7E.13.8.230.0000 7E.16.8.230.0000
Features
kWh Energy meter - 1-phase
Type 7E.13 5(32)A - 1 module wide
Type 7E.16 10(65)A - 2 module wide
Complies with EN 62053-21 and prEN 50470
Complies with the EU MID-directive 2004/22/EG
(Measuring Instruments Directive), mandatory
for meters subject to legal regulation
(from 31 Oct 2006)
Certified by PTB
(Physikalisch - Technischen Bundesanstalt)
Accuracy class 1
Protection class II
Pulse output for remote energy management;
SO interface (open collector) according
DIN 43864 to link the energy meter to a
centrally located monitoring/management system
Tamper-proof cover with lead seal facility
available as an accessory
Space saving small size
35 mm rail (EN 50022) mount
5/32 10/65
0.02 0.04
0.25...32 0.5...65
960 (10 ms) 1,950 (10 ms)
230 230
(0.8...1.15)UN(0.8...1.15)UN
50 50
< 0.4 < 0.5
Seven digit counter, red decimal digit, digit height 4 mm
999,999.9/0.1 999,999.9/0.1
2,000 1,000
5...30 5...30
20 20
10 10
1,000 1,000
50 50
100 100
1,000 1,000
11
–10…+45 –10…+45
–20…+55 –20…+55
II II
IP 50/IP 20 IP 50/IP 20
Nominal current 5 A (32 A Maximum)
1-phase 230 V AC
17.5 mm wide
Nominal current 10 A (65 A Maximum)
1-phase 230 V AC
35 mm wide
7E Series - Energy meter
L
N
N
-SO +SO
+24 V
LL
N
L
N
-SO +SO
+24 V
LL
N
PTB
1
Specification
Nominal/Maximum current measuring A
Minimum measured current A
Current range (within accuracy class) A
Maximum peak current A
Supply (& monitored) voltage V AC
Operating range
Frequency Hz
Rated power W
Display, Reading, Indication
Max. totalising count/Min. totalising count kWh
LED- Pulses per kWh
Open collector- output specification (SO+/SO–)
Voltage (external supply) V DC
Maximum current mA
Maximum leakage current @30 V/25 °C µA
Pulses per kWh
Pulse length ms
Internal series resistance
Maximum Cable length (30 V/20 mA) m
Technical data
Accuracy class
Ambient temperature (Within accuracy class) °C
Ambient temperature (Outside accuracy class) °C
Protective class
Protection category: Housing/terminal
Approvals (according to type)
For outline drawing see page 5
10/65 10/65
0.04 0.04
0.5...65 0.5...65
1,950 (10 ms) 1,950 (10 ms)
3 x 230 3 x 230
(0.8...1.15)UN(0.8...1.15)UN
50 50
< 1.5 < 1.5
Seven digit counter, red decimal digit, digit height 4 mm
999,999.9/0.1 999,999.9/0.1
100 100
5...30 5...30
20 20
10 10
1,000 1,000
50 50
100 100
1,000 1,000
BB
–25…+55 –25…+55
II II
IP 50/IP 20 IP 50/IP 20
7E.36.8.400.0000 7E.36.8.400.0002
7E Series - Energy meter
2
Features
kWh Energy meter - 3-phase
Type 7E.36-0000 10(65)A - Single tariff
Type 7E.36-0002 10(65)A - Dual tariff
Complies with EN 62053-21 and prEN 50470
Complies with the EU MID-directive 2004/22/EG
(Measuring Instruments Directive), mandatory
for meters subject to legal regulation
(from 31 Oct 2006)
Certified by PTB
(Physikalisch - Technischen Bundesanstalt)
Accuracy class B
Protection class II
Pulse output for remote energy management;
SO interface (open collector) according
DIN 43864 to link the energy meter to a
centrally located monitoring/management system
Tamper-proof cover with lead seal facility
available as an accessory
35 mm rail (EN 50022) mount
Nominal current 10 A (65 A Maximum)
3-phase
70 mm wide
Nominal current 10 A (65 A Maximum)
3-phase
Dual tariff (Day and Night)
70 mm wide
L1
L2
L3
N
(PEN)
N
+SO -SO
+24 V
3 x 230 V AC / 50 Hz
1L 1L 2L 2L 3L 3L
L1
L2
L3
N
(PEN)
RT1,T2
NE1E2
+SO -SO
+24 V
3 x 230 V AC / 50 Hz
1L 1L 2L 2L 3L 3L
PTB
Specification
Nominal/Maximum current measuring A
Minimum measured current A
Current range (within accuracy class) A
Maximum peak current A
Supply (& monitored) voltage V AC
Operating range
Frequency Hz
Rated power per phase W
Display, Reading, Indication
Max. totalising count/Min. totalising count kWh
LED- Pulses per kWh
Open collector- output specification (SO+/SO–)
Voltage (external supply) V DC
Maximum current mA
Maximum leakage current @30 V/25 °C µA
Pulses per kWh
Pulse length ms
Internal series resistance
Maximum Cable length (30 V/20 mA) m
Technical data
Accuracy class
Ambient temperature °C
Protective class
Protection category: Housing/terminal
Approvals (according to type)
RT1,T2 = Tariff switching equipment
For outline drawing see page 5
3
