Industrial Power Supplies TBL Series, 15 to 150 Watt CB Scheme Features UL60950-1 UL508 UL1310 Low profile case, module depth only 55mm Fits into flat control panels used in building automation Safety class ll product UL 1310 class II, NEC class 2 compliance (models up to 90 W) UL 508 listed 5 power ranges from 15 to 150 W Universal input range 85 to 264 VAC Operating temperature range: -25C to +70C max. Adjustable output voltage Short circuit and overload protection DC-OK indicator Easy snap-on mounting on DIN-rail or with wall mounting bracket (included) 3-year product warranty The TBL series is a new range of small DIN-rail mount power supplies which have been designed particularly with building- and factory automation applications in mind. The ultra-compact low profile cases fit in the standardized wall mounted control panels used in the building automation industry. The power supplies can be operated at full load across an ambient temperature range of -25C to +60C without need of additional cooling. Universal input voltage range and full compliance with all important safety and EMC standards qualifies the TBL series power supplies for worldwide markets. For commercial and residential applications requesting safety class ll the models up to 90 Watt are approved to UL 1310. Models Order Code Output Power (max.) Output Voltage* (nom.) Output Current (max.) Efficiency (typ.) TBL 015-105 12 W 5.0 VDC 2.4 A 73 % TBL 015-112 15 W 12 VDC 1.25 A 79 % TBL 015-124 15 W 24 VDC 0.63 A 81 % 12 VDC 2.5 A 81 % TBL 030-112 TBL 030-124 30 W 24 VDC 1.25 A 83 % TBL 060-112 54 W 12 VDC 4.5 A 83 % TBL 060-124 60 W 24 VDC 2.5 A 85 % TBL 090-112 72 W 12 VDC 6.0 A 86 % TBL 090-124 90 W 24 VDC 3.75 A 86 % TBL 150-112 120 W 12 VDC 10 A 84 % TBL 150-124 150 W 24 VDC 6.25 A 87 % * adjustable http://www.tracopower.com Page 1 of 3 Industrial Power Supplies TBL Series 15 to 150 Watt Input Specifications Input voltage - AC nominal rated TBL 150 models: - AC range (designed for) TBL 150 models: - DC range (designed for) - Power derating at low input voltage 100 - 240 VAC; 50/60 Hz 100 - 120 / 220 - 240 VAC; 50/60 Hz 85 - 264 VAC; 47 - 63 Hz 85 - 132 / 187 - 264 VAC; 47 - 63 Hz 120 - 373 VDC (except TLB 150 models) 5% below 90 VAC or 127 VDC Harmonic limits EN 61000-3-2, Class A Recommended circuit breaker (characteristic C or slow blow fuse) 6.0 A Output Specifications Output voltage adjustable range Output regulation 5 VDC model: 5.0 - 5.2 VDC 12 VDC models: 12 - 16 VDC 24 VDC models: 24 - 28 VDC 1 % Ripple and noise (20MHz bandwidth) <100 mV pk-pk Electronic short circuit protection current limitation at 100 - 150 % typ. (automatic recovery) Overvoltage protection, trigger point 5 VDC model: 12 VDC models: TBL 030-124, TBL 150-124: TBL 015-124, TBL 060-124, TBL 090-124: 5.5 - 7.5 VDC 16 - 24 VDC 30 - 37 VDC 29 - 44 VDC Hold-up time 115 VAC min. 10 ms 230 VAC min. 20 ms General Specifications Temperature ranges - Operating -25C to +70C max. - Storage -40C to +85C max. Power derating 2.5 %/K above 60C Humidity (non condensing) 5 - 95 % rel. H Temperature coefficient 0.02 %/K Reliability, calculated MTBF at +25C acc. to IEC 61709 TBL 015: >1,500 Mio h TBL 060: >2,100 Mio h all other models: >1,300 Mio h Safety standards Safety approvals - - - - - UL 508 listed UL 1310, class II (15 - 90 W models) IEC 60950-1 2nd, EN 60950-1:2006+ Am1:2010 +Am11:2009 +Am12:2011 EN 50178, EN 60204-1, EN 61558-2-16 CAN/CSA-C22.2 No. 60950-1-07 UL 60950-1 2nd CB report IEC 60950-1 www.tracopower.com/products/tbl-cb.pdf UL certification UL 508 listed (File e181381) www.tracopower.com/products/tbl-ul508.pdf UL certification UL 1310 (File e181381) www.tracopower.com/products/tbl-ul1310.pdf CSA certification UL/CSA 60950-1 www.tracopower.com/products/tbl-csa.pdf SIQ-BG certificate EN 60950-1 ++ www.tracopower.com/products/tbl-siq.pdf Electromagnetic compatibility (EMC), emissions EN 61000-6-3 - Conducted RI suppression on input EN 55022 class B - Radiated RI suppression EN 55022 class B Electromagnetic compatibility (EMC), immunity - Electrostatic discharge (ESD) - Radiated RF field immunity - Electrical fast transient / burst immunity - Surge immunity line - ground - Surge immunity line - line - Surge immunity output - Immunity to conducted RF disturbances - Mains voltage dips and interruptions http://www.tracopower.com EN 61000-6-2 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-5 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 4 kV / 8 kV 3 V/m 1 kV / 0.5 kV 2 kV 1 kV 0.5 kV 3V 30 % /10 mS, 60 % /100 mS Page 2 of 3 Industrial Power Supplies TBL Series 15 to 150 Watt General Specifications Protection class class II as per IEC/EN 61140 Case protection IP 20 (IEC 60529) Environment - Vibration acc. IEC 60068-2-6; - Shock acc. IEC 60068-2-27 Enclosure material 3 axis, sine sweep, 10 - 55 Hz, 0.075 mm 3 axis, 15 g half sine, 11 ms plastic FR2010-110C (UL 94V-0 rated) Mounting DIN-rails as per EN 50022-35x15/7.5 (snap-on with self-locking spring or wall mounting with bracket) (included) Connection screw terminals with combi-type screw heads for wire size 0.5 - 1.5 mm Installation instructions www.tracopower.com/products/tbl-inst.pdf Environmental compliance - Reach www.tracopower.com/products/tbl-reach.pdf - RoHS RoHS directive 2011/65/EU Case Dimensions TBL 015 26.3 (1.04) 100 (3.53) TBL 030 52.5 (2.07) 160 (5.64) TBL 060 70.0 (2.76 230 (8.11) TBL 090 105.0 (4.13) 340 (12.0) TBL 150 175 (6.89) 625 (22.0) 59.5 (2.34) 37.1 (1.46) 21.1 (0.83) Vadj 89.5 (3.52) Weigth g (oz) 69.5 (2.74) Width (W) mm (inch) 45.0 (1.77) Model 54.5 (2.15) W Dimensions in [mm], () = Inch Tolerances: 0.5 mm (0.02) Wall Mounting Bracket Instead on a DIN-rail, the modules can be also mounted on a chassis or wall with help of a mounting bracket which is supplied as standard with each power supply Wiring Description Wire size AC Input all models: L, N only (2 pin terminal) AWG 26 - 16 / 1.5 mm max. DC Output 15 - 30 W models: single terminal AWG 26 - 14 / 1.5 mm max. DC Output 60 - 150 W models: double terminal AWG 26 - 14 / 1.5 mm max. Specifications can be changed any time without notice. Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com www.tracopower.com Rev. December 13. 2013 Page 3 of 3