Extract from the online catalog IB IL AI 2/SF-230 Order No.: 2740818 The illustration shows version IB IL AI 2/SF http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818 Inline analog input terminal block, without accessories, 2 inputs, 0-20 mA, 4-20 mA, 20 mA, 0-10 V, 10 V, 3 dB base frequency at 230 Hz, 2-wire connection method Product notes WEEE/RoHS-compliant since: 08/29/2008 Commercial data GTIN (EAN) 4 017918 574789 sales group K412 Pack 1 pcs. Customs tariff 85389091 Catalog page information Page 72 (AX-2007) http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. Product description The analog Inline input terminals are suited for connecting conventional sensors for the acquisition of current and voltage signals. Particular features of the modules are: - High accuracy of measurement - Extremely rapid acquisition of measurement values PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Page 1 / 6 Feb 8, 2011 IB IL AI 2/SF-230 Order No.: 2740818 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818 - Excellent noise suppression and common mode rejection, and - Measurement value acquisition with a resolution of 16 bits It goes without saying that you also have advantages in handling with the analog Inline input terminals, such as multiwire connection or the automatic contact with the grounding conductor when the terminal is snapped onto the DIN rail. The Inline terminals can be labeled using hinged labeling fields. The fields have insert cards that can be labeled individually to suit the application. Additionally, there is the proven ZBFM-6... Zack strip for labeling the terminal points. Technical data General data Width 12.2 mm Height 136.8 mm Depth 71.5 mm Weight 47 g Mounting type DIN rail Ambient temperature (operation) -25 C ... 55 C Ambient temperature (storage/transport) -25 C ... 85 C Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2) Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 Test section 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min 7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC 50 Hz 1 min 7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min I/O / functional earth ground 500 V AC 50 Hz 1 min Interface Name Inline local bus Type of connection Inline data jumper Transmission speed 500 kbps 500 kBit/s Transmission physics PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Copper Page 2 / 6 Feb 8, 2011 IB IL AI 2/SF-230 Order No.: 2740818 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818 Inline potential routing Communications power UL 7.5 V DC (via voltage jumper) Current consumption from UL max. 60 mA Typ. 45 mA Current consumption from UM 0 A DC Current consumption from US 0 A DC I/O supply voltage UANA 24 V DC Current consumption from UANA max. 18 mA Typ. 13 mA Analog inputs Number of inputs max. 2 (single ended) Connection method 2-wire (shielded) Input name Analog inputs A/D conversion time 120 s (per channel) Resolution A/D 16 bit Limit frequency (3 dB) 40 Hz 230 Hz Data formats IL, IB ST, IB RT, standardized display Measured value representation 16 bits (15 bits + sign bit) Current input signal 0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA Voltage input signal 0 V ... 10 V -10 V ... 10 V Input resistance of voltage input < 220 k Precision 0.02 % Number of inputs 2 (single-ended voltage inputs) Voltage input signal 0 V ... 10 V -10 V ... 10 V Input resistance of voltage input 220 k Number of inputs 2 (single-ended current inputs) Current input signal 0 mA ... 40 mA 4 mA ... 20 mA -20 mA ... 20 mA Input resistance current input PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de 50 0.02 % Page 3 / 6 Feb 8, 2011 IB IL AI 2/SF-230 Order No.: 2740818 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818 Certificates / Approvals Certification CUL, GOST, UL Accessories Item Designation Description 0809492 ESL 62X10 Insert strip for laser printer, lettering field: 62 x 10 mm 2727501 IB IL FIELD 2 Labeling field, width: 12.2 mm 2740245 IB IL SCN 6-SHIELD-TWIN Inline shield connector 2726353 IB IL SCN-6 SHIELD Inline shield connector Marking Plug/Adapter Diagrams/Drawings Connection diagram PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Page 4 / 6 Feb 8, 2011 IB IL AI 2/SF-230 Order No.: 2740818 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818 Block diagram Dimensioned drawing PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Page 5 / 6 Feb 8, 2011 IB IL AI 2/SF-230 Order No.: 2740818 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2740818 Address PHOENIX CONTACT Deutschland GmbH Flachsmarktstr. 8 32825 Blomberg,Germany Phone +49 5235 3 12000 Fax +49 5235 3 41200 http://www.phoenixcontact.de (c) 2011 Phoenix Contact Technical modifications reserved; PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Page 6 / 6 Feb 8, 2011