SmartWire-DT
XV Series HMI-PLC
with SmartWire-DT
9.1 SmartWire-DT Panel Wiring Solution
System Overview
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-2
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-2
System Overview Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-3
System Components
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-6
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-8
System Controllers
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-11
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-11
Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-11
Contactor Modules
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-12
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-12
Product Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-13
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-14
Pilot Device Modules
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-15
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-15
Product Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-16
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-18
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-34
V7-T9-2 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
SmartWire-DT Panel Wiring Solution
Contents
Description Page
SmartWire-DT Panel Wiring Solution
System Components . . . . . . . . . . . . . . . . . . . . V7-T9-6
System Controllers . . . . . . . . . . . . . . . . . . . . . V7-T9-11
Contactor Modules . . . . . . . . . . . . . . . . . . . . . V7-T9-12
Pilot Device Modules . . . . . . . . . . . . . . . . . . . . V7-T9-15
Technical Data and Specifications . . . . . . . . . . V7-T9-20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-34
System Overview
Product Description
The SmartWire-DT system
uses a continuous green
flat cable located in the
control cabinet to connect
motor starters, pushbutton
actuators, and indicator lights.
It eliminates the need for
most of the conventional
point-to-point control wiring—
and even integrates 24 Vdc
control power for contactor
coils on the eight conductor
flat cable. The start of the
SmartWire-DT system is a
gateway—it establishes the
connection to standard
programmable logic controller
(PLC) fieldbuses, such as
EtherNet/IP, Modbus TCP,
PROFIBUS-DP and CANopen.
Because SmartWire-DT directly
integrates the input/output
(I/O) level in the switching
devices, no conventional PLC
I/O modules are needed—
instead communication
enabled modules are attached
to standard Eaton motor
control components. Thus,
the PLC in the control cabinet
simply consists of a central
processing unit (CPU) module.
Typical faults such as loose
connections and miswired
terminations are eliminated
using the flat cable and the
specialized connectors.
Furthermore, each
SmartWire-DT enabled device
has individual
diagnostic LEDs
built in, which r
educe
commissioning time and
troubleshooting in the field.
Nodes on the SmartWire-DT
network are automatically
assigned addresses on the
gateway with the push of a
button—assigning addresses
in the order that the nodes
are connected. The system
employs time monitoring
and a watchdog timeout
using the established
target configuration as a
reference—safely monitoring
the integrity of the control
scheme. SmartWire-DT has
a maximum network length
of 2000 ft, can be extended
to pushbutton control stations
outside of the control cabinet,
and can connect up to
99 nodes per gateway. A
software program called
SWD-Assist enables the
layout, planning, and
system configuration of a
SmartWire-DT network.
Features
Connects directly to
standard XTCE contactors,
XTRE control relays, and
M22 pilot devices
Supports EtherNet/IP,
Modbus TCP,
PROFIBUS-DP and
CANopen fieldbuses
Supports up to 99 nodes
on Ethernet and CANopen,
and 58 nodes on
PROFIBUS-DP
Automatically assigns
addresses to SmartWire-DT
nodes
Integrates and supplies
24 Vdc power to contactor
and relay coils over the
network
Includes diagnostic bi-color
LEDs on each node
connection
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-3
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
System Overview Diagram
SmartWire-DT Connection System
Item
Number Description
Item
Number Description
1Gateway to PLC fieldbus network 9Round cable
2Flat cable 10 Pilot device control station
3Modules for XT contactors with XTPR manual motor protectors 11 Emergency stop control station
4Powerfeed module 1 (optional 24 Vdc power feeder) 12 Cabinet cable adapter plug
5Modules for XT contactors with XTPE electronic manual motor protectors 13 Powerfeed module 2 (optional 15 Vdc and 24 Vdc power feeder)
6Digital I/O module 14 Digital I/O module (for connection of sensors and actuators)
7Modules for M22 pilot devices 15 Terminating resistor
8Cabinet cable adapter socket
7
10 11
9
8
45 6
3
2
1
14
12
13 5 3
15
7
V7-T9-4 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
System Components Overview
Future Product
Future Products
13
12
10
10
5
6
5
2
4
1
4
3
5555
5
55
15 16
17
19
18
8
9
911
7
5
5
17
17
18
19
19 32
44
14
4
20
21
22
21
31
22 25
24
23
24
24
26
4
4
5
55
29
27
27 27
30
28
28
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-5
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Item
Number Description
Item
Number Description
1Programmable logic controller (PLC) 17 M22 mounting adapter
2Gateway 18 SmartWire-DT M22 modules
3XV HMI-PLC 19 M22 pilot devices
4Flat plugs 20 Cabinet cable adapter
5Device plug 21 Plug connector
6I/O modules 22 M22 surface mounting enclosure
7Contactor module 23 PCB module for M22 pushbutton stations
8XT Contactors 24 M22 modules, base mount
9Contactor module with HOA switch 25 Universal module, base mount
10 XTPR manual motor controller 26 Adapter for flat/round cable for DIN rail mounting
11 PKE contactor module 27 XTPE module (manual motor protection)
12 XTPE manual motor controller 28 XTPE manual motor protector
13 Soft starter DS7 with electronic motor protection from XTPE 29 Terminating resistor
14 Powerfeed module 30 DS7 soft starters
15 Universal module, front mount 31 Round cable, 8-pole
16 M22 LED elements, front mount 32 SmartWire-DT configuration software, SWD-Assist
V7-T9-6 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
System Components
Contents
Description Page
System Components
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V7-T9-7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-8
System Controllers . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-11
Contactor Modules . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-12
Pilot Device Modules . . . . . . . . . . . . . . . . . . . . . . V7-T9-15
Technical Data and Specifications . . . . . . . . . . . . . V7-T9-20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-34
System Components
Product Description
The start of the SmartWire-DT
system is a gateway module.
The gateway connects as a
node to a programmable
logic controller (PLC) fieldbus.
The PLC used must have a
fieldbus polling master
module or input/output (I/O)
scanner card so that the
gateway can connect as a node
on the fieldbus network.
SmartWire-DT can connect to
EtherNet/IP, Modbus TCP,
PROFIBUS-DP and CANopen
fieldbuses.
To plan and lay
out a SmartWire-DT
network, a MS Windows
compatible software
program called SWD-Assist
is available as a free
download from the Eaton
website. The
SWD-Assist
configuration software will
calculate the control power
requirements needed and
generate a bill of materials of
all the required components.
Gateway Modules
Gateway modules connect
the SmartWire-DT system to
the PLC. They are connected
as nodes to the existing PLC
fieldbus and are the start of
the SmartWire-DT connection
system. Gateways are
available with Ethernet,
PROFIBUS-DP and CANopen
protocols.
Powerfeed Modules
Powerfeed modules feed
auxiliary 24 Vdc power and/or
15 Vdc network power into
the SmartWire-DT flat cable.
The auxiliary 24 Vdc power is
needed for the power supply
of contactors and the 15 Vdc
network power is used for
supplying power to additional
SmartWire-DT nodes.
Powerfeed modules are also
used to create zone control or
groups of devices controlled
by a single Emergency Stop.
Digital and Analog I/O Modules
Digital and analog I/O modules
are connected as nodes on
the SmartWire-DT network
and allow standard or generic
devices to be connected to
the SmartWire-DT system.
They can be connected
anywhere along the flat cable
network and can therefore be
positioned in the control
panel to help reduce the
I/O wiring.
Contactor Modules
Contactor modules fit into
standard XT contactors and
control relays directly on top,
in place of a top mounted
auxiliary contact block. The
modules fit all XTCE size B
and C frame contactors and
XTRE control relays.
Pilot Device Modules
Pilot device modules fit into
standard M22 pilot devices in
both front mount and base
mount configurations. Single
and double contact modules
with and without LEDs are
available to meet a wide
variety of control circuit
requirements.
Flat and Round Cables
The flat cable is an 8 AWG 24
conductor cable that is flexible,
durable, and rated for 600V so
that it can be placed in the
panel wiring duct along with
480V or 600V power
conductors. It has two
prominent features: (a) arrows
indicating the front of the cable
and the direction away from
the gateway and (b) black
edging indicating the polarity
of the flat cable, the 15 Vdc
wire and the reference mark
for installing the device plugs
and flat plugs.
The round cable has 4 AWG
20 and 4 AWG 24 wires and
is 300V rated. It is used
outside the control panel to
connect peripherals such as
pushbutton control stations
to the SmartWire-DT
network. Cable adapters are
available to transition a flat
cable to a round cable
connection and IP67 type
connectors are available to
provide quick-disconnect
cable connections on the
round cable.
Other System Accessories
Other accessories for the
SmartWire-DT system
include connectors, jumpers,
bushings, plugs, and sockets,
flat to round cable adapters
and crimping tools.
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Product Selection
Gateway Modules
Gateway modules connect the SmartWire-DT system to the programmable logic controller (PLC). They are
connected as nodes to the existing PLC fieldbus and are the start of the SmartWire-DT connection system.
Powerfeed Modules
Powerfeed modules feed auxiliary 24 Vdc power and/or 15 Vdc network power into the SmartWire-DT flat cable.
The auxiliary 24 Vdc power is needed for the power supply of contactors and the 15 Vdc network power is used for
supplying power to additional SmartWire-DT nodes. Powerfeed modules are also used to create zone control or
groups of devices controlled by a single Emergency Stop.
Digital I/O Modules
Digital input/output (I/O) modules are connected as nodes on the SmartWire-DT network and allow standard or
generic devices to be connected to the SmartWire-DT system. They can be connected anywhere along the flat
cable network and can therefore be positioned in the control panel to help reduce the I/O wiring.
Analog I/O Modules
Analog input/output (I/O) modules are connected as nodes on the SmartWire-DT network and allow standard or
generic devices to be connected to the SmartWire-DT system. They can be connected anywhere along the flat
cable network and can therefore be positioned in the control panel to help reduce the I/O wiring.
Description Pkg. Qty. Catalog Number
Ethernet Gateway
Connection to EtherNet/IP or Modbus TCP
Automatic baud rate detection 10/100 Mbps
Address set with DIP switch or DHCP
Two RJ45 sockets
Connection of up to 99 SmartWire-DT nodes
1 EU5C-SWD-EIP-MODTCP
PROFIBUS-DP Gateway
Automatic baud rate detection from 9.6 Kbps to 12 Mbps
Address range 1–126
9-pole SUB-D socket
Connection of up to 58 SmartWire-DT modes
1 EU5C-SWD-DP
CANopen Gateway
Automatic baud rate detection from 10 Kbps to 1 Mbps
Address range 1–32
9-pole SUB-D socket
Connection of up to 99 SmartWire-DT modes
1 EU5C-SWD-CAN
Description Pkg. Qty. Catalog Number
Powerfeed module 1 (for 24 Vdc auxiliary power) 1 EU5C-SWD-PF1-1
Powerfeed module 2 (for 24 Vdc auxiliary power and 15 Vdc network power) 1 EU5C-SWD-PF2-1
Description Pkg. Qty. Catalog Number
Digital module with 8 digital inputs 24 Vdc 1 EU5E-SWD-8DX
Digital module with 4 digital inputs 24 Vdc three-wire connections 1 EU5E-SWD-4DX
Digital module with 8 digital outputs 24 Vdc 10.5A 1 EU5E-SWD-X8D
Digital module with 4 digital inputs 24 Vdc and 4 transistor outputs 24 Vdc/0.5A 1 EU5E-SWD-4D4D
Digital module with 4 digital inputs 24 Vdc and 2 relay outputs 250 Vac 1 EU5E-SWD-4D2R
Description Pkg. Qty. Catalog Number
Analog module with 4 analog inputs 0–10V or 0–20 mA 1 EU5E-SWD-4AX
Analog module with 2 analog inputs 0–10V or 0–20 mA and 2 analog outputs 0–10V or 0–20 mA 1 EU5E-SWD-2A2A
RTD module with 4 temperature inputs PT100, PT1000 or Ni1000 1 EU5E-SWD-4PT
Gateway Module
Powerfeed Module
Digital I/O Module
Analog I/O Module
V7-T9-8 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Accessories
System Accessories
Accessories for the SmartWire-DT system includes cables, connectors, jumpers, bushings, plugs, sockets,
flat to round cable adapters, and crimping tools.
Description Length Pkg. Qty. Catalog Number
Flat Cable, 8 AWG 24, 600V
For SmartWire-DT network inside the control panel 328.1 ft (100m) 1 SWD4-100LF8-24
Complete with flat plugs SWD4-8MF2 installed at both ends 9.8 ft (3m) 1 SWD4-3LF8-24-2S
16.4 ft (5m) 1 SWD4-5LF8-24-2S
32.8 ft (10m) 1 SWD4-10LF8-24-2S
Round Cable, 4 AWG 20 and 4 AWG 24, 300V
For SmartWire-DT network outside of the control panel 164.0 ft (50m) 1 SWD4-50LR8-24
Universal (Placeholder) Modules
Front mount 20 M22-SWD-NOP
Base mount 20 M22-SWD-NOPC
Device Plugs
For connection to SmartWire-DT modules or nodes 10 SWD4-8SF2-5
Flat Plugs
For connection to SmartWire-DT system components: gateways, powerfeed
modules, coupling and terminating resistor
—10SWD4-8MF2
Flat Cable
SWD4-8SF2
SWD4-8SF2 SWD4-8S
Round Cable
Device Plug
Flat Plug
Universal—Front
Universal—Base
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
System Accessories, continued
Description Pkg. Qty. Catalog Number
Device Plug Jumpers
For bridging open, spare or inverted device plugs 5 SWD4-SEL8-10
Control Station PCB Jumpers
For bridging open mounting locations on the control station printed
circuit board
5M22-SWD-SEL8-10
Coupling
For connecting or joining flat cables with flat plugs 1 SWD4-8SFF2-5
Terminating Resistor
For terminating the end of the network on a flat cable 1 SWD4-RC8-10
Panel Cable Adapter
For flat cable (plug) to round cable terminals 1 SWD4-8FRF-10
Cabinet Cable Adapter Socket
For flat cable (plug) to round cable (plug) 1 SWD4-SFL8-20
Cabinet Cable Adapter Plug
For flat cable (plug) to round cable (socket) 1 SWD4-SML8-20
PCBs
For surface mounting M22 enclosures and for base-mount pilot device modules
Includes a built-in switchable terminating resistor
Element enclosure PCB 1 1 M22-SWD-I1-LP01
Element enclosure PCB 2 1 M22-SWD-I2-LP01
Element enclosure PCB 3 1 M22-SWD-I3-LP01
Element enclosure PCB 4 1 M22-SWD-I4-LP01
Element enclosure PCB 6 1 M22-SWD-I6-LP01
Adapter Socket
Adapter Plug
PCB
IN
OUT
OFF
ON
Device Plug Jumper
PCB Jumper
Coupling
+ 15V
SWD4-8SFF2-5
Terminating Resistor
+ 15V
SWD4-RC8-10
Adapter
1 2 3 4 5 6 7 8
+ 15 V
V7-T9-10 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
System Accessories, continued
Description Pkg. Qty. Catalog Number
Connectors for Round Cables
Round cable 8-pole socket 1 SWD4-SF8-67
Round cable 8-pole plug 1 SWD4-SM8-67
Right angle round cable 8-pole socket 1 SWD4-SF8-67W
Right angle round cable 8-pole plug 1 SWD4-SM8-67W
Enclosure Bushings
Enclosure bushing, 8-pole socket, M20 1 SWD4-SF8-20
Enclosure bushing, 8-pole plug, M20 1 SWD4-SM8-20
Cord Grip
Round cable cord grip, M20 1 V-M20
Crimping Tool
Device plug crimping tool 1 SWD4-CRP-1
Flat plug crimping tool 1 SWD4-CRP-2
Connector Socket
Connector
(Right Angle)
Bushing Socket
Bushing Plug
Cord Grip
Device Plug Tool
Flat Plug Tool
Connector Plug
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-11
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
System Controllers
Contents
Description Page
System Components . . . . . . . . . . . . . . . . . . . . . . . V7-T9-6
System Controllers
Contactor Modules . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-12
Pilot Device Modules . . . . . . . . . . . . . . . . . . . . . . V7-T9-15
Technical Data and Specifications . . . . . . . . . . . . . V7-T9-20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-34
System Controllers
XV Series HMI-PLC with SmartWire-DT
Product Description
The XV HMI-PLC controller
with SmartWire-DT™ master
is a powerful combination
of logic, visualization and
connectivity to motor control
devices. It is ideal for small to
mid-range PLC applications
where integrated logic and
visualization is advantageous
and/or where remote
administration is critical. The
SmartWire-DT master can
accept 99 nodes on a 2000
foot-long network.
