3
Insulation EN 62053-21 7E.13, 7E.16 7E.36
Insulation rated voltage V 250 250
Overvoltage category IV IV
Isolation between active part SO+/SO– terminals kV (1.2/50 µs) 6 6
adjacent phases kV (1.2/50 µs) — 6
Insulation between supply and SO+/SO– V AC 4,000 4,000
between adjacent phases V AC — 4,000
Protection class II II
EMC Specification Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 8 kV
air discharge EN 61000-4-2 15 kV
Radio-Frequency Electromagnetic Field (80...1,000)MHz EN 61000-4-3 10 V/m
Fast Transients (Burst) (5-50 ns, 5 kHz) on Supply Terminals EN 61000-4-4 Class 4 (4 kV)
on SO+/SO– Terminals EN 61000-4-4 Class 4 (2 kV)
Surge (1.2/50 µs) on Supply Terminals EN 61000-4-5 Class 4 (4 kV)
on SO+/SO– Terminals EN 61000-4-5 Class 3 (1 kV)
Radio-Frequency Common Mode (0.15...80)MHz on Supply terminals EN 61000-4-6 10 V
Radiated and Conducted Emission EN 55022 Class B
Other data
Pollution degree 2
Vibration resistance (10...60)Hz mm 0.075
(60...150)Hz g 1
Vibration resistance of the internal mechanical counter (10...500)Hz g 2
Schock resistance g/18 ms 30
Schock resistance of the internal mechanical counter g/18 ms 350
Power lost to the environment 7E.13 7E.16 7E.36
without current W 0.4 0.4 1.5
with maximum current W 1 2 6
Supply terminals 7E.13 7E.16, 7E.36
Max. wire size solid cable
stranded cable
solid cable
stranded cable
mm2 1...6 0.75...4 1.5...16 1.5...16
AWG 18...10 18...12 16...6 16...6
Screw torque for Imax Nm 0.8...1.2 1.5...2
Screw M4 Pozidrive No.1, Phillips No.1, Flat No.1
SO+/SO– terminals Max. wire size solid cable
stranded cable
solid cable
stranded cable
mm2 2.5 1.5 2.5 1.5
AWG 14 16 14 16
Screw torque for Imax Nm 0.5 0.8
Screw M3 Pozidrive No.1, M4 Pozidrive No.1,
Phillips No.1, Flat No.1 Phillips No.1, Flat No.1
7E Series - Energy meter
Example: Energy meter 32 A/230 V AC, with PTB certified, accuracy class 1, available with Tamper-proof lead sealed cover as accessory,
for 35 mm rail (EN 50022) mounting.
Series
Function
1 = 1-phase
3 = 3-phase
Current
3 = 32 A
6 = 65 A
Supply version
8 = AC 50 Hz
Option
0 = Standard
2 = Dual tariff (7E.36 only)
Supply voltage
230 = 230 V AC 50 Hz
400 = 3 x 230/400 V AC 50 Hz
All versions/width
7E.13.8.230.0000/17.8 mm
7E.16.8.230.0000/35 mm
7E.36.8.400.0000/70 mm
7E.36.8.400.0002/70 mm
1 3 0 08 0 0
Ordering information
... .
2307E
Technical data