SCD SPECIFICATION CONTROL DRAWING Title 400R0111 Date WIRE, RADIATION-CROSSLINKED, POLYOLEFIN-INSULATED, LIMITED FIRE HAZARD, 600 VOLT Revision 3-8-16 B This specification sheet forms a part of the latest issue of Raychem Specification WCD 3114. PRIMARY INSULATION - RADIATION-CROSSLINKED, POLYOLEFIN CONDUCTOR - TIN-COATED COPPER JACKET - RADIATION-CROSSLINKED, FLUOROPOLYMER Thickness: .003 .001 in. (.051 mm min, .102 mm max) TABLE I. CONSTRUCTION DETAILS FINISHED WIRE DIAMETER OF STRANDED CONDUCTOR (inch) (mm) MAXIMUM MAXIMUM RESISTANCE AT 20C (ohms/1000 ft.) (ohms/km) MINIMUM MAXIMUM .021 (.533) 41.3 (135.) .032 (.813) .036 (.914) 1.4 (2.08) .023 (.584) .026 (.660) 26.2 (86.0) .038 (.965) .042 (1.07) 2.0 (2.98) 19 x 34 .029 (.737) .033 (.838) 16.2 (53.1) .045 (1.14) .049 (1.24) 3.0 (4.46) 19 x 32 .037 (.940) .041 (1.04) 9.88 (32.4) .053 (1.35) .057 (1.45) 4.5 (6.70) 18 19 x 30 .046 (1.17) .051 (1.30) 6.23 (20.4) .063 (1.60) .067 (1.70) 6.8 (10.1) 400R0111-16-* 16 19 x 29 .052 (1.32) .058 (1.47) 4.81 (15.8) .069 (1.75) .075 (1.91) 8.6 (12.8) 400R0111-14-* 14 19 x 27 .065 (1.65) .073 (1.85) 3.06 (10.0) .085 (2.16) .093 (2.36) 13.2 (19.6) 400R0111-12-* 12 37 x 28 .084 (2.13) .090 (2.29) 2.02 (6.63) .104 (2.64) .112 (2.84) 20.2 (30.1) 400R0111-10-* 10 37 x 26 .106 (2.69) .114 (2.90) 1.26 (4.13) .125 (3.18) .133 (3.38) 31.1 (46.3) PART NUMBER 1/ WIRE SIZE (AWG) CONDUCTOR STRANDING (number x AWG) MINIMUM 400R0111-26-* 26 19 x 38 .018 (.457) 400R0111-24-* 24 19 x 36 400R0111-22-* 22 400R0111-20-* 20 400R0111-18-* DIAMETER (inch) (mm) MAXIMUM WEIGHT (lbs/1000 ft.) (kg/km) Users should evaluate the suitability of this product for their application. Specifications are subject to change without notice. Tyco Electronics Corporation also reserves the right to make changes in materials or processing, which do not affect compliance with any specification, without notification to Buyer. 1/ COLORS AND COLOR CODE DESIGNATORS SHALL BE IN ACCORDANCE WITH MIL-STD-681. OTHER CODES AND SUFFIXES MAY BE ADDED TO THE PART NUMBER, AS NECESSARY, TO CAPTURE ANY ADDITIONAL REQUIREMENTS IMPOSED BY THE PURCHASE ORDER. Raychem, TE Connectivity, TE connectivity (logo), and TE (logo) are trademarks. Page 1 of 2 DIMENSIONS ARE IN INCHES AND, UNLESS OTHERWISE DESIGNATED, ARE NOMINAL. THIS SPECIFICATION SHEET TAKES PRECEDENCE OVER DOCUMENTS REFERENCED HEREIN. REFERENCED DOCUMENTS SHALL BE OF THE ISSUE IN EFFECT ON DATE OF INVITATION FOR BID. Raychem Wire & Cable 501 Oakside Avenue Redwood City, CA 94063-3800 Phone: 1-800-227-8816 Fax: 1-650-361-6297 (c) 2015-2016 Tyco