Features
Built-in SmartWire-DT
master for 99 nodes
Brilliant image display with
65,536 colors
High resolution resistive
touch TFT displays
3.5 in, 5.7 in or 7 in
widescreen displays in
robust plastic housings
and bezels, or
5.7 in, 8.4 in or 10.4 in
displays in high-end
aluminum front bezels
and metal housings
Ethernet and RS485 serial
ports on all models
PROFIBUS-DP or
CANopen master on all
models larger than 3.5 in
Programmable with
IEC 61131-3 compliant
XSoft-CoDeSys software
Easy connection direct to
motor control components
or I/O modules on
SmartWire-DT flat cable
Standards and Certifications
CE
UL
cUL
RoHS
Note: For product selection of XV Series HMI-PLCs with SmartWire-DT,
see Tab 4 in this volume.
V7-T9-12 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Contactor Modules
Contents
Description Page
System Components . . . . . . . . . . . . . . . . . . . . . . V7-T9-6
System Controllers . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-11
Contactor Modules
Product Identification . . . . . . . . . . . . . . . . . . . . V7-T9-13
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V7-T9-14
Pilot Device Modules . . . . . . . . . . . . . . . . . . . . . . V7-T9-15
Technical Data and Specifications . . . . . . . . . . . . . V7-T9-20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-34
Contactor Modules
Product Description
Contactor modules fit onto
standard XT contactors and
control relays directly on top,
in place of a top mounted
auxiliary contact block. The
modules fit all XTCE size B
and C frame contactors and
XTRE control relays.
These modules facilitate
direct connection to the
SmartWire-DT flat cable and
eliminate the traditional point-
to-point wiring to the PLC
input and output modules as
well as wiring to the
contactor coils.
Features
Integrated 24 Vdc coil
power on network and
plug-in modules
Integrated switch position
polling
Integrated mechanical
switch position display
Integrated feedback circuit
to PLC
Built-in diagnostic bi-color
LEDs on each module
Connection to SmartWire-DT
flat cable via quick
disconnect device plugs
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-13
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Product Identification
SmartWire-DT Contactor Modules
Item
Number Description
1Flat cable
2Terminating resistor (SWD4-RC8-10)
3Device plug (SWD4-85F2-5)
4Modules for XT contactors with XTPR manual motor protectors, with 1-0-A switch (DIL-SWD-32-002)
5Modules for XT contactors with XTPR manual motor protectors (DIL-SWD-32-001)
6Device plug jumper (SWD4-SEL8-10)
21
45 6
13
V7-T9-14 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Product Selection
Contactor Modules 123
SmartWire-DT module for attachment to XTCE007–XTCE032 contactors and XTRE control relays.
One module is required per contactor.
PKE Contactor Module
SmartWire-DT module for connection of XTPE manual motor controllers.
One module is required per contactor and XTPE manual motor protector.
Design Note
The number of motor starters or XTCE contactors that can be connected is dependent
upon the power consumption of the contactor coils. To increase the number of
SmartWire-DT modules that can be connected. Powerfeed modules can be used.
Notes
1 Take account of the maximum current consumption of the contactor coils per SmartWire-DT line.
2 A2 connections must not be linked.
3 Connection terminals for electrical interlocking are not suitable for safety technology.
Description Pkg. Qty. Catalog Number
Two digital inputs for voltage-free contacts.
One electrical interlock for the surface mounting of reversing combinations.
Messages: Switch status contactor, status of the digital inputs 1 and 2.
Commands: Contactor actuation.
5 DIL-SWD-32-001
Two digital inputs for voltage-free contacts.
One electrical interlock for the surface mounting of reversing combinations.
1-0-A switch for manual or automatic operation.
Messages: Contactor switching position, status of the digital inputs 1 and 2, 1-0-A switch position.
Commands: Contactor actuation.
5 DIL-SWD-32-002
Description Pkg. Qty. Catalog Number
Connecting cable between module and XTPE trip block included as standard.
One electrical interlock for the surface mounting of reversing starters.
1-0-A switch for manual or automatic operation.
Selectable overload relay function for connecting the contactor on overload.
Messages:
Switch position contactor/PKE/1-0-A switch
Motor current in %
Thermal motor image in %
Trip-indicating auxiliary contact (Overload, Short-circuit,...)
Set value of overload releases
Set value Verification time (CLASS), Part no. Trip block.
Commands: Contactor actuation, activation of overload relay function (ZMR)
4 PKE-SWD-32
24 Vdc XTCE007 XTCE009 XTCE012 XTCE015 XTCE018 XTCE025 XTCE032
Pick-up power W 3 3 4.5 4.5 12 12 12
Sealing power W 3 3 4.5 4.5 0.5 0.5 0.5
Contactor Modules
PKE Contactor Module
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-15
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Pilot Device Modules
Contents
Description Page
System Components . . . . . . . . . . . . . . . . . . . . . . . V7-T9-6
System Controllers . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-11
Contactor Modules . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-12
Pilot Device Modules
Product Identification . . . . . . . . . . . . . . . . . . . . V7-T9-16
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V7-T9-18
Technical Data and Specifications . . . . . . . . . . . . . V7-T9-20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V7-T9-34
Pilot Device Modules
Product Description
Pilot device modules fit onto
standard M22 pilot devices in
both front mount and base
mount configurations. Single
and double contact modules
with and without LEDs are
available to meet a wide
variety of control circuit
requirements.
These modules facilitate
direct connection to the
SmartWire-DT flat cable and
eliminate the traditional point-
to-point wiring to the PLC
input and output modules.
