Auxiliary Contact Blocks
Front Mounting
Application
The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits.
Description
Types of auxiliary contact blocks in standard version for general use:
CA... 1 or 4-pole block, instantaneous with N.O., N.C. contacts.
CC... 1-pole block, with N.O. leading contact or N.C. lagging contact.
Type of auxiliary contact block for low current and voltage levels (PLC's outputs) and for use in dusty or humid
environments:
CE... 1-pole block, instantaneous with N.O. contact or N.C. contact, designed in 2 protection versions:
CE 5-.. D with built-in microswitch IP 40, degree of protection (IP 20 on terminals)
CE 5-.. W with bulit-in microswitch IP 67, degree of protection (IP 20 on terminals).
The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected
against accidental direct contact and bear the corresponding function marking.
Fitting Details
Refer to the table below
For further information about fitting details compatibility with contactors and other types of accessories please refer to:
- page 4/37 for A... and AF... 3-pole contactors - page 4/38 for AE..., TAE..., BC... and TBC... 3-pole contactors
- page 4/39 for AE... and TAE... 4-pole contactors - page 4/40 for BC... and TBC... 4-pole contactors
- page 3/15 for N... and NE..., KC... and TKC... contactor relays
Ordering Details
For Max. Contacts Type Order code Packing Weight
contactors number blocks pieces kg
of blocks
1-pole auxiliary contact blocks
1 CA 5-10 1SBN 01 0010 R1010 10 0.014
1 CA 5-01 1SBN 01 0010 R1001 10 0.014
1 CC 5-10 1SBN 01 0011 R1010 10 0.014
1 CC 5-01 1SBN 01 0011 R1001 10 0.014
1 CE 5-10 D 0.1 1SBN 01 0015 R1010 1 0.020
1 CE 5-01 D 0.1 1SBN 01 0015 R1001 1 0.020
1 CE 5-10 D 2 1SBN 01 0017 R1010 1 0.020
1 CE 5-01 D 2 1SBN 01 0017 R1001 1 0.020
1 CE 5-10 W 0.1 1SBN 01 0016 R1010 1 0.020
1 CE 5-01 W 0.1 1SBN 01 0016 R1001 1 0.020
1 CE 5-10 W 2 1SBN 01 0018 R1010 1 0.020
1 CE 5-01 W 2 1SBN 01 0018 R1001 1 0.020
4-pole auxiliary contact blocks
4 CA 5-40 E 1SBN 01 0040 R1040 2 0.060
3 1 CA 5-31 E 1SBN 01 0040 R1031 2 0.060
2 2 CA 5-22 E 1SBN 01 0040 R1022 2 0.060
0 4 CA 5-04 E 1SBN 01 0040 R1004 2 0.060
1 1 1 1 CA 5-11/11 E 1SBN 01 0040 R1018 2 0.060
3 1 CA 5-31 M 1SBN 01 0040 R1131 2 0.060
A 9 ... A 40-30-10 .......... 1 block
2 2 CA 5-22 M 1SBN 01 0040 R1122 2 0.060
BC 9 ... BC 25-30-10 ..... 1 block
0 4 CA 5-04 M 1SBN 01 0040 R1104 2 0.060
1 1 1 1 CA 5-11/11 M 1SBN 01 0040 R1118 2 0.060
4 CA 5-40 N 1SBN 01 0040 R1240 2 0.060
3 1 CA 5-31 N 1SBN 01 0040 R1231 2 0.060
2 2 CA 5-22 N 1SBN 01 0040 R1222 2 0.060
0 4 CA 5-04 N 1SBN 01 0040 R1204 2 0.060
(1) In mounting position 5, there should be no more than 2 N.C. front-mounted auxiliary contacts on types A 9 to A 40-30-01, A9 to A 26-22-00,
A 30-30-32, A 40-30-32, N 22 E, N 31 E. The side-mounted blocks offer additional N.C. contacts.
Whatever the mounting position, there should be no more than 2 N.C. front-mounted auxiliary contacts on types A 45 to A 75-22-00.
The side-mounted blocks offer additional N.C. contacts.
Note: The auxiliary contact blocks provided for the A... contactors can be used for the UA..., GA... and GAE types.