Electronics Corporation. All rights reserved. Page SPECIFICATION CONTROL DRAWING Revision 2 of 2 SCD 400R0111 B TABLE II. PERFORMANCE DETAILS BEND TESTING PART NUMBER 1/ MANDREL DIAMETER (inch) (mm) ( 3%) WEIGHT (lb) (kg) ( 3%) ACCELERATED AGING COLD BEND ACCELERATED AGING COLD BEND 400R0111-26-* .500 (12.7) .500 (12.7) .250 (.113) .500 (.227) 400R0111-24-* .500 (12.7) .500 (12.7) .375 (.170) .500 (.227) 400R0111-22-* .750 (19.1) .750 (19.1) .375 (.170) 1.00 (.454) 400R0111-20-* .750 (19.1) .750 (19.1) .375 (.170) 1.00 (.454) 400R0111-18-* 1.00 (25.4) 1.00 (25.4) .500 (.227) 1.00 (.454) 400R0111-16-* 1.00 (25.4) 1.00 (25.4) .500 (.227) 1.00 (.454) 400R0111-14-* 1.50 (38.1) 1.50 (38.1) 1.00 (.454) 3.00 (1.36) 400R0111-12-* 2.00 (50.8) 2.00 (50.8) 1.00 (.454) 3.00 (1.36) 400R0111-10-* 2.50 (63.5) 2.50 (63.5) 1.00 (.454) 3.00 (1.36) WIRE RATINGS AND ADDITIONAL REQUIREMENTS TEMPERATURE RATING: 125C Maximum continuous conductor temperature VOLTAGE RATING: 600 volts (rms) at sea level ACCELERATED AGING: 300 2C for 6 hours Identification legibility, 225 2C for 6 hours BLOCKING: 150 2C for 24 hours COLOR: White preferred FLAMMABILITY: Char Length, 5 ft. (1.5 m) (maximum) HUMIDITY RESISTANCE: Insulation Resistance, 5000 megohms for 1000 ft. (1524 megohms for 1 km) (minimum) INSULATION ELONGATION AND TENSILE STRENGTH: Primary Insulation, Elongation, 150% (minimum) Tensile Strength, 2500 lbf/in2 (17.2 MPa) (minimum) INSULATION FLAWS: Primary Insulation, Spark Test, 1.5 kV (rms) Impulse Dielectric Test, 6.0 kV (peak) Finished Wire, Spark Test, 3.0 kV (rms) at 3 kHz Impulse Dielectric Test, 8.0 kV (peak) 1/ See footer section on page 1 INSULATION RESISTANCE: 5000 megohms for 1000 ft. (1524 megohms for 1 km) (minimum) LOW TEMPERATURE-COLD BEND: -65 2C for 4 hours SHRINKAGE: 300 2C, 0.125 in. (3.18 mm) (maximum) in 12 inches (305 mm) SMOKE RELEASE: Peak Smoke Release Rate, 0.40 m2/s (maximum) Total Smoke Release, 150 m2 (maximum) SMOKE TEST: D4, 50 (maximum); Dm, 300 (maximum) TOXICITY: HCN: 100 ppm (maximum) SO2: 100 ppm (maximum) CO: 3500 ppm (maximum) HF: 100 ppm (maximum) NO: 100 ppm (maximum) HCI: 500 ppm (maximum) VOLTAGE WITHSTAND (Post Environmental): 2500 volts (rms), 60 Hz, 5 minutes 1/ PART NUMBER: The "*" in the part numbers in Tables I and II shall be replaced by a color code designator. Example: AWG 20, white: 400R0111-20-9 AWG 20, white with a black stripe: 400R0111-20-90 PRODUCT IDENTIFICATION: Outer surface of wire shall be marked in contrasting color as follows: "RAYCHEM 400R0111-xx - 600V Yr of Mfg" (xx = applicable AWG size)