New Product Single-phase Current Relay K8AB-AS Ideal for current monitoring for industrial facilities and equipment. * Monitor for overcurrents or undercurrents. * Manual resetting and automatically resetting supported by one Relay. * Startup lock and operating time can be set separately. * One SPDT output relay, 6 A at 250 VAC (resistive load). * Output relay can be switched between normally open and normally closed. * Process control signal (4 to 20 mA) and commercial CT input (0 to 1 A or 0 to 5 A) supported. * Output status can be monitored using LED indicator. * Inputs are isolated from the power supply. Model Number Structure Model Number Legend K8AB-@@ 1 2 3 4 1. Basic Model K8AB: Measuring and Monitoring Relays 2. Functions AS: Single-phase Current Relay (One-sided operation) 3. Measuring Current 1: 2 to 20 mA AC/DC, 10 to 100 mA AC/DC, 50 to 500 mA AC/DC 2: 0.1 to 1 A AC/DC, 0.5 to 5 A AC/DC, 0.8 to 8 A AC/DC 3: 10 to 100 A AC, 20 to 200 A AC (See note.) Note: The K8AB-AS3 is specially designed to be used in combination with the OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.) 4. Supply Voltage 24 VAC/DC: 24 VAC/DC 100-115 VAC: 100 to 115 VAC 200-230 VAC: 200 to 230 VAC Ordering Information List of Models Single-phase Current Relay Measuring current Supply voltage Model 2 to 20 mA AC/DC, 10 to 100 mA AC/DC, 50 to 500 mA AC/DC 24 VAC/DC K8AB-AS1 24 VAC/DC 100-115 VAC K8AB-AS1 100-115 VAC 200-230 VAC K8AB-AS1 200-230 VAC 0.1 to 1 A AC/DC, 0.5 to 5 A AC/DC, 0.8 to 8 A AC/DC 24 VAC/DC K8AB-AS2 24 VAC/DC 100-115 VAC K8AB-AS2 100-115 VAC 200-230 VAC K8AB-AS2 200-230 VAC 10 to 100 A AC, 20 to 200 A AC (See note.) 24 VAC/DC K8AB-AS3 24 VAC/DC 100-115 VAC K8AB-AS3 100-115 VAC 200-230 VAC K8AB-AS3 200-230 VAC Note: The K8AB-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.) 1 K8AB-AS Accessory (Order Separately) OMRON CT Current Transformer Input range 10 to 100 A AC, 20 to 200 A AC Applicable Relay K8AB-AS3 Model K8AC-CT200L Other CTs CT current on secondary side 0 to 1 A AC, 0 to 5 A AC Applicable Relay K8AB-AS2 Ratings and Specifications Input Range Model K8AB-AS1 K8AB-AS2 Range * Connection terminal 0 to 20 mA AC/DC I1-COM 0 to 100 mA AC/DC I2-COM 0 to 500 mA AC/DC I3-COM 0 to 1 A AC/DC I1-COM 0 to 5 A AC/DC I2-COM 0 to 8 A AC/DC I3-COM Measuring current 2 to 20 mA AC/DC, 10 to 100 mA AC/DC, 50 to 500 mA AC/DC Input impedance Approx. 1 Approx. 0.2 Approx. 0.12 (Load : 0.5 VA) 0.1 to 1 A AC/DC, 0.5 to 5 A AC/DC, 0.8 to 8 A AC/DC Overload capacity Approx. 5 Approx. 0.02 (Load : 1.5 VA) Continuous input : 120% of maximum input 1 s max. : 150% of maximum input Approx. 0.02 (Load : 3 VA) Continuous input : 120% of maximum input 30 s max. : K8AB-AS3 200% of maximum input 0 to 200 A AC I3-COM Using OMRON CT 1 s max. : 600% of maximum input Note: The K8AB-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.) * The range is selected using connected terminals. 0 to 100 A AC I2-COM Using OMRON CT 10 to 100 A AC, 20 to 200 A AC (See note.) 2 K8AB-AS Ratings Power supply voltage Isolated power supply 24 VDC, 24 VAC, 100 to 115 VAC, 200 to 230 VAC Power consumption 24 VDC: 24 VAC: 100 to 115 VAC: 200 to 230 VAC: Operating value setting range (SV) 10% to 100% of maximum measuring current K8AB-AS1: 2 to 20 mA AC/DC 10 to 100 mA AC/DC 50 to 500 mA AC/DC K8AB-AS2: 0.1 to 1 A AC/DC 0.5 to 5 A AC/DC 0.8 to 8 A AC/DC K8AB-AS3: When used together with a K8AC-CT200L Current Transformer 10 to 100 A AC 20 to 200 A AC Operating value 100% operation at set value Reset value setting range (HYS.) 5% to 50% of operating value Reset method Operating time setting range (T) 1 W max. 4 VA max. 4 VA max. 5 VA max. Manual reset/automatic reset (switchable) Note: Manual reset: Turn OFF power supply for 1 s or longer. 0.1 to 30 s 0 to 30 s Startup lock time setting range (LOCK) (The startup lock timer starts when the input has reached approximately 30% or more of the set value.) Note: Enabled only for overcurrent operation. Note: Enabled only for overcurrent operation. Indicators Power (PWR): Green, Relay output (RY): Yellow, Alarm outputs (ALM): Red Input impedance Refer to "Input Range" on previous page. Output relays One SPDT relay (NO/NC switched using DIP switch.) Output relay ratings Rated load Resistive load 6 A at 250 VAC (cos = 1) 6 A at 30 VDC (L/R = 0 ms) Inductive load 1 A at 250 VAC (cos = 0.4) 1 A at 30 VDC (L/R = 7 ms) Maximum contact voltage: 250 VAC Maximum contact current: 6 A AC Maximum switching capacity: 1,500 VA Minimum load: 10 mA at 5 VDC Mechanical life: 10,000,000 operations Electrical life: Make: 50,000 times, Break: 30,000 times Ambient operating temperature -20 to 60C (with no condensation or icing) Storage temperature -40 to 70C (with no condensation or icing) Ambient operating humidity 25% to 85% (with no condensation) Storage humidity 25% to 85% (with no condensation) Altitude 2,000 m max. Terminal screw tightening torque 0.49 N*m Terminal wiring method Recommended wire Solid wire: 2.5 mm2 Twisted wires: AWG16, AWG18 Note: 1. Ferrules with insulating sleeves must be used with twisted wires. 2. Two wires can be twisted together. Recommended ferrules Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact Al 1-8RD (for AWG18) manufactured by Phoenix Contact Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact Case color Munsell 5Y8/1 Case material PBT/ABS resin (self-extinguishing resin) UL94-V0 Weight Approx. 130 g Mounting Mounted to DIN Track or via M4 screws (tightening torque: 1.2 N*m) Dimensions 22.5 (W) x 90 (H) x 100 (D) mm 3 K8AB-AS Specifications Allowable power supply voltage range 85% to 110% of power supply voltage Allowable power supply frequency range 50/60 Hz 5 Hz Input frequency range K8AB-AS1 and K8AB-AS2: DC input or AC input (45 to 65 Hz) K8AB-AS3: AC input (45 to 65 Hz) K8AB-AS1 and K8AB-AS2: Continuous input: 120% of maximum input, 1 s max.: 150% of maximum input. K8AB-AS3: Continuous input: 120% of maximum input, 30 s max.: 200% of maximum input, 1 s max.: 600% of maximum input Overload capacity Note: Overload capacity of primary side of CT. Operating value Setting error Reset value Operating time Set value 10% full scale Startup lock time Repeat error Operating value Operating value 2% Error calculation: Error = ((Maximum operating value - Minimum operating value (over 10 operations))/2)/ Average value x 100% Reset value Reset value 2% Error calculation: Error = ((Maximum reset value - Minimum reset value (over 10 resets))/2)/Average value x 100% Operating time Operating time repeat error: 50 ms Overcurrent: Measured when input suddenly changes from 0% to 120% of setting. Undercurrent: Measured when input suddenly changes from 120% to 0% of setting. Startup lock time Startup lock time repeat error: 50 ms (measured at sudden change from 0% to 120% of setting) Temperature influence Operating value Drift based on measured value at standard temperature: -20C to standard temperature: 1,000 ppm/C max. Standard temperature to 60C : 1,000 ppm/C max. (Humidity: 25% to 80%) Operating time Fluctuation based on measured value at standard temperature: -20C to standard temperature: 10% max. Standard temperature to 60C : 10% max. (Humidity: 25% to 80%) Humidity influence Operating value Based on ambient humidity of 65% 25% to 80%: 5% max. Operating time Based on ambient room humidity 25% to 80%: 10% max. Influence of power supply voltage Operating value: 5% max. Operating time: 10% max. Influence of power supply frequency Operating value: 5% max. (at 45 to 65 Hz) Operating time: 10% max. (at 45 to 65 Hz) Note: The error in the operating value and operating time under standard conditions. Note: The error in the operating value and operating time under standard conditions. Influence of input frequency Operating value (45 to 65 Hz) K8AB-AS1 and K8AB-AS2: 5% max. K8AB-AS3: 10% max. Operating time (45 to 65 Hz) 10% max. Note: The error in the operating value and operating time under standard conditions. Applicable standards 4 Conforming standards EMC EN60255-5 and