A 9 ... A 26
(1)
................ 4 blocks
A 30, A 40
(1)
................. 5 blocks
A 45 ... A 110 ............... 6 blocks
AF 50 ... AF 110 .......... 6 blocks
AE 9 ... AE 26 .............. 4 blocks
AE 30, AE 40 ............... 5 blocks
AE 45 ... AE 110 .......... 6 blocks
TAE 45 ... TAE 110 ..... 6 blocks
BC 9 ... BC 30 ............. 4 blocks
TBC 9 ... TBC 30 ......... 4 blocks
KC .., TKC ................... 4 blocks
N ..
(1)
, NE ..................... 4 blocks
A 9 ... A 26-40-00 .......... 1 block
A 45 ... A 110 ................ 1 block
AE 9 ... AE 26-40-00 ..... 1 block
AE 45 ... AE 110 ............ 1 block
BC 9 ... BC 25-40-00 ..... 1 block
BC 30-30-00 .................. 1 block
N and KC 4-pole ............ 1 block
4
Low Voltage Products 4/3
1SBC100122C0201
L
l
Auxiliary Contact Blocks
Front Mounting
Technical Data
Types 1-pole CA 5, 4-pole CA 5, 1-pole CC 5 1-pole CE 5-..0.1 1-pole CE 5-..2
Compliance with standards IEC 60947-5-1 and EN 60947-5-1
Certification and approvals section 7
Rated insulation voltage Ui
according to IEC 60947-5-1 V690 250 250
according to UL/CSA V600 250 250
Rated operational voltage UeV a.c. 24 to 690 125 250
Conventional thermal current Ith A16 0.1 2
Rated operational current Ie
according to IEC 60947-5-1
in a.c. AC-15 AC-14 AC-15
24 to 127 V A6 0.1 2
220 to 240 V A42
380 to 440 V A3––
500 to 690 V A2––
in d.c. DC-13 DC-12 DC-12
24 V A6 0.1 2
48 V A2.8 0.1 1
72 V A1 0.1 0.3
110 V A0.55 0.1 0.2
125 V A0.55 0.2
220 V A0.3 0.1
250 V A0.3 ––
Short circuit protection A 10 (gG fuses) 0.1 (FF fuses*) 10 (FF fuses*)
Rated making capacity 10 x Ie AC-15 6 x Ie AC-14 10 x Ie AC-15
Rated breaking capacity 10 x Ie AC-15 6 x Ie AC-14 10 x Ie AC-15
Rated short-time withstand current I
cw
1 s A100 ––
θ = 40 °C 0.1 s A140 ––
Power loss per pole at 6 A W 0.15 ––
Min. switching capacity V / mA 17 / 5 (A 9 ... A 75) - 24 / 50 (A 95, A 110) 3 / 1 17 / 5
Reliability for min. switching capacity 10-8 10-8
Mechanical durability
millions of operating cycles 10 (A 9 ... A 75) 3 (A 95, A 110) 5 for CE 5-.. D 5 for CE 5-.. D
2.5 for CE 5-.. W 2.5 for CE 5-.. W
max. mech. switching frequency cycles/h 3600 3600 3600
Electrical durability
millions of operating cycles page 4/35 2.5 for CE 5-.. D 0.1 1 for CE 5-.. D 2
0.7 for CE 5-.. W 0.1 0.3 for CE 5-.. W 2
max. elec. switching frequency cycles/h 1200 1200 1200
Connecting terminals (Delivered in open position. M3.5 (+,-) pozidriv 2 screw with cable clamp
Screws of unused terminals should be tightened.)
Tightening torque
recommended Nm 1.00
max. Nm 1.20
Connecting capacity (min. ... max.)
Rigid solid 1 or 2 x mm21 ... 4
Flexible with cable end 1 or 2 x mm20.75 ... 2.5
Lugs L mm <8
l mm > 3.7
Degree of protection acc. to IEC 60529, IP 20 for the terminals
IEC 60144, DIN 40050 and NFC 20-010
* HRC fuses for very fast action (6.3 x 32 mm size)
>> Terminal Marking and Positioning ............................................................. section 8 >> Dimensions .................................................................................................. section 9
4/4 Low Voltage Products
1SBC100122C0201
SB7375C2
CAL 5-11
Auxiliary Contact Blocks
Side Mounting
Application
The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits.
Description
Types of auxiliary contacts blocks in standard version for general use:
CAL... 2-pole block instantaneous N.O. + N.C. contacts.
CCL ... 2-pole block N.O. leading + N.C. lagging contacts.
The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected
against accidental direct contact, and bear the corresponding function marking.
Fitting Details
Clipped onto the right and/or lefthand side of the contactors.
The CAL 5-11B is a second block for mounting in addition to a first CAL 5-11 block, right and/or lefthand of the
A 145 ... A 300 and AF 145 ... AF 750 contactors.
Refer to the table below
For further information about fitting details compatibility with contactors and other types of accessories please refer to:
- page 4/37 for A... and AF... 3-pole contactors - page 4/38 for AE..., TAE... 3-pole contactors
- page 4/39 for AE... and TAE... 4-pole contactors - page 3/15 for N... and NE... contactor relays
Ordering Details
For Max. Contacts Type Order code Packing Weight
contactors number blocks pieces kg
of blocks
1 piece
2-pole auxiliary contacts N.O. + N.C.
A 9 ... A 110 ............
2 blocks
A 145 ... A 300 ........
2 blocks
(1)
AF 50 ... AF 110 .....
2 blocks
AF 145 ... AF 750 ...
2 blocks
(1)
AE 9 ... AE 40 .........
2 blocks
1 1 CAL 5-11 1SBN 01 0020 R1011 2 0.050
AE 45 ... AE 110 .....
1 block
TAE 45 ... TAE 110 ...
1 block
N .............................
2 blocks
NE ...........................
1 block
A 145 ... A 300 ........
2 blocks
(1)
1 1 CAL 5-11B 1SBN 01 0420 R3311 2 0.050
AF 145 ... AF 750 ...
2 blocks
(1)
N.O. leading + N.C. lagging contacts
A 9 ... A 16 ..............
2 blocks
AE 9 ... AE 16 .........
2 blocks
1 1 CCL 5-11 1SBN 01 1421 R1008 2 0.050
N .............................
2 blocks
NE .............................. 2 blocks
(1) 2 blocks CAL 5-11 + 2 blocks CAL 5-11 B
Notes: The auxiliary contact blocks provided for the A... contactors can be used for the UA... and UA..-R contactors.
Only one contact block can be mounted on GA... type.
>> Auxiliary Contacts for Safety Circuits ................ page 7/4 >> Front Mounted Aux. Contact Blocks .................. page 4/2
>> Mounting and Compatibility of Accessories ............................................................................................................ pages 4/37 to 4/39
4
Low Voltage Products 4/5
1SBC100122C0201
L
l
Technical Data
Types CAL 5-11 CAL 5-11B CCL 5-11 (1)
Compliance with standards IEC 60947-5-1, EN 60947-5-1
Certification and approvals section 7
Rated insulation voltage Ui
according to IEC 60947-5-1 V690
according to UL/CSA V690
Rated operational voltage UeV a.c. 24 to 690
Conventional free air thermal current Ith A16
Rated operational current Ie acc. to IEC 60947-5-1
AC-15 24-127 V a.c. A6
220-240 V a.c. A4
380-440 V a.c. A3
500-690 V a.c. A2
DC-13 24 V d.c. A6
48 V d.c. A2.8
72 V d.c. A1
125 V d.c. A0.55
250 V d.c. A0.3
Short-circuit protection - gG type fuses A10
Rated making capacity 10 x Ie AC-15
Rated breaking capacity 10 x Ie AC-15
Rated short-time withstand current Icw 1 s A100
θ = 40 °C 0.1 s A140
Power loss per pole at 6 A W 0.15
Min. switching capacity V / mA 17 / 5 (A 9 ... A 75) - 24 / 50 (A 95 ... AF 750)
Mechanical durability
– millions of operating cycles 10 millions (A 9 ... A 75), 3 millions (A 95 ... A 110), 2 millions (A 145 ... AF 750)
– max. mech. switching frequency cycles / h 3600
Electrical durability
– millions of operating cycles page 4/35
– max. elec. switching frequency cycles / h 1200
Connecting terminals (Delivered in open position. M3.5 (+,-) pozidriv 2 screw with cable clamp
Screws of unused terminals should be tightened.)
Tightening torque
– recommended Nm 1.00
– max. Nm 1.20
Connecting capacity (min. ... max.)
Rigid solid 1 or 2 x mm21 ... 4
Flexible with cable end 1 or 2 x mm20.75 ... 2.5
Lugs L mm 8
l mm > 3.7
Degree of protection according to IEC 60529, IP 20
IEC 60144, DIN 40050 and NFC 20-010
(1) CCL 5-11 auxiliary contact, only for A 9 ... A 16 and AE 9 ... AE 16 contactors and N... contactor relays.
Auxiliary Contact Blocks
Side Mounting
>> Terminal Marking and Positioning ............................................................. section 8 >> Dimensions .................................................................................................. section 9