Features
Front or base mount
modules
Built-in diagnostic bi-color
LEDs on each module
Connection to SmartWire-DT
flat cable via quick
disconnect device plugs
V7-T9-16 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Product Identification
Pilot Device Modules Connections
1
18
20
22
17
16
17
21
19
14
15
1
2
3
4
1
5
6
8
7
10
11
12
13
9
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-17
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Pilot Device Modules Connections
Item
Number Description
1M22 contact module, front mount (M22-SWD-KC22)
2M22 LED module, front mount (M22-SWD-LED_)
3Module, front mount (M22-SWD-K11)
4M22 contact module with LED, front mount (M22-SWD-K11LED_)
5M22 contact module with LED, front mount (M22-SWD-K22LED_)
6Device plug jumper (SWD4-SEL8-10)
7Device plug (SWD4-85F2-5)
8Flat cable
9M22 LED module, base mount (M22-SWD-LEDC_)
10 M22 contact module, base mount (M22-SWD-KC11)
11 M22 contact module with LED, base mount (M22-SWD-K11LEDC_)
12 M22 contact module, base mount (M22-SWD-KC22)
13 M22 contact module with LED, base mount (M22-SWD-K22LEDC_)
14 1 element enclosure PCB (M22-SWD-I1-1P01)
15 M22 control station enclosure with M20 knockouts
16 Control station PCB jumper (M22-SWD-SEL8-10)
17 Round cable
18 Round cable plug (SWD4-SM8-67)
19 Enclosure bushing socket (SWD4-SF8-20)
20 Round cable socket (SWD4-SF8-67)
21 Enclosure bushing plug (SWD4-SM8-20)
22 M20 cord grip (V-M20)
V7-T9-18 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Product Selection
M22 Pilot Device Modules Connections
M22 Contact Modules, without LEDs
Number of
Changeover
Contacts
Contact
Sequence
Contact Travel Diagram
Stroke in Connection
with Front Element Configuration Pkg. Qty. Catalog Number
Front Mount
120M22-SWD-K11
210M22-SWD-K22
Base Mount
120M22-SWD-KC11
210M22-SWD-KC22
M22-SWD-K11
M22-SWD-K22
M22-SWD-KC11
M22-SWD-KC22
0 1.2 2.8 5.5
0 1.2 2.8 5.5
0 1.2 2.8 5.5
0 1.2 2.8 5.5
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-19
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
M22 Contact Modules, with LEDs
M22 LED Modules
Number of
Changeover
Contacts
Contact
Sequence
Contact Travel Diagram
Stroke in Connection
with Front Element Configuration Color LED Pkg. Qty. Catalog Number
Front Mount
120 M22-SWD-K11LED-W
M22-SWD-K11LED-B
M22-SWD-K11LED-G
M22-SWD-K11LED-R
210 M22-SWD-K22LED-W
M22-SWD-K22LED-B
M22-SWD-K22LED-G
M22-SWD-K22LED-R
Base Mount
120 M22-SWD-K11LEDC-W
M22-SWD-K11LEDC-B
M22-SWD-K11LEDC-G
M22-SWD-K11LEDC-R
210 M22-SWD-K22LEDC-W
M22-SWD-K22LEDC-B
M22-SWD-K22LEDC-G
M22-SWD-K22LEDC-R
Configuration Color LED Pkg. Qty. Catalog Number
Front Mount
20 M22-SWD-LED-W
M22-SWD-LED-B
M22-SWD-LED-G
M22-SWD-LED-R
Base Mount
20 M22-SWD-LEDC-W
M22-SWD-LEDC-B
M22-SWD-LEDC-G
M22-SWD-LEDC-R
M22-SWD-K11LED_
M22-SWD-K22LED_
M22-SWD-K11LEDC_
M22-SWD-K22LEDC_
0 1.2 2.8 5.5
0 1.2 2.8 5.5
0 1.2 2.8 5.5
0 1.2 2.8 5.5
312
M22-SWD-LED_
M22-SWD-LEDC_
V7-T9-20 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Technical Data and Specifications
XV Series HMI-PLCs
Model XV-102 XV-152
Screen Size 3.5 in 5.7 in 7.0 in 5.7 in 8.4 in 10.4 in
Operating system WinCE 5.0 Professional WinCE 5.0 Professional WinCE 5.0 Professional WinCE 5.0 Professional WinCE 5.0 Professional WinCE 5.0 Professional
Touchscreen technology Resistive Resistive Resistive Resistive Resistive Resistive
Display, colors Color TFT, 64k colors Color TFT, 64k colors Color TFT, 64k colors Color TFT, 64k colors Color TFT, 64k colors Color TFT, 64k colors
Pixel resolution (landscape)
portrait mode also available
QVGA 320 x 240 VGA 640 x 480 WVGA 800 x 480 VGA 640 x 480 VGA 640 x 480 VGA 640 x 480
Brightness (cd/m2) 250 250 250 350 350 350
Backlight LED, selectable dimming LED, selectable dimming LED, selectable dimming LED, selectable dimming LED, selectable dimming LED, selectable dimming
Lifespan of backlight (half-life) 40,000 hrs 40,000 hrs 40,000 hrs 40,000 hrs 40,000 hrs 40,000 hrs
Processor 32 bit RISC, 400 MHz 32 bit RISC, 400 MHz 32 bit RISC, 400 MHz 32 bit RISC, 400 MHz 32 bit RISC, 400 MHz 32 bit RISC, 400 MHz
Volatile memory 64 MB DRAM 64 MB DRAM 64 MB DRAM 64 MB DRAM 64 MB DRAM 64 MB DRAM
Non-volatile memory 125 KB NVRAM/64 MB
NAND, 1 SD card slot
125 KB NVRAM/64 MB NAND/
2 MB NOR, 1 SD card slot
125 KB NVRAM/64 MB NAND/
2 MB NOR, 1 SD card slot
Real time clock Yes Yes Yes Yes Yes Yes
Communication ports Ethernet 10/100, RS-485
or RS-232 USB Device
Ethernet 10/100, RS-485, RS-232
USB Host, USB Device
Ethernet 10/100, RS-485, RS-232 USB Host, USB Device
Slots for COMM modules None None None None None None
Power supply rated voltage 24 Vdc nominal (–20%/+25%) with polarity protection 24 Vdc nominal (–20%/+25%) with polarity protection
Continuous current consumption
(max. amps)
0.2 0.4 0.4 0.4 0.6 0.6
Starting current inrush (A2s) 1.5 1.5 1.5 1.5 1.5 1.5
Ambient conditions
Operation—relative humidity,
non-condensing
0 to 50°C, 10 to 95% 0 to 50°C, 10 to 95% 0 to 50°C, 10 to 95% 0 to 50°C, 10 to 95% 0 to 50°C, 10 to 95% 0 to 50°C, 10 to 95%
Storage/transport—relative
humidity, non-condensing
–20 to 60°C, 10 to 95% –20 to 60°C, 10 to 95% –20 to 60°C, 10 to 95% –20 to 60°C, 10 to 95% –20 to 60°C, 10 to 95% –20 to 60°C, 10 to 95%
Shock IEC 60068-2-27 15g for 11 ms duration IEC 60068-2-27 15g for 11 ms duration
Vibration IEC 60068-2-6
5–9 Hz: 3.5 mm displacement
9–60 Hz: 0.15 mm displacement
60–150 Hz: 2g acceleration
IEC 60068-2-6
5–9 Hz: 3.5 mm displacement
9–60 Hz: 0.15 mm displacement
60–150 Hz: 2g acceleration
Agency certifications and
standards
CE, UL/cUL, CSA (pending), RoHS CE, UL/cUL, CSA (pending), RoHS
Protection type
Front IP65, NEMA 4X (indoor) IP65, NEMA 4X (indoor) IP65, NEMA 4X (indoor) IP65, NEMA 4X (indoor) IP65, NEMA 4X (indoor) IP65, NEMA 4X (indoor)
Rear IP20, NEMA 1 IP20, NEMA 1 IP20, NEMA 1 IP20, NEMA 1 IP20, NEMA 1 IP20, NEMA 1
Housing material Plastic Plastic Plastic Metal Metal Metal
Dimensions WxHxD (mm) 136 x 100 x 30 170 x 130 x 39 210 x 135 x 38 212 x 156 x 53 275 x 208 x 53 345 x 260 x 54
Mounting cutout WxH (mm) 123 x 87 157 x 117 197 x 122 198 x 142 261 x 194 329 x 238
Approximate weight lbs (kg) 0.7 (0.3) 1.3 (0.6) 1.3 (0.6) 2.9 (1.3) 4.3 (2.1) 6.1 (3.0)
Ability to run third party
software
No No No No No No
XSoft-CoDeSys-2 development
software
SW-XSOFT-CODESYS-2-S (seat)
SW-XSOFT-CODESYS-2-M (multi-seat)
SW-XSOFT-CODESYS-2-S (seat)
SW-XSOFT-CODESYS-2-M (multi-seat)
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-21
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Gateways and Powerfeed Modules
Note
1If contactors with a total current consumption >3A are connected, a powerfeed module EU5C-SWD-PF1/2 has to be used.