EN60255-6 Installation environment (Pollution Degree 2, Overvoltage Category III) EN61326 Insulation resistance 20 M min. Between external terminals and case Between power supply terminals and input terminals (excluding models with DC power supply) Between power supply terminals and output terminals Between input terminals and output terminals Dielectric strength 2,000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals (excluding models with DC power supply) Between power supply terminals and output terminals Between input terminals and output terminals Noise immunity 1,500 V power supply terminal common/normal mode Square-wave noise of 1 s/100 ns pulse width with 1-ns rise time Vibration resistance Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s2 10 sweeps of 5 min each in X, Y, and Z directions Shock resistance 100 m/s2, 3 times each in 6 directions along three axes (up/down, left/right, forward/backward) Degree of protection Terminal section: Finger protection K8AB-AS Connections Wiring Diagram Overcurrent Operation Diagram (Output Relay Drive Method: Normally Open) Single-phase power Single-phase power DIP switch setting: SW3 OFF. Power supply voltage A1 Hysteresis (-5% to 50% of operating value) A1 Power supply voltage Power supply voltage A2 Operating value Input A2 I1 Current input Flashing Alarm indicator Lit I1 I2 I3 Current input or COM I2 I3 COM Relay 11-14 14 Signal output 12 Relay 11-12 T: Operating time (0.1 to 30 s) T Lock: Startup lock time (0 to 30 s) LOCK Undercurrent Operation Diagram (Output Relay Drive Method: Normally Closed) DIP switch setting: SW3 ON. Power supply voltage Load Relay signal output 14 Signal output 12 11 Relay signal output 11 Load Note: 1. The K8AB-AS3 is designed to be used in combination with the OMRON K8AC-CT200L Current Transformer (CT). 2. There is no polarity when a DC current input is used. 3. Refer to the "Setting Ranges and Wiring Connections" as the explanation of current input l1, l2, and l3 terminal. Operating value Input Alarm indicator Hysteresis (5% to 50% of operating value) Flashing Lit Relay 11-14 Relay 11-12 T T: Operating time (0.1 to 30 s) 5 K8AB-AS Nomenclature Front Indicators Item Terminal block (See notes 1 and 2.) Meaning Power indicator (PWR: Green) Lit when power is being supplied. Relay status indicator (RY: Yellow) Lit when relay is operating. Alarm indicator (ALM: Red) Lit when there is an overcurrent or undercurrent. The indicator flashes to indicate the error status after the input has exceeded the threshold value while the operating time is being clocked. Current knob (SV) Power indicator Relay status indicator Alarm indicator Hysteresis knob (HYS.) Operating time knob (T) Startup lock time knob (LOCK) Terminal block (See notes 1 and 2.) Setting Knobs Item Usage Current knob (SV) Used to set the current to 10% to 100% of maximum measuring current. Hysteresis knob (HYS.) Used to set the rest value to 5% to 50% of the operating value. Operating time knob (T) Used to set the operating time to 0.1 to 30 s. Startup lock time knob Used to set the startup lock time to 0 to (LOCK) 30 s. Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with insulating sleeve for the terminal connection. The length of the exposed current-carrying part inserted into the terminal must be 8 mm or less to maintain dielectric strength after connection. For 2.5 mm2 or smaller solid wires 8 mm max. Recommended ferrules Phoenix Contact * Al 1,5-8BK (for AWG16) * Al 1-8RD (for AWG18) * Al 0,75-8GY (for AWG18) 2. Tightening torque Recommended: 0.49 N*m Maximum: 0.54 N*m 6 For ferrules with insulating sleeves 8 mm max. K8AB-AS Operation and Setting Methods Setting Ranges and Wiring Connections Model K8AB-AS1 K8AB-AS2 K8AB-AS3 Measuring current Wiring connection 2 to 20 mA AC/DC I1-COM 10 to 100 mA AC/DC I2-COM 50 to 500 mA AC/DC I3-COM 0.1 to 1 A AC/DC I1-COM 0.5 to 5 A AC/DC I2-COM 0.8 to 8 A AC/DC I3-COM 10 to 100 A AC (See note 2.) I2-COM 20 to 200 A AC (See note 2.) I3-COM Note: 1. The DC input terminals have no polarity. 