Data sheet MICROSERIES MRS 24Vuc 1CO C1D2 Weidmuller Interface GmbH & Co. KG Klingenbergstrae 16 D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com Relays of the MICROSERIES are used for isolating and coupling digital signals. They are characterised by the following features: * modular width 6.1 mm * Pluggable relay * Pluggable cross-connection for four voltages in input and output circuits, * innovative retention and ejection aid, * LED operating indicator, reverse polarity protection diode, free-wheeling diode General ordering data Delivery status Available until Type Order No. Version GTIN (EAN) Qty. Alternative product This article will no longer be available in the future. 2016-12-31 MRS 24Vuc 1CO C1D2 8967360000 MICROSERIES, Relay module, No. of contacts: 1 CO contact AgNi, Rated control voltage: 24 V UC 10 %, Continuous current: 6 A, Screw connection 4032248788972 10 pc(s). 1984580000 Creation date September 13, 2018 4:53:56 AM CEST Catalogue status 31.08.2018 / We reserve the right to make technical changes. 1 Data sheet MICROSERIES MRS 24Vuc 1CO C1D2 Weidmuller Interface GmbH & Co. KG Klingenbergstrae 16 D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com Technical data Dimensions and weights Width Height Depth Net weight 6.1 mm 93 mm 94 mm 36.7 g Width (inches) Height (inches) Depth (inches) 0.24 inch 3.661 inch 3.701 inch 40 C / 93 % rel. humidity, no condensation -25 C -40 C -40 C...60 C Operating temperature, max. Storage temperature, max. Operating temperature 55 C 60 C -25 C...55 C 24 V UC 10 % 6.4 mA 15.8 V / 7 V DC Green LED Rated current AC Power rating Pull-in/drop-out current, typ. Protective circuit 11 mA 270 mVA / 154 mW 3.6 mA / 1.3 mA DC Rectifier 250 V AC 250 V 6A 144 W @ 24 V Max. switching voltage, AC Continuous current AC switching capacity (resistive), max. Switch-on delay Min. switching power 250 V 6A 1500 VA < 9 ms 1 mA @ 24 V, 10 mA @ 10 V, 100 mA @ 5 V 1 CO contact (AgNi) Mechanical service life 5 x 106 switching cycles cULus C1D2 No Beige Mounting rail Mechanical switch position indicator TS 35 No Surge voltage category Protection degree Dielectric strength to mounting rail III IP20 Certificate no. (cULusEX) E223527 Temperatures Humidity Operating temperature, min. Storage temperature, min. Storage temperature Input Rated control voltage Rated current DC Pull-in/drop-out voltage, typ. Status indicator Output Rated switching voltage Max. switching voltage, DC Inrush current DC switching capacity (resistive), max. Switch-off delay 9 ms Max. switching frequency at rated load 0.1 Hz Contact data Contact type General data Version Test button Colour Insulation coordination Rated voltage 300 V Pollution severity 2 Creepage and clearance distance input - output 5.5 mm Impulse withstand voltage 4 kV (1.2/50 s) 4 kVeff / 1 min. Further details of approvals / standards Standards DIN EN 50178, UL508 Creation date September 13, 2018 4:53:56 AM CEST Catalogue status 31.08.2018 / We reserve the right to make technical changes. 2 Data sheet MICROSERIES MRS 24Vuc 1CO C1D2 Weidmuller Interface GmbH & Co. KG Klingenbergstrae 16 D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com Technical data Connection data Wire connection method Clamping range, min. Blade size Screw connection 0.5 mm 0.6 x 3.5 mm Clamping range, rated connection Clamping range, max. 2.5 mm 4 mm EC001437 EC001437 30-21-18-01 27-37-16-01 27-37-16-01 27-37-16-01 ETIM 4.0 ETIM 6.0 eClass 5.1 eClass 7.1 eClass 9.0 EC001437 EC001437 27-37-16-01 27-37-16-01 27-37-16-01 Classifications ETIM 3.0 ETIM 5.0 UNSPSC eClass 6.2 eClass 8.1 eClass 9.1 Product information Descriptive text technical data Cross-connectors and markers - refer to MICROSERIES accessories Approvals Approvals ROHS Conform Downloads Engineering Data EPLAN, WSCAD Creation date September 13, 2018 4:53:56 AM CEST Catalogue status 31.08.2018 / We reserve the right to make technical changes. 3 Data sheet MICROSERIES MRS 24Vuc 1CO C1D2 Weidmuller Interface GmbH & Co. KG Klingenbergstrae 16 D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com Drawings Wiring diagram Graph DC load limit curve Creation date September 13, 2018 4:53:56 AM CEST Catalogue status 31.08.2018 / We reserve the right to make technical changes. 4