Description Unit
EU5C-SWD-EIP-MODTCP
Gateway
EU5C-SWD-DP
Gateway
EU5C-SWD-CAN
Gateway
EU5C-SWD-PF1-1
Powerfeed
EU5C-SWD-PF2-1
Powerfeed
General
Standards IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
Dimensions (W x H x D) in
(mm)
1.38 x 3.54 x 4.88
(35 x 90 x 124)
1.38 x 3.54 x 5.0
(35 x 90 x 127)
1.38 x 3.54 x 5.0
(35 x 90 x 127)
1.38 x 3.54 x 4.88
(35 x 90 x 124)
1.38 x 3.54 x 4.88
(35 x 90 x 124)
Weight lbs (kg) 0.37 (0.17) 0.35 (0.16) 0.35 (0.16) 0.24 (0.11) 0.37 (0.17)
Mounting Top-hat rail IEC/EN 60715, 35 mm DIN rail IEC/EN 60715, 35 mm
Mounting position Vertical Vertical Vertical Vertical Vertical
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20 IP20 IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15g/11 ms
Impacts9 9999
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II II II II II
Pollution degree 2 2222
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV8 8888
Contact discharge (Level 2) kV4 4444
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10 10 10
1.42 GHz V/m3 3333
22.7 GHz V/m1 1111
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables kV2 2222
CAN/DP bus cable kV 1 1 1
SmartWire-DT cables kV1 1111
Surge (IEC/EN 61131-2:2008, Level 1)
Supply cables kV 0.5 0.5 0.5 0.5 0.5
CAN/DP bus cable kV1 1111
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°)
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5–95 5–95 5–95 5–95 5–95
Supply Voltage UAux
SM Puffer Bremer V 24 Vdc (–15%/+20%)
Residual ripple on the input voltage % <5 5555
Protection against polarity reversal Yes Yes Yes Yes Yes
Max. current (Imax)A3
13 13 133
Short-circuit rating No, external fuse FAZ Z3
Power loss W Normally 1 Normally 1 Normally 1 Normally 1 Normally 1
Potential isolation No No No No No
Rated operating voltage of 24 Vdc modes V Typ. UAux –0.2 Typ. UAux –0.2 Typ. UAux –0.2 Typ. UAux –0.2 Typ. UAux –0.2
V7-T9-22 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Gateways and Powerfeed Modules, continued
Note
1If contactors with a total current consumption >0.7 A are connected, a Power Feeder module EU5C-SWD-PF2 has to be used.
Description Unit
EU5C-SWD-EIP-MODTCP
Gateway
EU5C-SWD-DP
Gateway
EU5C-SWD-CAN
Gateway
EU5C-SWD-PF1-1
Powerfeed
EU5C-SWD-PF2-1
Powerfeed
Supply Voltage UPow
Supply voltage V 24 Vdc (–15%/+20%)
Input voltage ripple % <5<5<5<5<5
Siemens MPI, (optional) Yes Yes Yes Yes
Rated current (I) A 0.7 0.7 0.7 0.7 0.7
Overload proof Yes Yes Yes Yes Yes
Inrush current and duration A 12.5 A/6 ms 12.5 A/6 ms 12.5 A/6 ms 12.5 A/6 ms 12.5 A/6 ms
Heat dissipation at 24 Vdc W 3.8 3.8 3.8 3.8 3.8
Potential isolation between UPow and
15V SmartWire-DT supply voltage
No No No Yes
Bridging voltage dips ms 10 10 10 10
Repetition rate s 1 1 1 1
Status indication (LED) Yes Yes Yes No Yes
SmartWire-DT Supply Voltage
Rated operating voltage (Ue) V 14.5 ±3% 14.5 ±3% 14.5 ±3% 14.5 ±3% 14.5 ±3%
Max. current (Imax) A 0.7 10.7 10.7 10.7 0.7
Short-circuit proof Yes Yes Yes No Yes
Connection Supply Voltages
Connection type Push in terminals Push in terminals Push in terminals Push in terminals Push in terminals
Solid mm20.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16)
Flexible with ferrule mm20.25–1.5 0.25–1.5 0.25–1.5 0.25–1.5 0.25–1.5
SmartWire-DT Network
Station type SmartWire-DT master SmartWire-DT master SmartWire-DT master
Number of SmartWire-DT modes 99 58 99
Baud rates 125
250
125 125
Address allocation Automatic Automatic Automatic None None
Status indication (LED)
SmartWire-DT master Green Green Green Green Green
Configurations Red Red Red Red Red
Connections Plug, 8-pole Plug, 8-pole Plug, 8-pole 2 x plug, 8-pole 2 x plug, 8-pole
Plug connectors Blade terminal SWD4-8MF2 Flat plug SWD4-8MF2 Flat plug SWD4-8MF2 Two flat plugs SWD4-8MF2 Two flat plugs SWD4-8MF2
Fieldbus Interface
Bus protocol Ethernet IP/Modbus TCP slave PROFIBUS-DP CANopen
Baud rates 10/100 mB Up to 12 mB To 1 mB
Address allocation Automatic Automatic Automatic
Station address 2–125 2–32
Address allocation DIP switch/DHCP/BOOTP
selection via DIP switch
DIP switch DIP switch
Status display fieldbus interface (LED) Link status: yellow (10 mB),
green (100 mB) flashing
Two-colored red/green Two-colored red/green
Terminating resistor Switchable via plug DIP switches
Connection design for field bus 2 x RJ45 (2-channel switch) 1 x SUB-D socket, 9-pole 1 x SUB-D plug, 9-pole
Potential isolation Yes Yes Yes
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-23
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Input/Output Modules
Note
1Minimum length 8 mm.
Description Unit EU5E-SWD-8DX EU5E-SWD-4DX EU5E-SWD-4D4D EU5E-SWD-4D2R EU5E-SWD-X8D
General
Standards IEC/EN 61131-2; EN 50178
Dimensions (W x H x D) in
(mm)
1.38 x 3.54 x 3.97
(35 x 90 x 101)
1.38 x 3.54 x 3.97
(35 x 90 x 101)
1.38 x 3.54 x 3.97
(35 x 90 x 101)
1.38 x 3.54 x 3.97
(35 x 90 x 101)
1.38 x 3.54 x 3.97
(35 x 90 x 101)
Weight lbs (kg) 0.22 (0.10) 0.22 (0.10) 0.22 (0.10) 0.22 (0.10) 0.22 (0.10)
Mounting DIN rail IEC/EN 60715,
35 mm
Top-hat rail IEC/
EN 60715, 35 mm
DIN rail IEC/EN 60715,
35 mm
DIN rail IEC/EN 60715,
35 mm
Top-hat rail IEC/
EN 60715, 35 mm
Mounting position Vertical Vertical Vertical Vertical Vertical
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20 IP20 IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15g/11 ms
Impacts99999
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II II II II II
Pollution degree 22222
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV88888
Contact discharge (Level 2) kV44444
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10 10 10
1.42 GHz V/m33333
22.7 GHz V/m11111
Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class A EN 55011 Class A EN 55011 Class A EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables kV22222
Signal lines kV11111
SmartWire-DT cables kV11111
Surge (IEC/EN 61131-2:2008, Level 1)
Supply cables kV 0.5 0.5 0.5 0.5 0.5
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°)
Relative humidity, non-condensing (IEC/
EN 60068-2-30)
% 5–95 5–95 5–95 5–95 5–95
SmartWire-DT Network
Station type SmartWire-DT (node) SmartWire-DT (slave) SmartWire-DT (node) SmartWire-DT (node) SmartWire-DT (slave)
Address allocation Automatic Automatic Automatic Automatic Automatic
SmartWire-DT status (LED) Green Green Green Green Green
Connection
Plug 8-pole Plug, 8-pole 8-pole 8-pole Plug, 8-pole
Connection plug External device plug SWD4-8SF2-5
Current consumption (15V SWD supply) See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33
V7-T9-24 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Input/Output Modules, continued
Note
1Three-wire connection with power supply l+, l-.