2. The K8AB-AS3 is designed to be used in combination with the OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.) Connections 1. Input Connect the input between the I1-COM, I2-COM, or I3-COM terminals, according to the input current. Malfunctions may occur if the input is connected to unused terminals and the Unit will not operate correctly. Terminal I1 is not used by the K8AB-AS3. If using the OMRON K8AC-CT200L CT, connect to terminals k and l on the K8AC-CT200L. (Terminals kt and lt are not used.) 2. Power Supply Connect the power supply to terminals A1 and A2. 3. Outputs SPDT relays are output to terminals 11, 12, and 14. Note: Use the recommended ferrules if using twisted wires. Single-phase power K8AB-AS3 A1 Power supply voltage A2 K8ACCT200L k Current input I1 I2 I3 COM l 14 Signal output 12 11 Relay signal output Load DIP Switch Settings The resetting method, relay drive method, and operating mode are set using the DIP switch located on the bottom of the Unit. K8AB-AS@ does not use SW1. DIP Switch Functions ON SWITCH OFF OFF Resetting method SW1 SW2 SW3 SW4 ON DIP switch 4 ON 2 1 OFF Automatic reset --- --- Manual reset --- --- --- --- --- --- --- --- --- --- Normally Relay drive method closed Normally open Operating mode 3 Undercurrent Overcurrent Note: All pins are set to OFF at the factory. NO USE Setting Method 1. Setting Current The current knob (SV) is used to set the current. The current can be set to 10% to 100% of the maximum measuring current. Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.) Use this as a guide to set the current. The maximum measuring current will differ depending on the model and the input terminal. Example: K8AB-AS3 Using Input Terminals I3-COM The maximum measuring current will be 200 A AC and the setting range will be 20 to 200 A. 7 K8AB-AS 2. Hysteresis Hysteresis is set using the hysteresis knob (HYS.) The setting range is 5 to 50% of the operating value. Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.) Use this as a guide to set the hysteresis. Example: Maximum of 200 A AC, Current Setting (SV) of 50%, and Overcurrent Operation Operation will be at 100 A and resetting at 90 A when the hysteresis (HYS.) is set to 10%. 3. Operating Time The operating time is set using the operating time knob (T). The operating time can be set to between 0.1 and 30 s. Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.) Use this as a guide to set the operating time. If the input current exceeds (drops lower than) the current setting, the alarm indicator will start flashing for the set period and then stay lit. 4. Startup Lock Time Inrush current The startup lock time is set using the startup lock time knob (LOCK). The startup lock time can be set to between 0 and 30 s. Current setting Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.) Use this as a guide to set the startup lock time. 30% of current setting The startup lock time will start when the input current reaches 30% or more of the current Startup lock time setting. There are no outputs Use startup lock time to prevent unwanted operation, e.g., as a result of inrush current. Startup lock timer start during this period. Dimensions (Unit: mm) Single-phase Current Relays K8AB-AS1 K8AB-AS2 K8AB-AS3 22.5 5 100 90 72 5 OMRON CT K8AC-CT200L 9.3 9.3 1.7 1.7 11 4.7 63 54 Four M4 x 6 screws 20 Mounting Hole Dimensions 17 50 8.5 13.5 Two M5 screw holes or two 5.5-dia. holes 34.5 81.5 76 33.5 6 14.5 57 86 30 dia. 14.5 5.2 10 10 20 1.8 4.1 8 76 5.9 Note: The OMRON Current Transformer (CT) is designed to be used with the K8AB-AS3. Use terminals k and l for connections. (Terminals kt and lt are not used.) K8AB-AS Questions and Answers Q Checking Operation Overcurrents Gradually increase the input from 80% of the setting. The input will equal the operating value when the input exceeds the setting and the alarm indicator starts flashing. Operation can be checked by the relay outputs that will start after the operating time has