Condor D.C. Power Supplies, Inc., A subsidiary of SL Industries, Inc. 805-486-4565 • (800) 235-5929 Fax: (805) 487-8911 http://www.condorpower.com
Dimensions: Inches
Millimeters
SPECIFICATIONS: ALL MODELS
INPUT
AC Input: 90-264 Vac continuous range, 47 to 63 Hz. Internally fused for 20 A.
Power Factor: 0.99 typical at full load. Meets EN61000-3-2.
Inrush: Cold start AC current is less than 90 A at 115 Vac and 180 A at 230 Vac. Limited by
thermistor.
Brownout Protection: Holds regulation to 85 Vac.
Holdup Time: 20 ms minimum after removal of power at full load.
Efficiency: 75% typical.
AC Power Fail: Provides TTL “0” 5 ms before output voltage goes out of regulation band
upon loss of AC power.
OUTPUT
Adjustability: All outputs user adjustable ±5% minimum. Outputs #2 and 3 have factory
adjustable preprogrammed slope.
Line & Load Reg: Outputs #1 and 4 hold ±1% over AC input range and 0 to 100% load
change. Outputs #2 and 3 hold ±2% (preprogrammed slope). Output #1 requires
minimum load of 10%.
Ripple & Noise: Less than 1% p-p or 100 mV, whichever is greater.
Remote Sense (Outputs #1, 2, and 3):Compensates for 250 mV total line drop. Open sense
lead protection.
Temperature Coefficient: 0.02% per degree C.
Stability: 0.1% over 8 hours after 30 minutes warm-up.
Transient Response (Output #1):Output voltage returns to within 1% in less than 500 µs for
a 50% load change. Peak transient does not exceed 5%.
Overload Protection: All outputs are protected against overload and short circuit. Automatic
recovery upon removal of fault.
Overvoltage Protection (Outputs #1, 2, and 3):Protects load against power supply induced
overvoltage. Trip point is factory set so that output voltage cannot exceed 136% of
nominal.
Peak Output Current: Dual current ratings define continuous and peak currents. The peak
current shown can be delivered for a maximum period of 30 seconds.
Remote Inhibit: Contact closure to the negative sense line or a TTL level “0” turns off DC
outputs.
DC Power Good: Provides a TTL “1” when output #1 is above 4.6 V nominal.
Redundancy: External OR-ing diodes and current sharing on outputs #1, 2, and 3 provide
“N+1” capability. Remote senses compensate for additional 0.6 V diode voltage drop.
When the forced current sharing terminal is connected among units, current sharing
remains within 10% of the unit’s full output current rating.
ENVIRONMENTAL
Thermal Protection: Shuts down power supply if overheated. Automatic recovery.
Temperature Range: 0° to 50°C at full ratings.
Safety Agencies: Most models are approved to UL1950; CSA 22.2 #234; IEC 950 and TÜV
EN60950, Class 1 SELV., CE 72/23/EEC/93/68EEC (low voltage directive).
Conducted RFI: Meets FCC Part 15, Subpart J, Class A; EN55022 Class B; CISPR 22 Class B.
Output Isolation: Isolated from ground 50 Vdc.
FUNCTION 115 VAC 230 VAC CONNECTOR
TB1- Line Line 1
TB1- Neutral Line 2
TB1- Safety Ground Safety Ground
AC INPUT (90-264 VAC Continuous Range)
FUNCTION LOCATION NOTES CONNECTOR
Output #1 Terminal marked +V Main output
Terminal marked -V Rtn (Common)
Output #2 J2-1, 2, 3
J2-4, 5, 6 Rtn (Common)
Output #3 J2-7, 8, 9
J2-4, 5, 6 Rtn (Common)
Output #4 J2-10, 11, 12, (+) Floating Output
J2-13, 14, 15 (-) Floating Output
DC OUTPUT
AMP # 350830-1
mates with plug
housing # 350736-1
with pins
Barrier strip
# 6-32 screws
3/8” centers
FUNCTION LOCATION NOTES CONNECTOR
Remote Sense J3-1 Output #1 Sense
J3-3 Output #1 Sense Rtn
J3-8 Output #2 Sense
J3-7 Output #2&3 Sense Rtn
J3-9 Output #3 Sense
DC Power Good J3-6 Reference to Common
AC Power Fail J3-4 when a Sense Rtn is
Inhibit J3-5 terminated
Current Share J3-2
STATUS AND CONTROL
AMP MTA type
#640456-9 pin
header (locking)
Studs # 5/16-18 x 1”
(L)
(N)
( )
NMX-1000
10.4 lbs - 4.7 kgs
1000 WATTS
12”x 8”x 3.38”
NMX-1000
Reverse Voltage: Protected against reverse voltage up to supply current rating.
Cooling: Self cooled with internal ball-bearing fans. Consult factory for alternative
configurations.
OPTIONS: