Product data sheet
Characteristics
RXM4AB2P7
Miniature Plug-in relay - Zelio RXM 4 C/O 230 V
AC 6 A with LED
Product availability : Stock - Normally stocked in distribution facility
Price* : 8.30 USD
Main
Range of product Zelio Relay
Series name Miniature
Product or component type Plug-in relay
Device short name RXM
Contacts type and composition 4 C/O
[Uc] control circuit voltage 230 V AC, 50/60 Hz
[Ithe] conventional enclosed thermal
current
6 Aat -40...131 °F (-40...55 °C)
Status LED With
Control type Lockable test button
Utilisation coefficient 20 %
Complementary
Shape of pin Flat
[Ui] rated insulation voltage 250 V conforming to IEC
300 V conforming to UL
300 V conforming to CSA
[Uimp] rated impulse withstand voltage 2.5 kV for 1.2/50 µs
Contacts material AgNi
[Ie] rated operational current 3 A at 28 V DC (NC) conforming to IEC
3 A at 250 V AC (NC) conforming to IEC
6 A at 28 V DC (NO) conforming to IEC
6 A at 250 V AC (NO) conforming to IEC
6 A at 277 V AC conforming to UL
8 A at 30 V DC conforming to UL
Maximum switching voltage 250 V conforming to IEC
Load current 6 A at 250 V AC
6 A at 28 V DC
2
Maximum switching capacity 1500 VA/168 W
Minimum switching capacity 170 mW at 10 mA, 17 V
Operating rate <= 18000 cycles/hour no-load
<= 1200 cycles/hour under load
Mechanical durability 10000000 cycles
Electrical durability 100000 cycles resistive load
Average coil consumption in VA 1.2 at 60 Hz
Average consumption 1.2 VA 60 Hz
Drop-out voltage threshold >= 0.15 Uc
Operating time 20 ms
Reset time 20 ms
Average resistance 15000 Ohm at 20 °C +/- 15 %
Rated operational voltage limits 184...253 V AC
Safety reliability data B10d = 100000
Protection category RT I
Operating position Any position
CAD overall height 82.8 mm
CAD overall depth 80.35 mm
Product weight 0.08 lb(US) (0.037 kg)
Device presentation Complete product
Environment
Dielectric strength 1300 V AC between contacts with micro disconnection insulation
2000 V AC between coil and contact with reinforced insulation
2000 V AC between poles with basic insulation
Product certifications GOST
CSA
REACH
UL
Lloyd's
CE
RoHS
Standards CSA C22.2 No 14
EN/IEC 61810-1
UL 508
Ambient air temperature for storage -40...185 °F (-40...85 °C)
Ambient air temperature for operation -40...131 °F (-40...55 °C)
Vibration resistance 3 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles in operation)
5 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles not operating)
IP degree of protection IP40 conforming to EN/IEC 60529
Shock resistance 10 gn in operation
30 gn not operating
Pollution degree 2
Ordering and shipping details
Category 21127 - ZELIO ICE CUBE RELAYS
Discount Schedule CP2
GTIN 00785901871781
Nbr. of units in pkg. 10
Package weight(Lbs) 8.0000000000000002E-2
Returnability Y
Country of origin ID
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0801 - Schneider Electric declaration of conformity
3
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
4
Product data sheet
Dimensions Drawings
RXM4AB2P7
Dimensions
Pin Side View
5
Product data sheet
Connections and Schema
RXM4AB2P7
Wiring Diagram
Symbols shown in blue correspond to Nema marking.
6
Product data sheet
Performance Curves
RXM4AB2P7
Electrical Durability of Contacts
Durability (inductive load) = durability (resistive load) x reduction coefficient.
Resistive AC load
X Switching capacity (kVA)
Y Durability (Number of operating cycles)
A RXM2AB•••
B RXM3AB•••
C RXM4ΑΒ•••
D RXM4GΒ•••
Reduction coefficient for inductive AC load (depending on power factor cos ϕ)
Y Reduction coefficient (A)
Maximum switching capacity on resistive DC load
X Voltage DC
Y Current DC
A RXM2AB•••
B RXM3AB•••
C RXM4ΑΒ•••
D RXM4GΒ•••
Note : These are typical curves, actual durability depends on load, environment, duty cycle, etc.