passed. Undercurrent Gradually decrease the input from 120% of the setting and check the operation using the same method as for overcurrent. Example: Overcurrent Operating Mode, Normally Open Relay Drive, and an Operating Time of 5 s Set value Current input 5s Relay output Connection Diagram A 100 VAC 0 to 10 A 30 400 W (two in parallel) Output Input terminals Power supply Variable autotransformer Use a screwdriver to turn the knobs. There is a stopper to prevent the knob from turning any further once it has been turned completely to the left or right. Do not force the knob past these limits. Q Can a motor with a rated current of 5 A be monitored using the K8AB? Are there any application precautions? The K8AB-AS1 and K8AB-AS2 cannot be used with motor loads. Use the K8AB-AS3 in combination with the K8ACCT200L Current Transformer (CT). With motor loads, the startup current and stall current will cause a current of many times the rated current to flow. Refer to the following figure for information on the motor startup current. Lit Flashing Alarm indicator Operating Adjustment Knobs A1 A2 Motor current (percentage of rated value) Q 500% 100% Several seconds to several tens of seconds Time from beginning of startup 100 VAC C 100 V Cycle counter Q For a motor with a rating of 5 A, the startup current will be approximately 30 A. The startup current will exceed the overload capacity (rating: 150% for 1 s) of the K8AB-AS1 and K8AB-AS2 and result in failure of the Relay. To monitor the motor load, use the K8AB-AS3. (Overload capacity: 120% of rating for continuous load, 200% of rating for 30 s, and 600% of rating for 1 s). The K8AB-AS3 has a large input range. Pass the conductors multiple times through the special CT. How to Measure the Operating Time Overcurrent Change the input suddenly from 0% to 120% of the set value and measure the time until the Unit operates. Undercurrent Change the input suddenly from 120% to 0% of the set value and measure the time until the Unit operates. Primary-side conductor To the K8AB-AS3 K8AC-CT200L Concept behind Passing Conductor through the CT When Using the K8AB-AS3 Example: Monitoring Overload of a Motor with a Rated Current of 5 A Q Monitoring Switch-mode Power Supplies Switch-mode Power Supplies cannot be monitored. In circuits with a capacitor input, including switch-mode power supplies, the input capacitor recharge current flows in pulse form as the load current. The K8AB-AS@ has a built-in filter as a countermeasure against high frequencies and cannot be used to remove pulse current. K8AB settings: Overcurrent detection, operating value setting: 25%, operating time: 0.1 s Startup lock timer: 0.1 to 30 s (Set the timer according to the duration of the startup current.) The setting range for the K8AB-AS3 is 10% to 100% of the rated current (i.e., 10 to 100 A). Pass the conductors through the CT five times so that at least 10 A of current flows. The input current to the K8AB will be 25 A (i.e., 5 A x 5 loops). If a startup current of six times the rated current is generated, it will be 150 A (i.e., 25 A x 6). The overload capacity for the K8AB-AS3 is 200% of the rating for 30 s. The Relay will not fail even if the startup current continues for 30 s, and it is possible to perform overload detection. 9 K8AB-AS 10 K8AB-AS 11 Warranty and Application Considerations Read and Understand this Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used. Know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Disclaimers PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your OMRON representative at any time to confirm actual specifications of purchased product. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. OMRON Corporation Industrial Automation Company Authorized Distributor: Tokyo, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 (c) OMRON Corporation 2005 All Rights Reserved. In the interest of product improvement, specifications are subject to change without notice. CSM_1_3_1209 Cat. No. N142-E1-03 0308(0505)