Low Voltage, Branch Circuit Rated Fuses One-time general purpose fuses NON (250Vac/125Vdc) Class K5 & H NOS (600Vac) Catalog Numbers (-Amps) NOS (600Vac) Class K5 & H NOS-1 NOS-12 NOS-70 NOS-200 NOS-2 NOS-15 NOS-75 NOS-225 Specifications Description: General purpose, non-current-limiting fuses. Dimensions: See page 11 for dimensions. Ratings: Volts -- NON: -- 250Vac -- 125Vdc (0-100A) -- NOS: -- 600Vac Amps -- 18-600A IR -- 50,000A RMS Sym. (NON & NOS Class K5 0-60A) -- 10,000A RMS Sym. (NON & NOS Class H 65-600A) -- 50,000A @ 125Vdc (NON Class K5 0-60A) -- 10,000A @ 125Vdc (NON Class H 65-100A) Agency Information: CE, UL Listed - 250V: Class K5 (0-60A), Std. 248-9, Class H (65-600A), Std. 248-6, (125Vdc: NON 0-100), 600V: Class K5 (0-60A), Std. 248-9, Class H (70-600A), Std. 248-6, Guide JDDZ, File E4273, CSA Certified - 250V: (0-12, 65-600), 600V: (0-600), Class 1421-01, File 53787. NOS-3 NOS-20 NOS-80 NOS-250 NOS-4 NOS-25 NOS-90 NOS-300 NOS-5 NOS-30 NOS-100 NOS-350 NOS-6 NOS-35 NOS-110 NOS-400 NOS-7 NOS-40 NOS-125 NOS-450 NOS-8 NOS-45 NOS-150 NOS-500 NOS-9 NOS-50 NOS-175 NOS-600 NOS-10 NOS-60 Recommended Fuse Reducers 250V Fuse Amp Size Clip Amp Size Catalog Number (Pair) 600V Fuse Amp Size Clip Amp Size Catalog Number (Pair) 30 60 263 30 60 No. 663 30 100 213 30 100 No. 216 60 100 216 60 100 No. 616 60 200 226 60 200 No. 626 100 200 2621 100 200 No. 2621 100 400 2641 100 400 No. 2641 200 400 2642 200 400 No. 2642 100 600 2661 100 600 No. 2661 200 600 2662 200 600 No. 2662 400 600 2664 400 600 No. 2664 For CSA Certified 15-60A Ratings, see PON Data Sheet 4126 Features and Benefits * Original fuse providing circuit protection. Typical Applications * Light Duty Circuit Locations NON (250Vac) Catalog Numbers (Amps) NON-18 NON-5 NON-40 NON-175 NON-12 NON-6 NON-45 NON-200 NON-34 NON-6 14 NON-50 NON-225 NON-810 NON-7 NON-60 NON-250 NON-1 NON-8 NON-65 NON-300 NON-1 14 NON-9 NON-70 NON-350 NON-1 12 NON-10 NON-75 NON-400 NON-1 610 NON-12 NON-80 NON-450 NON-2 NON-15 NON-90 NON-500 NON-600 NON-2 12 NON-20 NON-100 NON-3 NON-25 NON-110 NON-3 210 NON-30 NON-125 NON-4 NON-35 NON-150 For superior electrical protection, Cooper Bussmann recommends upgrading NON (250Vac) and NOS (600Vac) fuse applications to Low-Peak LPN-RK (250Vac) and LPS-RK (600Vac) fuses See page 16. Recommended Fuse Holders & Blocks For Class K5 & H 250V & 600V Fuses * See page 8 Data Sheet: 1030 36 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp