features : High efficiency 94% and low power dissipation 150% peak load capability Built-in active PFC function, PF>0.93 Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 UL 508 (industrial control equipment) approved EN61000-6-2(EN50082-2) industrial immunity level Built-in DC OK relay contact 100% full load burn-in test 3 years warranty SE M PQ IF SPECIFICATION SDR-240-24 SDR-240-48 DC VOLTAGE 24V 48V RATED CURRENT 10A 5A CURRENT RANGE 0 ~ 10A 0 ~ 5A RATED POWER 240W 240W PEAK CURRENT 15A 7.5A PEAK POWER Note.6 360W (3sec.) RIPPLE & NOISE (max.) Note.2 50mVp-p 50mVp-p VOLTAGE ADJ. RANGE 48 ~ 55V 1.0% 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% 0.5% LOAD REGULATION 1.0% SETUP, RISE TIME 650ms, 60ms/230VAC HOLD UP TIME (Typ.) 20ms/230VAC VOLTAGE RANGE 88 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 0.94/230VAC TPTC004 IEC62368-1 0.5% LINE REGULATION POWER FACTOR (Typ.) INPUT Bauar t gepruft Sicherheit egel ma ge od o s be wac g www. tuv.com ID 2000000000 EN62368-1 MODEL OUTPUT 47 1.0% 1300ms, 60ms/115VAC at full load 20ms/115VAC at full load 124 ~ 370VDC 0.99/115VAC at full load Note.8 94% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE 2.6A/115VAC 33A/115VAC 1.3A/230VAC 55A/230VAC <1mA / 240VAC Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery >150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds 56 ~ 65V 29 ~ 33V Protection type : Shut down o/p voltage with auto-recovery 955 (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load WORKING TEMP. Note.5 -25 ~ +70 (Refer to "Derating Curve") 20 ~ 95% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & ISOLATION RESISTANCE EMC EMC EMISSION (Note 4) OTHERS 0.03%/ (0 ~ 50) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, TUV EN62368-1, EAC TP TC 004 approved;(meet EN60204-1) I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020, SEMI F47 approved MTBF 169.3K hrs min. DIMENSION 63*125.2*113.5mm (W*H*D) 1.03Kg; 12pcs/13.4Kg/1.06CUFT PACKING NOTE -40 ~ +85, 10 ~ 95% RH MIL-HDBK-217F (25) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6. 3 seconds max., please refer to peak loading curves. 7. Derating may be needed under low input voltage. Please check the derating curve for more details. 8. After 30 minutes of burn-in. 9. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft). File Name:SDR-240-SPEC 2020-04-13 240W Single Output Industrial DIN RAIL with PFC Function SDR-240 series Mechanical Specification Unit:mm 113.5 Case No. 979A 125.2 TB1 DC OK 1 63 DC OK 3 +V ADJ. 2 TB2 1 2 3 4 5 6 + Terminal Pin No. Assignment (TB1) 35 Pin No. 1 2 3 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Assignment FG AC/N AC/L Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4 5,6 Assignment Relay Contact DC OUTPUT +V DC OUTPUT -V Block Diagram DC OK I/P EMI FILTER & RECTIFIERS POWER SWITCHING PFC CIRCUIT RECTIFIERS & FILTER +V -V O.C.P. U.V.P. FG PFC CONTROL O.L.P. PWM & PFC CONTROL DETECTION CIRCUIT O.V.P. DC OK Relay Contact Contact Close PSU turns on / DC OK. Contact Open PSU turns off / DC Fail. Contact Ratings (max.) 30V/1A resistive load. File Name:SDR-240-SPEC 2020-04-13 SDR-240 series 240W Single Output Industrial DIN RAIL with PFC Function Peak Loading (1) (2) 360W 360W 240W 120W 100 sec. 3 sec. 10 sec. 3 sec. Derating Curve Output derating VS input voltage 100 150 90 For 3 sec. (typ.) 112.5 80 70 LOAD (%) LOAD (%) 100 Continuous 75 60 60 50 40 -25 0 10 20 30 40 50 AMBIENT TEMPERATURE () 60 70 (VERTICAL) 88 100 110 135 155 230 264 INPUT VOLTAGE (V) 60Hz File Name:SDR-240-SPEC 2020-04-13