PGFI Series - 40, 50, 60 Amp Portable (Cord) Series
278
PGFI Series
40, 50 & 60 Amp Portable Series (Cord) ELCI
INTRODUCTION
The LineGard™ 40, 50 and 60 Amp Portable Series is an industrial grade ground fault interrupter device designed and manufactured by
North Shore Safety, Ltd., a leader in innovated safety products. These devices are designed for industrial and trade applications such
as welders, pumps, motors and generators and come standard with selectable key switching for fault level threshold, power on and
reset type (automatic vs. manual) settings.
As configured the device has three fault threshold settings of 6mA, 10mA and 30mA, with all engineered trip times of 25mS or less.
These units come standard with a 6’ primary cord and a 6’ secondary cord length with flying leads for field configuring. Integrated
NEMA or IEC 309 wiring devices are also available as factory customs. The enclosure is configured with floor mount feet but is
additionally supplied with wall or surface mounted feet for more permanent installations. All units are MADE IN THE USA and are UL
1053 Compliant.
• Powerandfaultstatusindicators
• Doubleinsulateduserinterface
• UL1053compliant
• ChemicalandUVresistantenclosure
• 40,50and60ampconfigurationsin1Ø120VAC,
1Ø240VAC,1Ø208VAC,1Ø277VAC,120/240VAC,
3Ø240VAC,3Ø208VAC,3Ø277(Availablewithor
withoutneutral),3Ø480VAC,3Ø600VAC
• Faultlevelkeyswitch-max.tripthreshold
6mA, 10mA, and 30mA
• Surgeprotectionoptional
• NEMA4Xwetlocationrated(indoor/outdoor)
• Automaticormanualresetkeyswitch1
SPECIFICATIONS
Rated Supply Voltage 120VAC1Øto600VAC3Ø
Rated Current 40 thru 60 Amps or rating of
wiringdeviceand/orcable
Trip Level Fieldselectablethreshold@
6mA, 10mA and 30mA
Phase Single, dual and three phase
Operating Frequency 60 Hz
Reset Type1Automatic or Manual
Response Time 25mSmax
Operating Temperature –35°C to 66°C
Operating Voltage Range 85%to110%ofratedVAC
Let-Go Voltage 60%ofsupplyvoltage
Open Neutral Protection Trips upon loss of neutral
Grounded Neutral Protection Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
FEATURES
2 Voltage
1 120 VAC 1Ø 2 240 VAC 1Ø
5 480 VAC 3Ø 6 600 VAC 3Ø
7 240 VAC 3Ø 8 208 VAC 3Ø
9 208 VAC 1Ø B 277 VAC 3Ø
C 120/240 VAC D 277 VAC 1Ø
3 Ampacity
4 40 amps
5 50 amps
6 60 amps
4 Power-up
4 Key Switch
Auto / Manual
PGFI - 1 5 4 5 N
Product Type
1
5 Secondary cord
5 6’ Black, SEOOW
6 Connectors
N Flying leads
Contact Sensata for custom integrated connectors
http://airpax.sensata.com/ PGFI Series - 40, 50, 60 Amp Portable (Cord) Series 279
APPLICATION OPPORTUNITIES:
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icingequipment(roofheaters)
RELATED CODES
Confined Space OSHA29CFR1926.404(b)(1)(ii),
OSHA29CFR1926.405(a)(2)(ii)(G)
Construction Sites (NEC 590.6)
Commercial Garages (NEC 511.12)
Outdoor Signs (NEC 600.10)
Fountains & Water
Displays
(NEC680.58)
Spa & Hot Tubs (NEC680.40)
Marinas & Boat Yards (NEC 555.3)
DECISION TABLES
Ground Fault / Equipment Leakage