Insulation EN 62053-21 7E.13, 7E.16 7E.36
Insulation rated voltage V 250 250
Overvoltage category IV IV
Isolation between active part SO+/SO– terminals kV (1.2/50 µs) 6 6
adjacent phases kV (1.2/50 µs) 6
Insulation between supply and SO+/SO– V AC 4,000 4,000
between adjacent phases V AC 4,000
Protection class II II
EMC Specification Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 8 kV
air discharge EN 61000-4-2 15 kV
Radio-Frequency Electromagnetic Field (80...1,000)MHz EN 61000-4-3 10 V/m
Fast Transients (Burst) (5-50 ns, 5 kHz) on Supply Terminals EN 61000-4-4 Class 4 (4 kV)
on SO+/SO– Terminals EN 61000-4-4 Class 4 (2 kV)
Surge (1.2/50 µs) on Supply Terminals EN 61000-4-5 Class 4 (4 kV)
on SO+/SO– Terminals EN 61000-4-5 Class 3 (1 kV)
Radio-Frequency Common Mode (0.15...80)MHz on Supply terminals EN 61000-4-6 10 V
Radiated and Conducted Emission EN 55022 Class B
Other data
Pollution degree 2
Vibration resistance (10...60)Hz mm 0.075
(60...150)Hz g 1
Vibration resistance of the internal mechanical counter (10...500)Hz g 2
Schock resistance g/18 ms 30
Schock resistance of the internal mechanical counter g/18 ms 350
Power lost to the environment 7E.13 7E.16 7E.36
without current W 0.4 0.4 1.5
with maximum current W 1 2 6
Supply terminals 7E.13 7E.16, 7E.36
Max. wire size solid cable
stranded cable
solid cable
stranded cable
mm2 1...6 0.75...4 1.5...16 1.5...16
AWG 18...10 18...12 16...6 16...6
Screw torque for Imax Nm 0.8...1.2 1.5...2
Screw M4 Pozidrive No.1, Phillips No.1, Flat No.1
SO+/SO– terminals Max. wire size solid cable
stranded cable
solid cable
stranded cable
mm2 2.5 1.5 2.5 1.5
AWG 14 16 14 16
Screw torque for Imax Nm 0.5 0.8
Screw M3 Pozidrive No.1, M4 Pozidrive No.1,
Phillips No.1, Flat No.1 Phillips No.1, Flat No.1
7E Series - Energy meter
Example: Energy meter 32 A/230 V AC, with PTB certified, accuracy class 1, available with Tamper-proof lead sealed cover as accessory,
for 35 mm rail (EN 50022) mounting.
Series
Function
1 = 1-phase
3 = 3-phase
Current
3 = 32 A
6 = 65 A
Supply version
8 = AC 50 Hz
Option
0 = Standard
2 = Dual tariff (7E.36 only)
Supply voltage
230 = 230 V AC 50 Hz
400 = 3 x 230/400 V AC 50 Hz
All versions/width
7E.13.8.230.0000/17.8 mm
7E.16.8.230.0000/35 mm
7E.36.8.400.0000/70 mm
7E.36.8.400.0002/70 mm
1 3 0 08 0 0
Ordering information
... .
2307E
Technical data
Phase L1L1inverted or loss Phase L2L2inverted or loss Phase L3L3inverted or loss
LED indication (Normal operation)
7E Series - Energy meter
4
LED indication (Abnormal operation)
Status indicates errors of installation, as below
Type
7E.13
7E.16
7E.36
Device ON, incorrect connection (L-N inverted). Mark = 600 ms, Space = 600 ms
SO+/SO– Open collector output wiring diagram
The pulsating open collector output available at terminals SO+ and SO– can be interfaced with the input of a computer, plc or other
energy management equipment to allow the remote monitoring of energy consumed.
®®®®®
®®®®®
3 s 3 s 3 s 3 s 3 s ®®®®®
®®®®®
3 s 3 s 3 s 3 s 3 s ®®®®®
®®®®®
3 s 3 s 3 s 3 s 3 s
®®®®®
®®®®®
3 s 3 s 3 s 3 s 3 s
Phase L1L1and L2L2inverted or loss Phase L1L1and L3L3inverted or loss Phase L1L1and L2L2and L3L3
inverted or loss
®®®®®
®®®®®
3 s 3 s 3 s 3 s 3 s ®®®®®
®®®®®
3 s 3 s 3 s 3 s 3 s
Mark = 100 ms,
+
24 V DC
Energy meters – at difference locations
(Note: Both Single and Dual tariff meters
provide only a single pulsating output)
Central monitoring/management system
(max. 20 mA for each input)
Type
7E.13
7E.16
7E.36
Energy consumption
None Low High
Pulses Pulse
per kWh space
2,000 100 ms
1,000 100 ms
100 150 ms
The LED Pulse rate represents
the instantaneous power being
consumed, according to the following
kW = (number of pulse per Minute) / 33.3
kW = (number of pulse per Minute) / 16.7
kW = (number of pulse per Minute) / 1.7
7E Series - Energy meter
07E.13
Terminal cover for type 7E.13 07E.13
For the tamper-proof lead seal use 2 terminal cover
Accessories
07E.16
Terminal cover for type 7E.16 and 7E.36 07E.16
7E.16 - For the tamper-proof lead seal use 2 terminal covers
7E.36 - For the tamper-proof lead seal use 4 terminal covers
Outline drawing
17.5
35.6
89.2
85
62.1
45
23.8
44
58
63
85
82
35
31
58
62
45
7E.13.8.230.0000 7E.16.8.230.0000
82
70
31
58
62
45