Description Unit EU5E-SWD-8DX EU5E-SWD-4DX EU5E-SWD-4D4D EU5E-SWD-4D2R EU5E-SWD-X8D
Connection Supply and I/O
Connection type Push in terminals Push in terminals Push in terminals Push in terminals Push in terminals
Solid mm20.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16)
Flexible with ferrule 1mm20.25–1.5 (AWG 24–16) 0.25–1.5 0.25–1.5 0.25–1.5 0.25–1.5 (AWG 24–16)
24 Vdc Supply for Output Supply
Rated operational voltage (Ue) V 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%)
Residual ripple on the input voltage % <55 <5
Protection against polarity reversal Yes Yes Yes
Digital Inputs
Quantity 8 4 144—
Input current mA Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc
Voltage level to IEC/EN 61131-2
Limit value type 1 Low <5 Vdc; High >15 Vdc
Input delay
High <0.2 ms <0.2 ms <0.2 ms <0.2 ms <0.2 ms
Low <0.2 ms <0.2 ms <0.2 ms <0.2 ms <0.2 ms
SmartWire-DT status (LED) Yellow Yellow Yellow Yellow
Power Supply l+, l-
Overload proof Yes, with diagnostics
Output current per input supply A <0.5———
Supply voltage V Ue 0.16V
Transistor Outputs
Number ——4 —8
Output current A Normally 0.5 at 24 Vdc Normally 0.5 at 24 Vdc
Short-circuit tripping current A Max. 1.2 over 3 ms Max. 1.2 over 3 ms
Lamp load (RLL) W——3 <3
Overload proof Yes, with diagnostics Yes, with diagnostics
Switching capacity EN 60947-5-1 utilization
category DC-13
EN 60947-5-1 utilization
category DC-13
Status display LED————Yellow
Relay Outputs
Number ———2
Contact type art ———N/O contact
Operations
Utilization category AC-1, 250V, 6A >6 x 104
Utilization category AC-15, 250V, 3A ———>5 x 10
4
Utilization category DC-13, 24V, 1A ———>2 x 10
5
Safe isolation Vac———230
Minimum load current mA ———100 mA, 12 Vdc
Pick-up/drop-out time ms———5/2.5
Bounce duration ms———Normally 1.5
Short-circuit protection ———External 4A gL/gG
Status display outputs (LED) Yellow Yellow
Potential Isolation
Inputs for SmartWire-DT Yes Yes Yes Yes Yes
Transistor outputs for SmartWire-DT Yes Yes
Transistor outputs for inputs No
Relays for SmartWire-DT ———Yes
Relays for inputs ———Yes
Relays for relays ———Yes
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-25
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Analog I/O Modules
Note
1Minimum length 8 mm.
Description Unit EU5E-SWD-4AX EU5E-SWD-2A2A EU5E-SWD-4PT
General
Standards IEC/EN 61131-2/EN 50178 IEC/EN 61131-2/EN 50178 IEC/EN 61131-2/EN 50178
Dimensions (W x H x D) in (mm) 1.38 x 3.54 x 3.97 (35 x 90 x 101) 1.38 x 3.54 x 3.97 (35 x 90 x 101) 1.38 x 3.54 x 3.97 (35 x 90 x 101)
Weight lbs (kg) 0.22 (0.10) 0.22 (0.10) 0.22 (0.10)
Mounting Top-hat rail IEC/EN 60715, 35 mm Top-hat rail IEC/EN 60715, 35 mm Top-hat rail IEC/EN 60715, 35 mm
Mounting position Vertical Vertical Vertical
Ambient Conditions, Mechanical
Protection type (IEC/EN 60529) IP20 IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15g/11 ms
Impacts 9 9 9
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II II II
Pollution degree 2 2 2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8 8 8
Contact discharge (Level 2) kV 4 4 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10
1.4–2 GHz V/m 3 3 3
2–2.7 GHz V/m 1 1 1
Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class A EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables kV 2 2 2
Signal lines kV 2 2 2
SmartWire-DT cables kV 2 2 2
Surge (IEC/EN 61131-2:2008, Level 1) Supply cables 1.0 kV Supply cables 1.0 kV Supply cables 1.0 kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) 13° to 131° (–25° to 55°) 13° to 131° (–25° to 55°) 13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures Prevent with suitable measures Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°)
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5–95 5–95 5–95
SmartWire-DT Network
Station type SmartWire-DT slave SmartWire-DT slave SmartWire-DT slave
Baud rate setting Automatic Automatic Automatic
SmartWire-DT status LED LED Green Green Green
Connection Plug: 8-pole/Connection plug: External device plug SWD4-8SF2-5
Current consumption (15V SWD supply) See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33
Connection Supply and I/O
Connection type Push in terminals Push in terminals Push in terminals
Solid mm20.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16)
Flexible with ferrule 1mm20.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16)
24 Vdc Supply for Output Supply
Rated operational voltage (Ue) V 24 Vdc –15%/+20% 24 Vdc –15%/+20% 24 Vdc –15%/+20%
Residual ripple on the input voltage % <5<5<5
Current consumption mA 10 50
Protection against polarity reversal Yes Yes Yes
V7-T9-26 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Analog I/O Modules, continued
Description Unit EU5E-SWD-4AX EU5E-SWD-2A2A EU5E-SWD-4PT
Analog Inputs
Quantity Four (two-wire connection,
screened, length <10m)
Two (two-wire connection,
screened, length <10m)
Parameterization
Part no. Voltage, current Voltage, current
Averaging Adjustable Adjustable
Voltage
Input voltage V 0–10 0–10
Input impedance k ohms 13.3 13.3
Maximum current
Input current mA 0–20 0–20
Input impedance ohms < 250 < 250
Resolution Bit 12 12
Conversion time ms 20 20
Total error % ±1 ±1
Repetition accuracy % ±0.5 ±0.5
Dielectric strength V ±30 ±30
Analog Outputs
Number Two (two-wire connection, screened)
Parameterization
Part no. Voltage, current
Averaging ———
Voltage
Output voltage V 0–10
Maximum output current mA 10
Maximum current
Output current mA 0–20
Load resistance ohms <500
Overload and short-circuit proof Yes
Resolution Bit 12
Conversion time ms 20
Total error % ±1
Repetition accuracy % ±0.5
Temperature Inputs
Number Four (two-, three-wire connection,
screened, length <10m)
Parameterization
Averaging Adjustable
Temperature sensor PT100, PT1000, Ni1000
Temperature range °F (°C) PT100, PT1000:
–58° to 392° (–50° to 200°)
Ni1000:
–58° to 302° (–50° to 150°)
Resolution °F (°C) 32° (0.1°)
Conversion time ms 250
Display °C, °F, raw value
Total error %——±1
Repetition accuracy % ±0.5
Potential Isolation
Inputs for SmartWire-DT Yes Yes Yes
Outputs to SmartWire-DT Yes
Input to input No No No
Output to input No
Output to output No
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-27
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Accessories
Description Unit
SWD4-RC8-10
Resistor
SWD4-8SF2-5
Plug
SWD4-8SFF2-5
Coupling
SWD4-SF8-20
Bushing
General
Standards IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178
Dimensions (W x H x D) in
(mm)
1.91 x 1.36 x 0.34
(48.5 x 34.5 x 10)
0.59 x 1.44 x 0.69
(15 x 36.5 x 17.5)
1.91 x 1.36 x 0.34
(48.5 x 34.5 x 10)
0.94 x 1.02 x 6.34
(24 x 26 x 162)
Weight lbs (g) 0.022 (10) 0.012.1 (5.5) 0.010 (4.5) 0.044 (20)
Mounting position As required As required As required As required
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20 IP20 IP67
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15g/11 ms
Impacts999—
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II
Pollution degree 2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8
Contact discharge (Level 2) kV 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10
1.4–2 GHz V/m 3
2–2.7 GHz V/m 1
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
SmartWire-DT cables kV 1
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°)
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5 –95 5 –95 5 –95 5 –95
Connection Options
SWD-In Plug, 8-pole Plug connector Plug, 8-pole
Number of insertion cycles >200 1 >200
SWD-Out Socket, 8-pole Plug, 8-pole Socket, 8-pole
Number of insertion cycles >200 >200 >500
Current consumption (15V SWD supply) See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33
V7-T9-28 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Accessories, continued
Description Unit
SWD4-SM8-20
Bushing
SWD4-8FRF-10
Adapter
SWD4-SFL8-20
Adapter
SWD4-SML8-20
Adapter
General
Standards IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178
Dimensions (W x H x D) in
(mm)
0.94 x 1.02 x 6.69
(24 x 26 x 170)
1.38 x 3.54 x 1.38
(35 x 90 x 35)
1.38 x 3.27 x 1.57
(35 x 83 x 40)
1.38 x 3.27 x 1.82
(35 x 83 x 46)
Weight lbs (g) 0.050 (22.5) 0.093 (42) 0.110 (50) 0.110 (50)
Mounting position As required As required As required As required
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP67 IP20 IP67 IP67
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15g/11 ms
Impacts 9 9 9
Drop to IEC/EN 60068-2-31 (drop height) in (mm) ————
Free fall, packaged (IEC/EN 60068-2-32) ft (m) ————
Electromagnetic Compatibility (EMC)
Overvoltage category ————
Pollution degree ————
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8 8 8
