L-4
ELECTRONIC PRODUCTS
Visit www.GemsSensors.com for most current information.
SAFE-PAK SAFE-PAK P/N 144600
Relay
Style
Operating &
Load Voltage
Range
Load
Current
Maximum
Turn-On
Sensitivity
(Typical)1
Turn-Off
Sensitivity
(Typical)1
Voltage
Loss
Operating
Temperature
Range
Output Leakage
Current
Maximum
Switching
Operation
Part
Number
SAFE-PAK®
95 to 135
VAC
5A 400 K 1 M Ω2 VAC 0°F to +120°F
(-17.8°C to +48.9°C)
6 mA
@ 120 VAC SPST N.O. 224455
100 to 135
VAC
6 mA
@ 120 VAC SPST N.C. 258725
200 to 250
VAC
12 mA
@ 250 VAC SPST N.O. 25873
Low Sensitivity
SAFE-PAK®
110 to 130
VAC
.5A @ 20 VAC2
.05A @ 200 VAC2300 1000 Ω-10°F to +140°F
(-23.3°C to +60°C) 0 SPST N.O. 64101
105 to 125
VAC 5A 500 2000 Ω2 VAC -40°F to +120°F
(-40°C to +48.9°C)
6 mA
@ 120 VAC SPST N.O. 144600
7/32˝ DIA. (5.5 mm)
3-1/8˝
(79.4 mm)
1-5/8˝
(41.3 mm)
2-1/4˝
(57.2 mm)
13/16˝
(20.7 mm)
MOUNTING TAB
2-5/8˝
(66.6 mm)
(76.2 mm) 2-5/8˝
(66.6 mm)
(76.2 mm)
7/32˝ DIA.
(5.5 mm)
MOUNTING TAB
1-3/8˝
(35 mm)
1-5/16˝
(33.3 mm)
7/8˝
(22.2 mm)
2-7/8˝
(73 mm)
®
Intrinsically SAFE-PAK® Relays Amplify
Sensor Load-Handling Capabilities
Costly explosion-proof enclosures with their mounting requirements are unnecessary.
No purging is required.
SAFE-PAK: Less than 100 microamps at 9 VDC actuates the unit to control loads to
5A at 120 VAC. Resistive (up to 100,000 ) or short-circuiting sensors operate the
unit. 120 VAC and 240 VAC model.
Low Sensitivity SAFE-PAK: Sensor closures up to 1000 resistance control resistive
loads to 5A at 120 VAC. 120 VAC, N.O. model.
See table on Page L-2 for specific approval information.
Dimensions
How To Order
Select Part Number based on Relay Style, Operating Voltage and Switch Operation required.
P/N
22445
25872
25873
64101
P/N
144600
Notes:
1. Temperature Dependent.
2. 50-60 Hz
3. All AC voltage and current specifications are RMS values unless otherwise stated.
4. Housing material is Polysulfone.
5. Certified intrinsically safe under MSHA certification No. 1662 for use on permissible equipment.
For Group D use only.
Stock Items.
L-5
ELECTRONIC PRODUCTS
Visit www.GemsSensors.com for most current information.
BLACK
RED
N.O. DRY
OR
N.C. DRY
NON-HAZARDOUS
AREA
FUSE
FUSE
LOAD
SAFE-PAK
HOT VAC
NEUTRAL VAC
DC
POWER
SUPPLY
ANNUNC.
(–)
(+)
321
BLACK
RED
2 CONDUCTOR
CABLE
N.O. DRY
OR
N.C. DRY
HAZARDOUS
AREA
NON-HAZARDOUS
AREA
FUSE*
HAZARDOUS
AREA
DC
POWER
SUPPLY
ANNUNC.
(–)
(+)
321
BLACK
RED
2 CONDUCTOR
CABLE
N.O. DRY
OR
N.C. DRY
HAZARDOUS
AREA
NON-HAZARDOUS
AREA
FUSE*
SENSE
RESISTOR
321
SIGNAL RETURN
BARRIER
SUPPLY BARRIER
BLACK
RED
N.O. DRY
OR
N.C. DRY
NON-HAZARDOUS
AREA
LOAD
SAFE-PAK
HOT VAC
NEUTRAL VAC
HAZARDOUS
AREA
INTRINSICaLLy SafE RELayS
Typical Wiring Diagrams
SAFE-PAK, Part Numbers 25872, 25873, 64101 or 144600
with sensor switch in hazardous location.
Transient Protection for SAFE-PAK (AC Loads) Use a properly sized
metal oxide varistor (MOV) as shown below.
Installation and maintenance must be in accordance with the National Electrical
Code and the applicable GEMS INSTRUCTION, INSTALLATION and SERVICE bulletin
available at www.gemssensors.com