Contact discharge (Level 2) kV 4 4 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10
1.4–2 GHz V/m 3 3
2–2.7 GHz V/m 1 1
Radio interference suppression (SmartWire-DT) ————
Burst (IEC/EN 61131-2:2008, Level 3) ————
SmartWire-DT cables kV————
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°)
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5–95 5–95 5–95 5–95
Connection Options
SWD-In Plug, 8-pole Plug, 8-pole Plug, 8-pole Plug, 8-pole
Number of insertion cycles >500 >200 >200 >500
SWD-Out Push in terminals Socket, 8-pole Plug, 8-pole
Number of insertion cycles >500 >200
Current consumption (15V SWD supply) See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-29
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Contactor Modules
Description Unit DIL-SWD-32-001 DIL-SWD-32-002 PKE-SWD-32
General
Standards IEC/EN 61131-2
EN 50178
IEC/EN 60947
IEC/EN 61131-2
EN 50178
IEC/EN 60947
IEC/EN 61131-2
EN 50178
IEC/EN 60947
Dimensions (W x H x D) in
(mm)
1.77 x 1.50 x 3.0
(45 x 38 x 76)
1.77 x 1.50 x 3.0
(45 x 38 x 76)
1.77 x 1.50 x 3.0
(45 x 38 x 76)
Weight lbs (kg) 0.9 (0.04) 0.9 (0.04) 0.9 (0.04)
Mounting on XTCE007–XTCE032 on XTCE007–XTCE032
Mounting position as XTCE007–XTCE032 as XTCE007–XTCE032
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15g/11 ms
Impacts 9 9 9
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II II II
Pollution degree 2 2 2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8 8 8
Contact discharge (Level 2) kV 4 4 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10
1.4–2 GHz V/m 3 3 3
2–2.7 GHz V/m 1 1 1
Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class A EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
CAN/DP bus cable kV 1 1 1
SmartWire-DT cables kV 1 1 1
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 140° (–25° to 60°) –13° to 140° (–25° to 60°) –13° to 140° (–25° to 60°)
Condensation Prevent with suitable measures Prevent with suitable measures Prevent with suitable measures
Storage °F (°C) –22° to 158° (–30° to 70°) –22° to 158° (–30° to 70°) –22° to 158° (–30° to 70°)
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5–95 5–95 5–95
V7-T9-30 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Contactor Modules, continued
Notes
1Own supply.
2Minimum length: 8 mm.
Description Unit DIL-SWD-32-001 DIL-SWD-32-002 PKE-SWD-32
SmartWire-DT Network
Station type SmartWire-DT station (mode) SmartWire-DT station (mode) SmartWire-DT (slave)
Address allocation Automatic Automatic Automatic
SmartWire-DT status LED Green/orange Green/orange Green/orange
Connections
Plug 8-pole 8-pole 8-pole
Plug connectors External device plug SWD4-8SF2-5 External device plug SWD4-8SF2-5 External device plug SWD4-8SF2-5
Current consumption (15V SWD supply) See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33
Mode Parameter
Manual/automatic mode No Yes Yes
Setting Rotary switch Rotary switch
Connection Auxiliary Contact
Number 2 2
Rated voltage (Ue) 1Vdc1515—
Input current at 1 signal, typical mA 3 3
Potential isolation No No
Cable length ft (m) <9.2 (2.8) <9.2 (2.8) <9.2 (2.8)
Connection type Push in terminals Push in terminals Push in terminals
Terminal Capacities
Solid mm20.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16)
Flexible with ferrule 2mm20.25–1.5 0.25–1.5 0.25–1.5
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-31
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Pilot Device Modules
Description Unit M22-SWD-K11 M22-SWD-KC11 M22-SWD-LED-_ M22-SWD-LEDC-_ M22-SWD-K11-LED_
General
Standards IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
Dimensions (W x H x D) in
(mm)
0.47 x 1.65 x 1.54
(12 x 42 x 39)
0.47 x 1.77x 1.46
(12 x 45 x 37)
0.39 x 1.65 x 1.77
(10 x 42 x 45)
0.39 x 1.77 x 1.65
(10 x 45 x 42)
0.47 x 1.65 x 1.77
(12 x 42 x 45)
Weight lbs (g) 0.022 (10) 0.022 (10) 0.022 (10) 0.022 (10) 0.022 (10)
Mounting position As required As required As required As required As required
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20 IP20 IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150 8.4–150 8.4–150
Mechanical shock resistance
(IEC/EN 60068-2-27) semi-sinusoidal
15g/11 ms
Impacts99999
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category Not applicable Not applicable Not applicable Not applicable Not applicable
Pollution degree 22222
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV88888
Contact discharge (Level 2)kV44444
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10 10 10
1.42 GHz V/m33333
22.7 GHz V/m11111
Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class A EN 55011 Class A EN 55011 Class A EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables kV22222
SmartWire-DT cables kV11111
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C)
–22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C)
–40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°)
Relative humidity, non-condensing
(IEC/EN 60068-2-30)
% 9–95 9–95 9–95 9–95 9–95
SmartWire-DT Network
Station type SmartWire-DT station (node)
Address allocation Automatic Automatic Automatic Automatic Automatic
SmartWire-DT status LED Green Green Green Green Green
Connections
Plug 8-pole 8-pole 8-pole 8-pole 8-pole
Plug connectors SWD4-8SF2-5 M22-SWD-I_LP SWD4-8SF2-5 M22-SWD-I_LP SWD4-8SF2-5
Number of insertion cycles >50 >50 >50 >50 >50
Current consumption (15V SWD supply) See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33
Function Element
Contacts 1 changeover contact 1 changeover contact 1 changeover contact
Lifespan mechanical/electrical (operations) 1 x 1061 x 106——1 x 10
6
LED display No No Yes Yes Yes
Diagnostics Yes Yes No No Yes
Mounting Front mount Base mount Front mount Base mount Front mount
V7-T9-32 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Pilot Device Modules, continued
Description Unit M22-SWD-K11LEDC-_ M22-SWD-K22 M22-SWD-KC22 M22-SWD-K22-LED_ M22-SWD-K22LEDC-_
General
Standards IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
Dimensions (W x H x D) in
(mm)
0.47 x 1.77 x 1.65
(12 x 45 x 42)
0.67 x 1.65 x 1.54
(17 x 42 x 39)
0.67 x 1.77 x 1.46
(17 x 45 x 37)
0.67 x 1.65 x 1.77
(17 x 42 x 45)
0.67 x 1.77 x 1.65
(17 x 45 x 42)
Weight lbs (g) 0.022 (10) 0.030 (14) 0.030 (14) 0.030 (14) 0.030 (14)
Mounting position As required As required As required As required As required
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20 IP20 IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4 5–8.4 5–8.4
Constant acceleration 1g Hz 8.4–150 8.4–150 8.4–150 8.4–150 8.4–150
Mechanical shock resistance
(IEC/EN 60068-2-27) semi-sinusoidal
15g/11 ms
Impacts99999
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category Not applicable Not applicable Not applicable Not applicable Not applicable
Pollution degree 22222
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV88888
Contact discharge (Level 2)kV44444
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10 10 10
1.42 GHz V/m33333
22.7 GHz V/m11111
Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class A EN 55011 Class A EN 55011 Class A EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables kV22222
SmartWire-DT cables kV11111
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C)
–22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°) –22° to 131° (–30° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C)
–40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°) –40° to 176° (–40° to 80°)
Relative humidity, non-condensing
(IEC/EN 60068-2-30)
% 9–95 5–95 5–95 5–95 5–95
SmartWire-DT Network
Station type SmartWire-DT station (node)
Address allocation Automatic Automatic Automatic Automatic Automatic
SmartWire-DT status LED Green Green Green Green Green
Connections
Plug 8-pole 8-pole 8-pole 8-pole 8-pole
Plug connectors M22-SWD-I_LP SWD4-8SF2-5 M22-SWD-I_LP SWD4-8SF2-5 M22-SWD-I_LP
Number of insertion cycles >50 >50 >50 >50 >50
Current consumption (15V SWD supply) See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33 See Page V7-T9-33
Function Element
Contacts 1 contact 2 contacts 2 contacts 2 contacts 2 contacts
Lifespan mechanical/electrical (operations) 1 x 1061 x 1061 x 1061 x 1061 x 106
LED display Yes No No Yes Yes
Diagnostics Yes Yes Yes Yes Yes
Mounting Base mount Front mount Base mount Front mount Base mount
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-33
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Current Consumption Ratings
Power Consumption/Current Consumption
24 Vdc Control Voltage UAUX
Current Consumption 15 Vdc Supply Voltage
Note
1With terminating resistor switched on.
Description Unit DIL-SWD-32-_
Pick-Up Power
For XTCE007–XTCE009 W 3
For XTCE012–XTCE015 W 4,5
For XTCE018–XTCE032 W 12
Pick-Up Current
For XTCE007–XTCE009 mA 125
For XTCE012–XTCE015 mA 188
For XTCE018–XTCE032 mA 500
Holding Power
For XTCE007–XTCE009 W 3
For XTCE012–XTCE015 W 4,5
For XTCE018–XTCE032 W 0,5
Holding Current
For XTCE007–XTCE009 mA 125
For XTCE012–XTCE015 mA 188
For XTCE018–XTCE032 mA 21
Catalog Number
Current
Consumption (mA) Catalog Number
Current
Consumption (mA)
DIL-SWD-32-001 40 M22-SWD-K22 7
DIL-SWD-32-002 40 M22-SWD-K22LED-B 19
EU5E-SWD-4D2R 45 M22-SWD-K22LED-G 19
EU5E-SWD-4D4D 45 M22-SWD-K22LED-R 19
EU5E-SWD-8DX 12 M22-SWD-K22LED-W 19
M22-SWD-I1-LP01 117 M22-SWD-K22LEDC-B 19
M22-SWD-I2-LP01 117 M22-SWD-K22LEDC-G 19
M22-SWD-I3-LP01 117 M22-SWD-K22LEDC-R 19
M22-SWD-I4-LP01 117 M22-SWD-K22LEDC-W 19
M22-SWD-I6-LP01 117 M22-SWD-KC11 7
M22-SWD-K11 7M22-SWD-KC22 7
M22-SWD-K11LED-B 19 M22-SWD-LED-B 19
M22-SWD-K11LED-G 19 M22-SWD-LED-G 19
M22-SWD-K11LED-R 19 M22-SWD-LED-R 19
M22-SWD-K11LED-W 19 M22-SWD-LED-W 19
M22-SWD-K11LEDC-B 19 M22-SWD-LEDC-B 19
M22-SWD-K11LEDC-G 19 M22-SWD-LEDC-G 19
M22-SWD-K11LEDC-R 19 M22-SWD-LEDC-R 19
M22-SWD-K11LEDC-W 19 M22-SWD-LEDC-W 19
SWD4-RC8-10 17
V7-T9-34 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Dimensions
Approximate Dimensions in Inches (mm)
Gateways
EU5C-SWD_
Powerfeed Modules
EU5C-SWD-PF_
I/O Modules
EU5E-SWD_
3.54
(90.0)
1.38 (35.0) 0.18 (4.5)
4.80 (122.0)
0.18 (4.5)
4.72 (120.0)
3.54
(90.0)
1.38 (35.0)
3.54
(90.0)
3.82 (97.0)
1.38 (35.0) 0.18 (4.5)
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-35
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Approximate Dimensions in Inches (mm)
Terminating Resistor
SWD4-RC8-10
Coupling
SWD4-8SFF2-5
Enclosure Bushing Plug
SWD4-SM8-20
Enclosure Bushing Socket
SWD4-SF8-20
Cabinet Cable Adapter Plug
SWD4-SML8-20
Cabinet Cable Adapter Socket
SWD4-SFL8-20
1.91
(48.4)
1.02 (25.9)
0.40 (10.2)
0.16
(4.0)
1.35 (34.3)
1.91
(48.4)
1.02 (25.9)
0.40 (10.2)
0.16
(4.0)
1.35 (34.3)
5.67 (144.0)
0.95 (24.0)
0.50 (12.5)
0.12 (3.0)
M20 x 1.5
Ø 0.94 (24.0)
5.95 (151.0)
0.95 (24.0)
0.47 (12.0)
0.12 (3.0)
M20 x 1.5
Ø 0.94 (24.0)
3.24
(82.4)
1.38 (35.0)
0.55
(14.0)
M18 x 0.75
0.83
(21.0)
0.16
(4.0)
3.24
(82.4)
1.38 (35.0)
0.55
(14.0)
M18 x 0.75
0.83
(21.0)
0.16
(4.0)
V7-T9-36 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Approximate Dimensions in Inches (mm)
Panel Cable Adapter
SWD4-8FRF-10
Round Cable Socket
SWD4-SF8-67
Round Cable Plug
SWD4-SM8-67
Right Angle Round Cable Socket
SWD4-SF8-67W
Right Angle Round Cable Plug
SWD4-SM8-67W
3.54
(90.0)
1.38 (35.0) 0.91
(23.2) 1.42 (36.0)
Ø 0.73
(18.5)
1.77 (45.0)
1.75 (44.5)
M16 x 0.75
Ø 0.73
(18.5)
Ø 0.71
(18.0)
M16 x 0.75
1.47
(37.4)
2.13 (54.0)
0.79
(20.0)
1.21 (30.8)
M16 x 0.75
1.46
(37.1)
2.17 (55.0)
0.79
(20.0)
1.21 (30.8)
Ø 0.71
(18.0)
Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T9-37
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT Panel Wiring Solution
Approximate Dimensions in Inches (mm)
Contactor Modules
DIL-SWD-32-001 and DIL-SWD-32-002
SmartWire-DT PKE Modules
PKE-SWD-32
Pilot Device Modules
M22-SWD-K_, M22-SWD-LED_
Device Plug
SWD4-8SF2-5
1.50
(38.0)
1.77 (45.0) 2.10 (53.1)
2.85 (72.3)
1.54
(39.0)
1.77 (45.0) 2.41 (61.1)
3.17 (80.6)
2.52 (64.0)
1.73
(44.0)
1.18
(30.0)
0.68
(17.2)
1.43 (36.4)
0.50
(12.8)
1.18 (30.0) 0.59
(14.9)